Philips GreenSpace User Manual
Displayed below is the user manual for GreenSpace by Philips which is a product in the Spotlights category. This manual has pages.
Related Manuals
DN460B, DN461B DN462B,
DN463B, DN470B, DN471B,
DN472B, DN473B
GreenSpace Downlight
Emergency Lighting
Optional:
Polycarbonate cover
Dimensions in mm
LED driver
Battery
Inverter
B
2
A
IP54
IK06
1 - 20
For versions with polycarbonate cover (PCC)
IP20
74
200
32
197
54
29
208
32
45
74
* In charging mode.
P1
indoor
50Hz
60Hz
220V
240V IK02
Max.
40 °C
Min.
0 °C
GLOW
WIRE
750 °C
IP20
/
© Signify Holding. All rights reserved
Printed in The Netherlands
Data subject to change without notice
Keep for future reference: www.philips.com/lighting
Lumen
(lm)
CCT
(K)
Pmax.
(W)*UGR
IP..
Max.
... °C
Min.
-... °C
A B
Ø mm
kg
DNB
,
/
.
DNB
DNB PCC
DNB PCC
DNB
.
.
DNB
DNB PCC
DNB PCC
DNB
DNB
DNB PCC
DNB PCC
L
NBrown wire
Yellow-Green wire
Blue wire
The luminaire shall, under no circumstance,
be covered with thermal insulation matting or
similar material.
!
1+5
0
Ø See table on 1st page
Trustlight Basic & Pro version
2a
Trustlight DALI version
2b
0.8Nm
P1
150
430 300
Battery
LED
driver
N
NA/Ls
DA/N LED-
LED+
PE
L
Inverter
L
N
swN
swL
swN
swL
Battery+
Battery-
Indicator LED red
Indicator LED green
LED-
LED+
Driver+
Driver-
220-240V
Switched
IA1
driver
PE
LED-
LED+
N
L
N
N
L
L
Cable to
LED driver
Already
installed
DALI
IN
DALI
OUT
Switched IN
220-240V
Mains IN
220-240V
920
L
N
Ø 6-9 mm
2 x 0.50-2.5 mm2
Cable to
LED driver
Already
installed
Mains IN
220-240V
L
L
NN
Swiched
mains
220-240V
0.8Nm
P1
/
Light output in emergency operation mode
(UGR) BLF:
Light output in emergency operation mode
(UGR) BLF:
3
4
DN460B / DN462B 38%DN470B / DN472B 19% DN461B / DN463B 38%DN471B / DN473B 19%
Polar intensity diagram
120° 180°
0°
120°
90°
60°
30°
90°
60°
30°
y
Polar intensity diagram
120° 180°
0°
120°
90°
60°
30°
90°
60°
30°
y
Polar intensity diagram
120° 180°
0°
120°
90°
60°
30°
90°
60°
30°
y
Polar intensity diagram
120° 180°
0°
120°
90°
60°
30°
90°
60°
30°
y
5a 5b
22
11
2
Through-wiring PSE-E / IA1
Through-wiring option:
PSED-E driver in combination
with ELB or ELP inverter
0.8Nm
P1
0.8Nm
P1
Mains IN
220-240V
L
L
NN
Mains OUT
220-240V
Swiched
mains
220-240V
Through-wiring PSED-E
Mains IN
220-240V
L
L
NN
Mains OUT
220-240V
Swiched
mains
220-240V
Swiched
OUT
DALI
OUT
DALI IN
N
L
Cable to
LED driver
Already
installed
Cable to
LED driver
Already
installed
L
N
Through-wiring option:
PSE-E driver in combination
with ELB or ELP inverter
Safety cable
Not included
Emergency ux (lm) Emergency ux (lm)
DNB DNB
DNB DNB
DNB IP DNB IP
DNB IP DNB IP
/
- Charging time: 16h
- Charge current: 130mA
- Battery: NiMH 2500 mAh sC-Cells
- Battery fuse: F4A 250V (fast)
- AC line fuse: T500mA 250V
- Inrush current (Ipeak): 3,2A
- Ipeak (half peak time): 1 msec
- Battery storage temp:
· at 20 - 30°C: max. 6 months
· at 20 - 40°C: max. 1 month
To assure the lighting quality of this unique LED lighting concept there are only a few instructions regarding the maintenance of this
LED luminaire:
- Do not touch electronic components! Electronic components maybe under high voltage.
- Do not stare into LED light beam.
- The luminaire shall be installed by a qualied electrician and wired in accordance with the latest IEE electrical regulations or the
national requirements.
- The batteries have a life time expectancy of 4 years.
- After storage time has passed battery can be revitalize only once by full charging.
- Only to be installed outside arms reach as recessed ceiling luminaire
- The light source of this luminaire is not replaceable, when the light source reaches its end of life the whole luminaire shall be replaced.
Charging
After rst installation (and after each emergency mode operation), the batteries need to be charged for at least 24 hours to become
suciently charged again. If the battery is not completely discharged the required charge time is shorter accordingly. The status of the
battery is given by the indicator LED.
Periodic testing
For TrustSight Basic periodic tests should be performed according to EN 50172:2004, clause 7.2.3 and 7.2.4. monthly, switch on in the
emergency mode by simulation of a failure of the supply to the normal lighting for a period sucient to ensure that each lamp is
illuminated. Annually, each luminaire shall be tested for its full rated duration (at least 1hr or 3hrs (depending on product installed).
Self-Test
The TrustSight Pro and DALI versions are equipped with a self-test functionality according IEC 62034. At 28 days after power-up the
TrustSight will perform a functional test of 30 seconds. Every 6th test (after half year) will be a duration test. This test will run until the
battery is empty and it will check if the capacity of the battery is sucient to provide 1hr or 3hrs emergency time for respectively a 1hr or
3hrs system. This will result in 2 full duration tests every year. During the tests the battery and output is checked. During the duration
test also the battery capacity is checked. In case of a failure, an error will be indicated by the indicator LED.
When scheduling a test (functional or duration test) the operation of the AC-driver is also checked. When the AC-driver is active,
so normal lighting is on, the test will be postponed for a maximum of 3 days. When the AC-driver is o for at least 1 hour the test is
started. The functional and duration test can only be started when the battery is fully charged.
Test button:
7&8 connectors
Initiate functional test as
long as switch pressed:
press 0 < time < 10 s
Initiate duration test:
press > 10 s
Luminaire classicatioin:
X1 ---E 180
self-contained
maintained
Including test device
non replaceable lamp/battery
duration of emergency mode [min]
X:
1:
A:
E:
180:
10
2 x 0.50-1.5 mm2
Test button
Maintained
AC LED driver
L N
Inverter
DA
out
DA
out
DA
in
DA
in
SWN
out
SWL
out
SWN
IN
SWL
IN
NL LED module
DALI
DALI
L
N
SW N
SW L
1, switch o
Switched mains
For periodic testing switch o mains (1)
Permanent
mains
Test button is not supplyed with the luminaire.
For launch testing connect testbutton here.
2, push test button
87
10 987654321
The battery should be replaced when it no
longer meets the rated duration of operation
after the corresponding recharge period.
The batteries have a life time expectancy of
4 years.
Light source (LED) is not replaceable.
1.) Disconnect the old battery
2. Reconnect the new battery
Service: (Driver/battery replacement)
I mains (A)
I nom.
Time (us)
Tref
max/2
I max
Inrush current
/
PSE-E PSED-E IA1
20W 36W 20W 36W 36W
Electrical characteristics
Imax (A) 15.8 16 20.4 20.4 12
Tref (µs) 224 216 195 195 250
MCB Luminaires max.
B-10 A 22 22 15 15 15
B-16 A 36 36 24 24 24
C-10 A 37 37 25 25 25
C-16 A 61 61 40 40 40