Samsung AC052HBMDKH/EU User Manual
Displayed below is the user manual for AC052HBMDKH/EU by Samsung which is a product in the Split-System Air Conditioners category. This manual has pages.
Related Manuals
2
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
(Applicable in the countries with separate collection systems)
This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g. charger, headset, USB
cable) should not be disposed of with other household waste at the end of their working life. To prevent possible harm to the environment
or human health from uncontrolled waste disposal, please separate these items from other types of waste and recycle them responsibly to
promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local government office, for details of where
and how they can take these items for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This product and its electronic
accessories should not be mixed with other commercial wastes for disposal.
Safety precautions ......................................................................... 3
Checking before use ..................................................................... 9
Viewing the parts ........................................................................ 11
Cleaning and maintaining the air conditioner .............. 12
Appendix ........................................................................................ 17
Cool Summer Oer
On those hot sweltering summer days and long restless
nights, there is no better escape from the heat than the
cool comforts of home. Your new air conditioner brings an
end to exhausting hot summer days and lets you rest.
This summer, beat the heat with your own air conditioner.
Cost Ecient System
Your new air conditioner not only provides maximum
cooling power in the summer, but can also be an ecient
heating method in the winter with the advanced “Heat
pump” system. This technology is up to 300% more
ecient than electrical heating, so you can further reduce
its running cost. Now, meet year-round needs with one air
conditioner.
Flexible installation
Duct type air conditioner is designed to be slimmer and
oers dierent solutions for any shape room allowing for
specic air ow requirements. Also, the air intake can be
set up on either the bottom or rear of the unit, so there is
more exibility in installation.
Features of your new air conditioner
Contents
For information on Samsung’s environmental commitments and product specic regulatory obligations e.g. REACH visit:
samsung.com/uk/aboutsamsung/samsungelectronics/corporatecitizenship/data_corner.html
3
ENGLISH
Safety precautions
Before using your new air conditioner, please read this manual thoroughly to ensure that
you know how to safely and eciently operate the extensive features and functions of your
new appliance.
Because the following operating instructions cover various models, the characteristics of
your air conditioner may dier slightly from those described in this manual. If you have any
questions, call your nearest contact center or nd help and information online at www.
samsung.com.
Important safety symbols and precautions:
WARNING
Hazards or unsafe practices that may result in severe personal injury
or death.
CAUTION
Hazards or unsafe practices that may result in minor personal injury
or property damage.
Follow directions.
Do NOT attempt.
Make sure the machine is grounded to prevent electric shock.
Unplug the power plug from the wall socket.
Do NOT disassemble.
FOR INSTALLATION
WARNING
Use the power line with the power specications of the product or higher and use
the power line for this appliance only. In addition, do not use an extension line.
Extending the power line may result in electric shock or fire.
Do not use an electric transformer. It may result in electric shock or fire.
If the voltage/frequency/rated current condition is different, it may cause fire.
The installation of this appliance must be performed by a qualied technician or
service company.
Failing to do so may result in electric shock, fire, explosion, problems with the
product, or injury.
Install a switch and circuit breaker dedicated to the air conditioner.
Failing to do so may result in electric shock or fire.
Fix the outdoor unit rmly so that the electric part of the outdoor unit is not exposed.
Failing to do so may result in electric shock or fire.
4
Safety precautions
FOR INSTALLATION
WARNING
Do not install this appliance near a heater, inammable material. Do not install
this appliance in a humid, oily or dusty location, in a location exposed to direct
sunlight and water (rain drops). Do not install this appliance in a location where
gas may leak.
This may result in electric shock or fire.
Never install the outdoor unit in a location such as on a high external wall where it
could fall.
If the outdoor unit falls, it may result in injury, death or property damage.
This appliance must be properly grounded. Do not ground the appliance to a gas
pipe, plastic water pipe, or telephone line.
Failure to do so may result in electric shock, fire, an explosion, or other problems with
the product.
Never plug the power cord into a socket that is not grounded correctly and make
sure that it is in accordance with local and national codes.
FOR INSTALLATION
CAUTION
Install your appliance on a level and hard oor that can support its weight.
Failing to do so may result in abnormal vibrations, noise, or problems with the
product.
Install the draining hose properly so that water is drained correctly.
Failing to do so may result in water overflowing and property damage.
When installing the outdoor unit, make sure to connect the draining hose so that
draining is performed correctly.
The water generated during the heating operation by the outdoor unit may overflow
and result in property damage.
In particular, in winter, if a block of ice falls, it may result in injury, death or property
damage.
5
ENGLISH
FOR POWER SUPPLY
WARNING
When the circuit breaker is damaged, contact your nearest service center.
Do not pull or excessively bend the power line. Do not twist or tie the power line.
Do not hook the power line over a metal object, place a heavy object on the power
line, insert the power line between objects, or push the power line into the space
behind the appliance.
This may result in electric shock or fire.
FOR POWER SUPPLY
CAUTION
When not using the air conditioner for a long period of time or during a thunder/
lightning storm, cut the power at the circuit breaker.
Failing to do so may result in electric shock or fire.
FOR USING
WARNING
If the appliance is ooded, please contact your nearest service center.
Failing to do so may result in electric shock or fire.
If the appliance generates a strange noise, a burning smell or smoke, unplug the
power plug immediately and contact your nearest service center.
Failing to do so may result in electric shock or fire.
In the event of a gas leak (such as propane gas, LP gas, etc.), ventilate immediately
without touching the power line.
Do not touch the appliance or power line.
Do not use a ventilating fan.
A spark may result in an explosion or fire.
To reinstall the air conditioner, please contact your nearest service center.
Failing to do so may result in problems with the product, water leakage, electric
shock, or fire.
A delivery service for the product is not provided. If you reinstall the product in
another location, additional construction expenses and an installation fee will be
charged.
Especially, when you wish to install the product in an unusual location such as in
an industrial area or near the seaside where it is exposed to the salt in the air, please
contact your nearest service center.
6
Safety precautions
FOR USING
WARNING
Do not touch the circuit breaker with wet hands.
This may result in electric shock.
Do not strike or pull the air conditioner with excessive force.
This may result in fire, injury, or problems with the product.
Do not place an object near the outdoor unit that allows children to climb onto
the machine.
This may result in children seriously injuring themselves.
Do not turn the air conditioner o with the circuit breaker while it is operating.
Turning the air conditioner off and then on again with the circuit breaker may cause a
spark and result in electric shock or fire.
After unpacking the air conditioner, keep all packaging materials well out of the
reach of children, as packaging materials can be dangerous to children.
If a child places a bag over its head, it may result in suffocation.
Do not insert your ngers or foreign substances into the outlet when the air
conditioner is operating or the front panel is closing.
Take special care that children do not injure themselves by inserting their fingers into
the product.
Do not touch the front panel with your hands or ngers during the heating
operation.
This may result in electric shock or burns.
Do not insert your ngers or foreign substances into the air inlet/outlet of the air
conditioner.
Take special care that children do not injure themselves by inserting their fingers into
the product.
Do not use this air conditioner for long periods of time in badly ventilated
locations or near inrm people.
Since this may be dangerous due to a lack of oxygen, open a window at least once an
hour.
7
ENGLISH
FOR USING
WARNING
If any foreign substance such as water has entered the appliance, cut the power by
unplugging the power plug and turning the circuit breaker o and then contact
your nearest service center.
Failing to do so may result in electric shock or fire.
Do not attempt to repair, disassemble, or modify the appliance yourself.
Do not use any fuse (such as cooper, steel wire, etc.)other than the standard fuse.
Failing to do so may result in electric shock, fire, problems with the product, or injury.
FOR USING
CAUTION
Do not place objects or devices under the indoor unit.
Water dripping from the indoor unit may result in fire or property damage.
Check that the installation frame of the outdoor unit is not broken at least once a
year.
Failing to do so may result in injury, death or property damage.
Max current is measured according to IEC standard for safety and current is
measured according to ISO standard for energy eciency.
Do not stand on top of the appliance or place objects (such as laundry, lighted
candles, lighted cigarettes, dishes, chemicals, metal objects, etc.) on the appliance.
This may result in electric shock, fire, problems with the product, or injury.
Do not operate the appliance with wet hands.
This may result in electric shock.
Do not spray volatile material such as insecticide onto the surface of the appliance.
As well as being harmful to humans, it may also result in electric shock, fire or
problems with the product.
Do not drink the water from the air conditioner.
The water may be harmful to humans.
Do not apply a strong impact to the remote controller and do not disassemble the
remote controller.
Do not touch the pipes connected with the product.
This may result in burns or injury.
8
Safety precautions
FOR USING
CAUTION
Do not use this air conditioner to preserve precision equipment, food, animals,
plants or cosmetics, or for any other unusual purposes.
This may result in property damage.
Avoid directly exposing humans, animals or plants from the air ow from the air
conditioner for long periods of time.
This may result in harm to humans, animals or plants.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
For use in Europe : This appliance can be used by children aged from 8 years
and above and persons with reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe way and understand the
hazards involved. Children shall not play with the appliance. Cleaning and user
maintenance shall not be made by children without supervision.
FOR CLEANING
WARNING
Do not clean the appliance by spraying water directly onto it. Do not use benzene,
thinner or alcohol to clean the appliance.
This may result in discoloration, deformation, damage, electric shock or fire.
Before cleaning or performing maintenance, unplug the air conditioner from the
wall socket and wait until the fan stops.
Failing to do so may result in electric shock or fire.
FOR CLEANING
CAUTION
Take care when cleaning the surface of the heat exchanger of the outdoor unit
since it has sharp edges.
To avoid cutting your fingers, wear thick cotton gloves when cleaning it.
Do not clean the inside of the air conditioner by yourself.
For cleaning inside the appliance, contact your nearest service center.
When cleaning the internal filter, refer to the descriptions in the ‘Cleaning and
maintaining the air conditioner’ section.
Failure to do may result in damage, electric shock or fire.
9
ENGLISH
Checking before use
Operation ranges
The table below indicates the temperature and humidity ranges the air conditioner can
be operated within.
Refer to the table for ecient use.
• Thestandardizedtemperatureforheatingis7˚C/45˚F.Iftheoutdoortemperaturedropsto0˚C/32˚Forbelow,the
heating capacity can be reduced depending on the temperature condition.
Ifthecoolingoperationisusedatover32˚C/90˚F(indoortemperature),itdoesnotcoolatitsfullcapacity.
NOTE
•
Theuseoftheairconditioneratarelativehumidityabovetheexpectedone(80%)may
cause the formation of condensate and the leakage of water drops on the oor.
CAUTION
MODE OUTDOOR TEMPERATURE INDOOR TEMPERATURE INDOOR HUMIDITY
COOLING -15°C/5°Fto50°C/122°F 18°C/64°Fto32°C/90°F
80%orlessHEATING -20°C/-4°Fto24°C/75°F 27°C/81°Ftoless
DRYING -15°C/5°Fto50°C/122°F 18°C/64°Fto32°C/90°F
Maintaining your air conditioner
Internal protections via the unit control system
This internal protection operates if an internal fault occurs in the air conditioner.
Type Description
Against cold air The internal fan will be o to against cold air when the heat pump is heating.
De-ice cycle
(Defrost cycle) The internal fan will be o to against cold air when the heat pump is heating.
Anti-protection of
internal battery
The compressor will be o to protect internal battery when the air conditioner operates
in Cool mode.
Protect compressor The air conditioner does not start operating immediately to protect the compressor of
the outdoor unit after it has been started.
• IftheheatpumpisoperatinginHeatmode,De-icecycleisactuatedtoremovefrostfromanoutdoorunitthatmay
have deposited at low temperatures.
The internal fan is switched o automatically and restarted only after the de-ice cycle is completed.
NOTE
10
Checking before use
Tips on using air conditioner
Here are some tips that you would follow when using your air conditioner.
TOPIC RECOMMENDATION
Cooling • Ifcurrentoutsidetemperaturesaremuchhigherthantheselected
indoor temperature, it may take time to bring the inner temperature
to the desired coolness.
• Avoiddrasticallyturningdownthetemperature.Energyiswastedand
the room does not cool faster.
Heating • Sincetheairconditionerheatstheroombytakingheatenergy
from outdoor air, the heating capacity may decrease when outdoor
temperatures are extremely low. If you feel the air conditioner
insuciently heats, using an additional heating appliance in
combination with the air conditioner is recommended.
Frost & De-ice • WhentheairconditionerrunsinHeatmode,duetotemperature
dierence between the unit and the outside air, frost will form.
If this happens:
- The air conditioner stops heating.
-
The air conditioner will operate automatically in De-ice mode for 10 minutes.
- The steam produced on the outdoor unit in De-ice mode is safe.
No intervention is required; after about 10 minutes, the air conditioner
operates again normally.
❈ The unit will not operate when it starts to de-ice.
Fan • Fanmaynotoperateforabout3~5minutesatthebeginningto
prevent any cold blasts while the air conditioner is warming up.
High indoor/
outdoor
temperatures
• Ifbothindoorandoutdoortemperaturesarehighandtheair
conditioner is running in Heat mode, the outdoor unit’s fan and
compressor may stop at times. This is normal; wait until the air
conditioner turns on again.
Power failure • Ifapowerfailureoccursduringtheoperationoftheairconditioner,
theoperatingimmediatelystopsandunitwillbeo.Whenpower
returns, the air conditioner will run automatically.
Protection
mechanism
• Iftheairconditionerhasjustbeenturnedonafteroperationstopsor
beingpluggedin,cool/warmairdoesnotcomeoutfor3minutesto
protect the compressor of the outdoor unit.
11
ENGLISH
SLIM DUCT TYPE
Viewing the parts
• Yourairconditioneranddisplaymaylookslightlydierentfromtheillustrationshownabovedependingonyour
model.
NOTE
MA DUCT TYPE
Air intake
Air outlet
Ceiling
Airlter(thereturnairside)
Air intake
Air outlet
Ceiling
Airlter(thereturnairside)
Congratulationsonthepurchaseoftheairconditioner.Wehopeyouenjoythefeaturesofyourairconditionerandstaycoolor
warm with optimal eciency.
Please read the user manual to get started and to make the best use of the air conditioner.
GLOBAL DUCT Type
Air intake
Air outlet
Ceiling
Airlter(thereturnairside)
12
Cleaning and maintaining the air conditioner
Cleaning the lter
• Theillustrationshownabovemaydierfromyoursdependingonyourmodel.
• Aftercleaningthelter,presstheFilter Reset button on the remote control for 2 seconds to reset the lter
schedule. Filter sign indicator will be on for cleaning time.
NOTE
Slim duct type
1. Slide out the Air lter on the rear side panel to the right side.
2. Clean the Air lter with a vacuum cleaner or soft brush. If dust is too heavy, then rinse it with running water and dry it
in a ventilated area.
• Forbestconditions,repeateverytwoweeks.
• IftheAirfilterdriesinaconfined(orhumid)area,odorsmaygenerate.Ifitoccurs,
re-clean and dry it in a
ventilated area.
3. Insert the Air lter back in its original position.
Forthebestperformancefromyourairconditioner,cleanitperiodically.Whencleaning,makesuretounplugfromtheunitfor
user’s safety.
Whencleaningthelter,makesuretounplugthepowerfromtheunit.WashablefoambasedAirltercaptureslargeparticles
from the air. The lter is cleaned with a vacuum or by hand washing.
13
ENGLISH
MA duct type
1. Slide out the Air lter on the rear side panel to the right side.
2. Clean the Air lter with a vacuum cleaner or soft brush. If dust is too heavy, then rinse it with running water and dry it
in a ventilated area.
• Forbestconditions,repeateverytwoweeks.
• IftheAirlterdriesinaconned(orhumid)area,odorsmaygenerate.Ifitoccurs,
re-clean and dry it in a ventilated area.
3. Insert the Air lter back in its original position.
• Theillustrationshownabovemaydierfromyoursdependingonyourmodel.
• Aftercleaningthelter,presstheFilter Reset button on the remote control for 2 seconds to reset the lter
schedule. Filter sign indicator will be on for cleaning time.
NOTE
14
Cleaning and maintaining the air conditioner
GLOBAL DUCT (Plastic Type)
1. Press both hooks and take the lter downward.
2. Clean the Air lter with a vacuum cleaner or soft brush. If dust is too heavy, then rinse it with running water and dry it
in a ventilated area.
• Forbestconditions,repeateverytwoweeks.
• IftheAirlterdriesinaconned(orhumid)area,odorsmaygenerate.Ifitoccurs,
re-clean and dry it in a ventilated area.
3. Insert the Air lter back in its original position.
• Theillustrationshownabovemaydierfromyoursdependingonyourmodel.
• Aftercleaningthelter,presstheFilter Reset button on the remote control for 2 seconds to reset the lter
schedule. Filter sign indicator will be on for cleaning time.
NOTE
15
ENGLISH
GLOBAL DUCT (Steel wire Type)
1. Pull out the Air lter from the frame .
2. Clean the Air lter with a vacuum cleaner or soft brush. If dust is too heavy, then rinse it with running water and dry it
in a ventilated area.
• Forbestconditions,repeateverytwoweeks.
• IftheAirlterdriesinaconned(orhumid)area,odorsmaygenerate.Ifitoccurs,
re-clean and dry it in a ventilated area.
3. Insert the Air lter back in its original position.
• Theillustrationshownabovemaydierfromyoursdependingonyourmodel.
• Aftercleaningthelter,presstheFilter Reset button on the remote control for 2 seconds to reset the lter
schedule. Filter sign indicator will be on for cleaning time.
NOTE
16
If the air conditioner will not be used for an extended period of time, dry the air conditioner to maintain it in best condition.
DrytheairconditionerthoroughlybyoperatinginFanmodefor3to4hoursand
disconnect the power plug.
There may be internal damage if moisture is left in components.
Before using the air conditioner again, dry the inner components of the air conditioner
againbyrunninginFanmodefor3to4hours.Thishelpsremoveodorswhichmayhave
generated from dampness.
• Thedescribedoperationsshouldbeperformedmorefrequentlyiftheareaofinstallationisverydusty.
NOTE
• Theseoperationsmustalwaysbeperformedbyqualiedpersonnel.Formore
detailed information, see the installation part in the manual.
CAUTION
Periodical checks
Refer to the following chart to maintain the air conditioner properly.
Type Description Monthly Every 4
months Once a year
Indoor unit
Cleantheairlter(1)
●
Cleanthecondensatedrainpan(2)
●
Thoroughlycleantheheatexchanger(2)
●
Cleanthecondensatedrainpipe(2)
●
Replacetheremotecontrolbatteries(1)
●
Outdoor unit
Cleantheheatexchangerontheoutsideoftheunit(2)
●
Cleantheheatexchangerontheinsideoftheunit(2)
●
Cleantheelectriccomponentswithjetsofair(2)
●
Verifythatalltheelectriccomponentsarermlytightened(2)
●
Cleanthefan(2)
●
Verifythatallthefanassemblyisrmlytightened(2)
●
Cleanthecondensatedrainpan(2)
●
●: This check mark requires checking the indoor/outdoor unit periodically, following to the description to maintain the air
conditioner properly.
Cleaning and maintaining the air conditioner
17
ENGLISH
Appendix
Troubleshooting
Refer to the following chart if the air conditioner operates abnormally. This may
save time and unnecessary expenses.
PROBLEM SOLUTION
The air conditioner
does not operate
immediately after it
has been restarted.
• Becauseoftheprotectivemechanism,theappliancedoesnotstart
operating immediately to keep the unit from overloading.
The air conditioner will start in 3 minutes.
The air conditioner
does not work at all.
• Checkthatthepowerplugisproperlyconnected.Insertthepower
plug into the wall socket correctly.
• Checkifthecircuitbreakerisswitchedo.
• Checkifthereisapowerfailure.
• Checkyourfuse.Makesureitisnotblownout.
The temperature
does not change.
• CheckifyouselectedFanmode.
Press the Mode button on the remote control to select another
mode.
The cool (warm)
air does not come
out of the air
conditioner.
• Checkifthesettemperatureishigher(lower)thanthecurrent
temperature. Press the Temperature button on the remote control
to change the set temperature. Press the Temperature button to
decrease or increase the temperature.
• Checkiftheairlterisblockedbydirt.Cleantheairltereverytwo
weeks.
• Checkiftheairconditionerhasjustbeenturnedon.Ifso,wait3
minutes. Cool air does not come out to protect the compressor of
the outdoor unit.
• Checkiftheairconditionerisinstalledinaplacewithadirect
exposure to sunlight. Hang curtains on windows to boost cooling
eciency.
• Checkifthecoveroranyobstacleisnotneartheoutdoorunit.
• Checkiftherefrigerantpipeistoolong.
• CheckiftheairconditionerisonlyavailableinCoolmode.
• Checkiftheremotecontrolisonlyavailableforcoolingmodel.
18
PROBLEM SOLUTION
The fan speed does
not change.
• CheckifyouselectedAutoorDrymode.
TheairconditionerautomaticallyadjuststhefanspeedtoAutoin
Auto/Drymode.
Timer function does
not set.
• CheckifyoupressthePower button on the remote control after
you have set the time.
Odors permeate in
the room during
operation.
• Checkiftheapplianceisrunninginasmokyareaorifthereisasmell
entering from outside. Operate the air conditioner in Fan mode or
open the windows to air out the room.
The air conditioner
makes a bubbling
sound.
• Abubblingsoundmaybeheardwhentherefrigerantiscirculating
through the compressor. Let the air conditioner operate in a
selected mode.
• WhenyoupressthePower button on the remote control, noise may
be heard from the drain pump inside the air conditioner.
Water is dripping
from the air ow
blades.
• Checkiftheairconditionerhasbeencoolingforanextendedperiod
of time with the air ow blades pointed downwards. Condensation
may generate due to the dierence in temperature.
Remote control is
not working.
• Checkifyourbatteriesaredepleted.
• Makesurebatteriesarecorrectlyinstalled.
• Makesurenothingisblockingyourremotecontrolsensor.
• Checkthattherearestronglightingapparatusneartheair
conditioner. Strong light which comes from uorescent bulbs or
neon signs may interrupt the electric waves.
The air conditioner
does not turn on or
o with the wired
remote control.
• Checkifyousetthewiredremotecontrolforgroupcontrol.
The wired remote
control does not
operate.
• CheckifTESTindicatorisdisplayedonthewiredremotecontrol.
If so, turn o the unit and switch o the circuit breaker. Call your
nearest contact center.
The indicators of
the digital display
ashes.
• PressthePower button on the remote control to turn the unit o
and switch the circuit breaker o. Then, switch it on again.
Appendix
19
ENGLISH
Dimension and weight
Type Model Net dimension (WxDxH) (mm) Net weight(kg)
Indoor Unit
AC052HBLDKH 1100*450*200 22.5
AC071HBLDKH 1100*450*200 22.5
AC035HBMDKH 850*700*250 25
AC052HBMDKH 850*700*250 25
AC060HBMDKH 850*700*250 25
AC071HBMDKH 850*700*250 25
AC052HBMPKH 850*700*250 25
AC090HBMDKH 1200*700*250 32
AC100HBMDKH 1200*700*250 32
AC120HBMDKH 1300*700*300 36
AC140HBMDKH 1300*700*300 36
AC071HBMPKH 1200*700*250 32
AC090HBMPKH 1300*700*300 36
AC100HBMPKH 1300*700*300 36
AC120HBMPKH 1300*700*300 36
AC140HBMPKH 1300*700*300 36
AC026HBLDKH 700*600*199 20
AC035HBLDKH 700*600*199 20
Model specication (
Dimension and weight)
QUESTIONS OR COMMENTS?
COUNTRY CALL OR VISIT US ONLINE AT
UK 0330 SAMSUNG (7267864) www.samsung.com/uk/support
EIRE 0818 717100 www.samsung.com/ie/support
GERMANY
0180 6 SAMSUNG bzw.
0180 6 7267864*
(*0,20 €/Anruf aus dem dt. Festnetz, aus dem Mobilfunk max. 0,60 €/Anruf)
[HHP] 0180 6 M SAMSUNG bzw.
0180 6 67267864*
(*0,20 €/Anruf aus dem dt. Festnetz, aus dem Mobilfunk max. 0,60 €/Anruf)
www.samsung.com/de/support
FRANCE 01 48 63 00 00 www.samsung.com/fr/support
ITALIA 800-SAMSUNG (800.7267864) www.samsung.com/it/support
SPAIN 0034902172678
[HHP] 0034902167267 www.samsung.com/es/support
PORTUGAL 808 20 7267 www.samsung.com/pt/support
LUXEMBURG 261 03 710 www.samsung.com/be_fr/support
NETHERLANDS 0900-SAMSUNG (0900-7267864) (€ 0,10/Min) www.samsung.com/nl/support
BELGIUM 02-201-24-18 www.samsung.com/be/support (Dutch)
www.samsung.com/be_fr/support (French)
NORWAY 815 56480 www.samsung.com/no/support
DENMARK 70 70 19 70 www.samsung.com/dk/support
FINLAND 030-6227 515 www.samsung.com//support
SWEDEN 0771 726 7864 (0771-SAMSUNG) www.samsung.com/se/support
POLAND
801-172-678* lub +48 22 607-93-33*
Dedykowana infolinia do obsługi zapytań dotyczących telefonów
komórkowych: 801-672-678* lub +48 22 607-93-33*
* (koszt połączenia według taryfy operatora)
www.samsung.com/pl/support
HUNGARY 0680SAMSUNG (0680-726-786)
0680PREMIUM (0680-773-648) www.samsung.com/hu/support
AUSTRIA
0800-SAMSUNG (0800-7267864)
[Only for Premium HA] 0800-366661
[Only for Dealers] 0810-112233
www.samsung.com/at/support
SWITZERLAND 0800 726 78 64 (0800-SAMSUNG) www.samsung.com/ch/support (German)
www.samsung.com/ch_fr/support (French)
CZECH 800 - SAMSUNG
(800-726786) www.samsung.com/cz/support
SLOVAKIA 0800 - SAMSUNG
(0800-726 786) www.samsung.com/sk/support
CROATIA 072 726 786 www.samsung.com/hr/support
BOSNIA 055 233 999 www.samsung.com/support
MONTENEGRO 020 405 888 www.samsung.com/support
SLOVENIA 080 697 267 (brezplačna številka) www.samsung.com/si
SERBIA 011 321 6899 www.samsung.com/rs/support
BULGARIA *3000 Цена в мрежата
0800 111 31 , Безплатна телефонна линия www.samsung.com/bg/support
ROMANIA *8000 (apel in retea)
08008-726-78-64 (08008-SAMSUNG) Apel GRATUIT www.samsung.com/ro/support
CYPRUS 8009 4000 only from landline, toll free
www.samsung.com/gr/support
GREECE 80111-SAMSUNG (80111 726 7864) only from land line
(+30) 210 6897691 from mobile and land line
LITHUANIA 8-800-77777 www.samsung.com/lt/support
LATVIA 8000-7267 www.samsung.com/lv/support
ESTONIA 800-7267 www.samsung.com/ee/support
SUZHOU SAMSUNG ELECTRONICS CO.,LTD.
No.501,Suhong East Road,Suzhou Industrial Park,Jiangsu Province,P.R.China
Samsung Electronics
Service Department
PO Box 12987, Blackrock, Co. Dublin. Ireland
or
Blackbushe Business Park,Yateley, GU46 6GG. UK
Air Conditioner
user manual
imagine the possibilities
Thank you for purchasing this Samsung product.
Duct Type Series
Slim Duct
MA Duct
Global Duct
DB68-04234A-06
EN ES FR IT PT DE EL