APC SmartBunkerSX 24U 3kVA UPS User Manual
Displayed below is the user manual for SmartBunkerSX 24U 3kVA UPS by APC which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals
NetShelter™ SX 24U Cabinet
Installation and Customization
990-3206A-001
Publication Date: May, 2014
Schneider Electric Legal Disclaimer
The information presented in this manual is not warranted by Schneider Electric to be authoritative, error free,
or complete. This publication is not meant to be a substitute for a detailed operational and site specific
development plan. Therefore, Schneider Electric assumes no liability for damages, violations of codes,
improper installation, system failures, or any other problems that could arise based on the use of this
Publication.
The information contained in this Publication is provided as is and has been prepared solely for the purpose of
evaluating data center design and construction. This Publication has been compiled in good faith by Schneider
Electric. However, no representation is made or warranty given, either express or implied, as to the
completeness or accuracy of the information this Publication contains.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, OR ANY PARENT, AFFILIATE OR SUBSIDIARY COMPANY
OF SCHNEIDER ELECTRIC OR THEIR RESPECTIVE OFFICERS, DIRECTORS, OR EMPLOYEES BE
LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL
DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT,
REVENUE, DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING OUT,
OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT,
EVEN IF SCHNEIDER ELECTRIC HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH
DAMAGES. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH
RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME
WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio,
video, text, and photographs) rests with Schneider Electric or its licensors. All rights in the content not expressly
granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons
accessing this information.
This Publication shall not be for resale in whole or in part.
Table of Contents
NetShelter SX Cabinet - Installation and Customization Manual i
Introduction............................................................................................................ 1
Unpack the Cabinet............................................................................................... 2
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Please Recycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Important Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Component Identification....................................................................................... 4
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hardware Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cabinet Installation................................................................................................ 6
Move the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Level the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rack stabilization options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Remove the casters and leveling feet (optional) . . . . . . . . . . . . . . . . . . . . . . . . . 8
Side Panels, Roof, and Doors............................................................................... 9
Side Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Roof. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Reverse the Front Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Equipment Installation ......................................................................................... 14
Adjust the Vertical Mounting Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Position the Vertical Mounting Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vertical Mounting Flange Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Ground the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Install Equipment................................................................................................. 18
To install rack-mount equipment in the cabinet: . . . . . . . . . . . . . . . . . . . . . . . . 18
Installing cage nuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Removing cage nuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cable Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Accessory Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Rear Door Cable Containment Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Specifications ...................................................................................................... 20
24U Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
AR3104 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Limited Factory Warranty .................................................................................... 21
Terms of Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Non-transferable Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Exclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Warranty Claims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1 NetShelter SX Cabinet - Installation and Customization Manual
Introduction
The Schneider Electric NetShelter SX 600 mm (23.6 in.) wide, 24U cabinet is a high-quality cabinet for storage
of industry-standard (EIA-310), 19 in. rack-mount hardware, which includes servers and voice, data,
networking, internetworking, and power protection equipment.
This manual covers the following NetShelter SX cabinet:
Model Rack Mounting
Height
Rack Mounting
Width
External Cabinet
Width
Cabinet
Depth
AR3104 24U* 482 mm
(18.98 in.)
600 mm
(23.62 in.)
1070 mm
(42.13 in.)
*1U= 44.45 mm (1.75 in.)
NetShelter SX Cabinet - Installation and Customization Manual2
Unpack the Cabinet
Disclaimer
Schneider Electric is not responsible for damage sustained during reshipment of this product.
Inspection
Inspect the packaging and contents for shipping damage. Make sure that all parts are accounted for. Report
any damage immediately to the shipping agent. Report missing contents, damage, or other problems
immediately to Schneider Electric or your reseller.
Please Recycle
The shipping materials are recyclable. Save them for later use, or dispose of them appropriately.
Important Safety Information
Read the instructions carefully to become familiar with the device before trying to install, operate, service or
maintain it. The following messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard
exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death
or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death
or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor
or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation
which, if not avoided, can result in equipment damage.
NOTICE
NOTICE addresses practices not related to physical injury including certain environmental
hazards, potential damage or loss of data.
3 NetShelter SX Cabinet - Installation and Customization Manual
Safety Instructions
This manual contains important instructions that must be followed during the installation and customization of
the cabinet.
Labels
Look for additional safety information affixed to the cabinet. See “Labels” on page 6 for more information.
WARNING
TIP HAZARD
• This cabinet is easily tipped. Use extreme caution when unpacking or moving.
• Use at least two people to unpack and move the cabinet.
• Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom of the
cabinet for extra stability.
• When moving on its casters, make sure the leveling feet are up and push the cabinet from the front
or rear.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
HEAVY EQUIPMENT
Use at least two people to unpack the cabinet.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NetShelter SX Cabinet - Installation and Customization Manual4
Component Identification
Cabinet
Adjustable vertical 0U accessory channel Casters
Removable rear split doors Bolt-down bracket
Rear door cable containment bracket Removable and reversible front door
Removable side panels with locks Nameplate (if equipped)
Cabinet frame Key for doors and side panels
Adjustable leveling feet Vertical mounting flanges
Hardware bag 1070 mm (42.13 in.) roof
ns1185a
5 NetShelter SX Cabinet - Installation and Customization Manual
Hardware Bag
Tools (provided)
Plastic cup
washer (60)
M6 x 16 Phillips
slot screw (60)
M5 x 12
screw (4)
Cage nut (60) 7 mm (0.28 in.)
hole plug (4)
TORX® T30/#2 Phillips tool Cage nut tool (1)
NetShelter SX Cabinet - Installation and Customization Manual6
Cabinet Installation
Move the Cabinet
WARNING
TIP HAZARD
• This cabinet is easily tipped. Use extreme caution when unpacking or moving.
• Use at least two people to unpack and move the cabinet.
• Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom of the
cabinet for extra stability.
• When moving on its casters, make sure the leveling feet are up and push the cabinet from the front
or rear.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Labels. The following labels can be found on the cabinet, and
serve to communicate the following information:
Label : Generic Tip Hazard
Label : Extend Slide-Mounted Hardware One Piece at a Time
Casters
2250 lbs Max
(1020 kg)
Leveling Feet:
3000 lbs Max
(1361 kg)
U.S. Patent No.
初⦌₢Ⓒ⚆
7,293,666
Casters. The cabinet can be moved on its casters with up to
1020 kg (2,250 lb) of equipment installed. Once in place, lower the
leveling feet. With the leveling feet lowered, the static cabinet can be
loaded to 1364 kg (3,000 lb).
Note: Some labels on cabinet indicate caster related information.
See label to right.
ns2303a
< 562 LBS (255 KG)
Eye bolts. The cabinet can be lifted by removing the hole plugs and attaching
eye bolts (not included), to the top of the cabinet frame. Use rated M10 eye bolts.
The maximum weight of installed equipment should be 142 kg (312 lb) per eye
bolt, 567 kg (1,250 lb) total.
Note: If using supplemental lifting hardware, ensure the cord length allows for
a minimum of a 75° angle, as shown to the right.
Note: Each individual frame lift
point is capable of lifting 255 kg
(562 lb).
>75°
ns2295a
7 NetShelter SX Cabinet - Installation and Customization Manual
Level the Equipment
Note: The leveling feet at the corners of the equipment provide a stable base if the floor is uneven, but they
cannot compensate for a badly sloped surface.
1. Ensure the cabinet is in its intended location. Remove the front and rear doors.
See “Removal” on page 11 for instruction.
Note: Before removing the front door, unplug the ground wires and any other wire connections that may
interfere with the removal of the doors.
2. Insert a Phillips head screwdriver into the screw above the leveling foot. Turn the screw clockwise to
extend the leveling foot until it makes firm contact with the floor.
3. Adjust each foot and, using a level, adjust the feet until the cabinet is level and plumb.
4. Install the front and rear doors.
DANGER
HAZARD OF ELECTRIC SHOCK
When Installing the doors, remember to reconnect all ground and other connection wires.
Failure to follow these instructions will result in death or serious injury.
ns2304a
Notes:
1. If loaded with equipment, a 13
mm open ended wrench can also
be used to lower the leveling feet.
2. This method works best with an empty, or near empty
cabinet.
3. Door removal is not required if using the 13 mm open-ended wrench.
NetShelter SX Cabinet - Installation and Customization Manual8
Rack stabilization options
Brackets can be used to bolt the cabinet to the floor internally or externally for additional stabilization.
See www.apc.com for bracket installation and further related information.
Note: Only use the bolt-down bracket or stabilization plate with the casters or leveling feet installed.
Remove the casters and leveling feet (optional)
1. Lay the cabinet on its side.
2. Using a 10-mm socket wrench (not provided), remove the four hex nuts from each of the casters and
remove the casters.
3. For each leveling foot, use a Phillips screwdriver to turn the foot clockwise until it is released from the
frame.
Note: Remove all equipment from the cabinet before removing casters and leveling feet.
ns0879a
9 NetShelter SX Cabinet - Installation and Customization Manual
Side Panels, Roof, and Doors
Side Panels
Removal
ns1207a
1. Use the key to unlock the panel, if necessary.
2. Slide the panel latch down and pull the top of the panel away
from the cabinet.
3. Release the latch and lift the panel up and off the side brace
lip at the bottom of the panel frame.
Installation
1. Engage the bottom of the panel securely
with the side brace lip before pushing the
top of the panel forward into place.
2. Slide the panel latch up.
ns1208a
NetShelter SX Cabinet - Installation and Customization Manual10
Roof
X
2
ns1724a
11 NetShelter SX Cabinet - Installation and Customization Manual
Door
Removal
Installation
ns0944b
1. The doors self-align on hinge pins when
properly installed. With the door at a 90
degree angle to the front of the cabinet,
position the door over the hinge pins.
2. Slowly lower the door into the cabinet
frame ensuring that the door hinges
correctly align to the cabinet frame
hinges.
3. Connect the ground wire and any other
wire connections. Make sure the door
opens and closes properly.
ns0928c
1. Unlock the cabinet front door handle and
open the door.
2. Disconnect the ground wire and any other
wire connections that may interfere with
the removal of the doors.
3. The hinges come apart by lifting upward
and outward. Slowly lift and pull the door
from the cabinet until the hinge pins on the
door are free of the hinges on the cabinet
frame.
NetShelter SX Cabinet - Installation and Customization Manual12
Reverse the Front Door
Note: The front door can be reversed so that the door opens in the other direction. This procedure assumes
that initially, when facing the cabinet, the hinges are on the left and the door is opening from right.
ns0176b
180°
ns0974b
ns0919a
ns1709a
1. Remove the handle by removing the screw-
plate. Pull the handle from the door.
3. Locate the upper hinge on the cabinet frame. Remove the two screws
holding the hinge in place. Install the hinge onto the other side of the cabinet
frame. Repeat this step for the lower hinge.
4. Remove the hinges from the door
and install them using the set of
holes directly below where they
were originally installed. Rotate
the door 180 degrees and install
on cabinet
2. Disconnect the ground wire, and any other wire con-
nections. Remove the door from the frame. See “Re-
moval” on page 11 for more information.
13 NetShelter SX Cabinet - Installation and Customization Manual
7. Remove the nameplate (if equipped) from the door. Install the nameplate at the location shown in the illustrations
below.
6. Locate the lock handle. Remove the
cam screw, cam washer, and cam.
Rotate the cam washer 90 degrees,
and the latch 180 degrees. Install the
handle on the door.
5. Install the door to the hinges now on the reverse side of the cabinet
frame. See “Installation” on page 11 for instruction. Connect the ground
wire and any other wire connections previously disconnected.
ns1766b
300 mm (11.8 in.) (600 mm wide)
375 mm (14.8 in.) (750 mm wide)
307 mm (12 in.)
ns2010a
ns2308a
NetShelter SX Cabinet - Installation and Customization Manual14
Equipment Installation
Note: NetShelter SX cabinets are intended for use with Listed equipment. If you install un-Listed equipment, you
should evaluate the safety of your configuration.
Adjust the Vertical Mounting Flanges
Vertical mounting flanges come factory-installed
at 737 mm (29 in.), the proper location for use with
rack-mountable equipment.
The mounting flanges are adjustable towards the
front or the rear of the cabinet to accommodate
different rails or equipment with other depths.
Position the Vertical Mounting Flanges
WW
D
D
a
b
c
ns2293a
Accessory Channel
Top View
• Configuration : The Accessory Channel is installed.
The Vertical Mounting Flanges can be installed a
minimum distance of (a) and can extend as far as (b).
• Configuration : The Accessory Channel is removed.
The Vertical Mounting Flanges can extend as far as (c).
Models
Cabinet
Width (W)
Cabinet
Depth (D) a b c
AR3104 600 mm 1070 mm 190.5 mm
(7.5 in.)
781.0 mm
(30.75 in.)
920.7 mm
(36.25 in.)
ns1701a
15 NetShelter SX Cabinet - Installation and Customization Manual
Vertical Mounting Flange Adjustment
WARNING
FALLING EQUIPMENT
Remove all equipment installed on the vertical mounting flanges before performing any adjustments.
Failure to follow these instructions can result in serious injury or equipment damage.
ns2302a
1. Use the provided TORX T30 tool to loosen the top and
bottom TORX screws holding the vertical mounting
flange in place.
The brackets, held in place by the TORX screws, will
now be loose.
Move both brackets to the designated unlocked
position.
ns2290a
NetShelter SX Cabinet - Installation and Customization Manual16
ns1623a
ns2292a
ns2305a
2. Move the mounting flange to the desired location. Vertical
mounting flanges adjust in 6 mm (1/4 in.) increments.
3. To align the vertical mounting flange, note the symbol
(for example, a diamond). Only one symbol will be visible. In
the factory standard position, a circle symbol is visible.
Make sure the same symbol is visible through the
corresponding hole at both the top and the
bottom of the flange.
4. When the vertical mounting flange is in
the desired location at the top and
bottom, raise the flat bracket to the
lock position. The teeth in the bracket
will engage fully with the teeth in the
side brace.
Tighten the TORX screws.
17 NetShelter SX Cabinet - Installation and Customization Manual
Ground the Cabinet
The doors, side panels, and roof of the cabinet are grounded to the cabinet frame. The doors are grounded with
quick-disconnect cables. The roof and side panels are inherently grounded through spring fingers.
Each cabinet should be bonded directly to a common ground using one of the designated grounding locations
(two M6 threaded inserts) at the top or bottom of the cabinet.
• Use a Common Bonding Network Jumper kit (for example, Listed [KDER] Panduit® RGCBNJ660PY or
equivalent).
• Use paint-piercing washers between the ground terminal and the cabinet frame, or remove the paint on
the frame under the ground terminals, per NEC NFPA 70 Article 250.12.
• Torque the screws to 6.9 N•m (60 lb-in).
• Do not ground one cabinet to another cabinet in a cascading style. Ground each cabinet directly to the
building ground.
DANGER
HAZARD OF ELECTRIC SHOCK
Connection of the cabinet to building Common Bonding Network (CBN) is required.
Failure to follow these instructions will result in death or serious injury.
ns2306a
ns2307a
NetShelter SX Cabinet - Installation and Customization Manual18
Install Equipment
To install rack-mount equipment in the cabinet:
1U
7
6
5
ns0014a
1. Review the equipment manufacturer’s installation instructions.
2. Locate the top and bottom U-space on the vertical mounting rails. Every
third hole on the mounting rails is numbered to indicate the middle of a
U-space.
3. Install the cage nuts on the interior of the vertical mounting rail; then
install the equipment. (To remove a cage nut, squeeze the sides to
release it from the square hole.)
Installing cage nuts
Schneider Electric offers a cage nut hardware kit (AR8100) for
use with square holes.
Note: Install cage nuts horizontally, with the ears engaging the
sides of the square hole. Do NOT install cage nuts vertically with
the ears engaging the top and bottom of the square hole.
1. Insert the cage nut into the square hole by hooking one ear of the cage nut assembly through the far
side of the hole.
Note: Install the cage nuts on the interior of the vertical mounting flange.
2. Place the cage nut tool on the other side of the cage nut and pull to snap it into position.
Removing cage nuts
gen0188a
1.Remove any attached screw.
2.Grasp the cage nut and squeeze the sides to release it from the
square hole.
WARNING
TIP HAZARD
• This cabinet is easily tipped. Make sure you have secured the cabinet to the floor before installing
equipment.
• Install the heaviest equipment first and toward the bottom of the cabinet to prevent the cabinet
from becoming top-heavy.
• Do not extend equipment on sliding rails until you have installed 158 kg (350 lb) of equipment into
the bottom of the cabinet for stability or until you have installed the stabilizer plate or bolt-down
brackets. Do not extend more than one piece of equipment on sliding rails at a time.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
ns1768a
19 NetShelter SX Cabinet - Installation and Customization Manual
Cable Management
The NetShelter SX cabinet has multiple cable access openings, including on the roof, sides, and bottom.
Route, secure, and organize cables using these openings.
In addition, two rear vertical 0U cable organizers, or accessory channels, are included with the cabinet. Further
cable management accessories are available. Please see www.apc.com or contact a Schneider Electric
re-seller for more information.
Accessory Channel
The accessory channels provide toolless mounting capabilities for Rack Power Distribution Units and cable
management accessories.
There are two accessory channels included
with the 1070 mm (47.24 in.) deep cabinet. The
factory-default position for the accessory
channels is in the rear of the cabinet, as shown
in the graphic to the left.
The channels also provide tie-off locations for
cables, as well as other specific holes for
managing cables with many NetShelter
brackets, fasteners, and toolless mounting
equipment.
Similar to the mounting flanges, the accessory
channel can be moved anywhere along the
side braces. See “Adjust the Vertical Mounting
Flanges” on page 14 for more information.
Note: If needed, the accessory channels can be removed. Additional vertical 0U accessory channels are
available for order.
ns1212a
NetShelter SX Cabinet - Installation and Customization Manual20
Rear Door Cable Containment Bracket
ns1725a
The rear door cable containment bracket is installed within the cabinet under the left hand door. The bracket
has 4 lobes for attaching cables with hook-and-loop fasteners (provided) and cable ties (not provided).
21 NetShelter SX Cabinet - Installation and Customization Manual
Specifications
24U Cabinet
AR3104
Item Measurements
Height 1199 mm (47.20 in.)
Width 600 mm (23.62 in.)
Depth 1070 mm (42.13 in.)
Net weight 88.90 kg (196.00 lb)
Total open area (front door) 345 808 mm2 (536.00 in2)
Total open area (rear door) 375 870 mm2 (582.60 in2)
Open area per U (front door) 14 406 mm2 (22.33 in2)
Open area per U (rear door) 15 658 mm2 (24.27 in2)
Percent open (front) 67%
Percent open (rear) 73%
Clearance * 60.96 mm (2.40 in.)
* wiring between front door and vertical rail
Weight rating: static load11361 kg (3,000 lb)
Weight rating: rolling 1021 kg (2,250 lb)
Weight rating: shipping 567 kg (1,250 lb)
1 Lower the leveling feet if the static weight is over 1020.58 kg (2,250 lb).
Note: Additional packaging may be required if the rack is being reshipped with equipment
installed. See the NetShelter SX product family page at www.apc.com for details on
cabinets with shock packaging.
Limited Factory Warranty
The limited warranty provided by Schneider Electric in this Statement of Limited Factory Warranty applies only
to Products you purchase for your commercial or industrial use in the ordinary course of your business.
Terms of Warranty
Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of
five years (two years in Japan) from the date of purchase. Its obligation under this warranty is limited to
repairing or replacing, at its sole discretion, any such defective products. This warranty does not apply to
equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified
in any way. Repair or replacement of a defective product or part thereof does not extend the original warranty
period. Any parts furnished under this warranty may be new or factory-remanufactured.
Non-transferable Warranty
This warranty applies only to the original purchaser who must have properly registered the product. Product
may be registered at http://www.warranty.apc.com.
Exclusions
Schneider Electric shall not be liable under the warranty if its testing and examination disclose that the alleged
defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence,
improper installation or testing. Further Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection, inappropriate
on-site operation conditions, corrosive atmosphere, repair, installation, start-up by non-Schneider Electric
designated personnel, a change in location or operating use, exposure to the elements, Acts of God, fire, theft,
or installation contrary to Schneider Electric recommendations or specifications or in any event if the Schneider
Electric serial number has been altered, defaced, or removed, or any other cause beyond the range of the
intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF
PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION
HEREWITH. SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC EXPRESS
WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR
LIABILITY WILL ARISE OUT OF, SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER
ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND
REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE
WARRANTIES SET FORTH ABOVE CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND
PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SCHNEIDER
ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD
PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS, AFFILIATES OR
EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE
DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER
SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT
LIABILITY OR WHETHER SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBLY
OF SUCH DAMAGES. SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS, SUCH
AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF
SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR
OTHERWISE. NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS AUTHORIZED TO
ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT
ALL, ONLY IN WRITING SIGNED BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Warranty Claims
Customers with warranty claims issues may access the Schneider Electric worldwide customer support
network by visiting http://www.apc.com/support. Select your country from the country selection pull-down
menu. Open the Support tab at the top of the web page to obtain contact information for customer support in
your region.
Worldwide Customer Support
Customer support for this or any other product is available at no charge in any of the following ways:
• Visit the Schneider Electric Web site to access documents in the Schneider Electric Knowledge Base and to submit customer
support requests.
–www.schneider-electric.com (Corporate Headquarters)
Connect to localized Schneider Electric Web sites for specific countries, each of which provides customer support information.
–www.schneider-electric.com/support/
Global support searching Schneider Electric Knowledge Base and using e-support.
• Contact the Schneider Electric Customer Support Center by telephone or e-mail.
– Local, country-specific centers: go to www.schneider-electric.com > Support > Operations around the world for contact
information.
For information on how to obtain local customer support, contact the representative or other distributors from whom you purchased your
product.
4/2014990-3206A-001