Eaton 5PXEBM48RT2UG2 User Manual
Displayed below is the user manual for 5PXEBM48RT2UG2 by Eaton which is a product in the UPS Batteries category. This manual has pages.
Related Manuals
Eaton 5PX
Advanced User Guide
Copyright © 2021 EATON
All rights reserved.
614-40094-00
5PX1000IRT2UG2
5PX1500IRT2UG2
5PX2200IRT2UG2
5PX2200IRT3UG2
5PX3000IRT2UG2
5PX3000IRT3UG2
5PXEBM48RT2UG2
5PXEBM72RT2UG2
5PXEBM72RT3UG2
614-40094-00
2
1 Special symbols
The following are examples of symbols used on the UPS or accessories to alert you to importantinformation:
DANGER: Dangerous voltage levels are present within the UPS. The UPS has its own internal power
source (the battery). Consequently, the power outlets may be energized even if the UPS is
disconnected from the AC power source.
Important instructions that must always be followed.
CAUTION: Batteries present a risk of energy or electrical shock or burn from high short circuit current.
Observe proper precaution. Batteries may contain HIGH VOLTAGE and CORROSIVE, TOXIC and
EXPLOSIVE substances.
Information, advice, help.
Read the documentation provided.
Disconnect input plug.
Before maintenance, first shut down the UPS then disconnect the AC power source, internal and
external batteries then discharge capacitors by pressing the ON button and wait 5 minutes.
This equipment should only be used in a dry indoor environment.
Operating range of temperature.
Operating range of humidity.
The UPS and their batteries must be kept in a ventilated place.
614-40094-00
3
2 Table of content
1 Special symbols ........................................................................................................... 2
2 Table of content ........................................................................................................... 3
3 Introduction ................................................................................................................. 5
3.1 Environmental protection .................................................................................................................. 5
3.2 Benefits................................................................................................................................................ 6
4 Presentation................................................................................................................. 7
4.1 Standard installation .......................................................................................................................... 7
4.2 Rear panel............................................................................................................................................ 8
4.3 Optional accessories........................................................................................................................... 9
5 Installation ................................................................................................................... 9
5.1 Inspecting the equipment .................................................................................................................. 9
5.2 Recommended positions.................................................................................................................. 11
5.3 EBM connection ................................................................................................................................ 12
5.4 UPS connection................................................................................................................................. 14
5.5 Connection with a FlexPDU (Power Distribution Unit) optional module....................................... 14
5.6 Connection with a HotSwap MBP (Maintenance ByPass) optional module .................................. 14
6 Interfaces and communication ................................................................................. 16
6.1 Control panel..................................................................................................................................... 16
6.2 LCD description................................................................................................................................. 17
6.3 Display functions............................................................................................................................... 18
6.4 User settings...................................................................................................................................... 20
6.5 Communication ports....................................................................................................................... 23
6.6 UPS remote control functions.......................................................................................................... 25
6.7 Eaton Intelligent Power Software suite ........................................................................................... 28
6.8 Cybersecurity .................................................................................................................................... 28
7 Operation ................................................................................................................... 28
7.1 Start-up and normal operation ........................................................................................................ 28
7.2 Starting the UPS on battery.............................................................................................................. 28
7.3 UPS shutdown................................................................................................................................... 29
7.4 Operating modes .............................................................................................................................. 29
614-40094-00
4
7.5 Return of AC input power ................................................................................................................. 29
7.6 Configuring battery settings............................................................................................................. 29
7.7 Retrieving the event log.................................................................................................................... 30
7.8 Retrieving the fault log ..................................................................................................................... 30
8 UPS maintenance....................................................................................................... 30
8.1 Equipment care................................................................................................................................. 30
8.2 Storing the equipment...................................................................................................................... 30
8.3 When to replace batteries................................................................................................................. 31
8.4 Replacing batteries ........................................................................................................................... 31
8.5 Replacing the UPS equipped with a HotSwap MBP ........................................................................ 33
8.6 Recycling the used equipment......................................................................................................... 33
9 Troubleshooting......................................................................................................... 34
9.1 Typical alarms and faults.................................................................................................................. 34
9.2 Silencing the alarm ........................................................................................................................... 36
9.3 Service and support.......................................................................................................................... 36
10 Specification and technical characteristics.............................................................. 36
10.1 UPS model list ................................................................................................................................... 36
10.2 Extended Battery Module model list................................................................................................ 37
10.3 Weights and dimensions................................................................................................................... 37
10.4 Electrical input .................................................................................................................................. 37
10.5 Electrical input connections............................................................................................................. 38
10.6 Electrical output................................................................................................................................ 38
10.7 Electrical output connection............................................................................................................ 39
10.8 Battery ............................................................................................................................................... 39
10.9 Environmental and safety ................................................................................................................ 40
11 Glossary ...................................................................................................................... 40
614-40094-00
5
•
•
•
Materials Abbreviations Number in the symbols
Polyethylene terephthalate PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
3 Introduction
Thank you for selecting an Eaton 5PXproduct to protect your electrical equipment.
TheEaton 5PXrange has been designed with the utmost care. We recommend that you take the time to read this
advanced user guide to take full advantage of the many features of your UPS (Uninterruptible Power System).
Before installing yourEaton5PX,please read the information and safety instructions provided. Follow the instructions in
the quick start guide and if necessary, refer to this advance user guide.
To discover the entire range ofEatonproducts, we invite you to visit ourweb siteateaton.comor
contactyourEatonlocal representative.This UPS can be used in IT power system. This UPS complies with the IP20
protection type.
3.1 Environmental protection
Eatonhas implemented an environmental-protection policy. Products are developed according to an eco-design
approach.
Substances
This product does not contain CFC and HCFC. This product does not contain asbestos. This product is compliant with
regulations on the restriction of the use of substances in electrical and electronic equipment.
Packaging
To improve waste treatment and facilitate recycling, separate the various packing components.
The cardboard we use comprises over 50% of recycled cardboard.
Plastic bags are made of polyethylene.
Packing materials are recyclable and bear the appropriate identification symbol.
Follow all local regulations for the disposal of packing materials.
End of life
Eatonwill process products at the end of their service life in compliance with local regulations. Eatonworks with
companies in charge of collecting and eliminating our products at the end of their service life.
Product
The product is made up of recyclable materials. Dismantling and destruction must take place in compliance with all local
regulations concerning waste. At the end of its service life, the product must be transported to a processing center for
electrical and electronic waste.eaton.com/recycling
614-40094-00
6
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning
batteries. The battery may be removed to comply with regulations and in view of correct disposal.
3.2 Benefits
The Eaton 5PXuninterruptible power system (UPS) protects your sensitive electronic equipment from themost common
power problems, including power outages, voltagesags, impulsive transients, line noise, and long-term under and over
voltage conditions.
Power outages can occur when you least expect it and power quality can be erratic. These power problemshave the
potential to corrupt critical data, destroy unsaved work sessions, and damage hardware - causinghours of lost
productivity and expensive repairs.
With the Eaton 5PX, you can safely eliminate the effects of power disturbances and guard the integrityof your equipment.
Providing outstanding performance and reliability, the Eaton 5PX’s unique benefitsinclude:
• ABM® technology that uses advanced battery management to increase battery service life, optimize recharge time, and
provide a warning before the end of useful battery life.
• Standard communication options:one RS-232 communication port, one USB communication port, relay output
contacts.
• Optional connectivity cards with enhanced communication capabilities.
• Extended runtime with up to four Extended Battery Modules (EBMs) per UPS.
• Remote on/off (ROO) and remote power off (RPO).
• Backed by worldwide agency approvals.
• Remote firmware upgrade capability.
614-40094-00
7
4 Presentation
4.1 Standard installation
Tower installation Rack installation
Weights and dimensions
Description (UPS) Weights (lb / kg) Dimentions (inch / mm) D x W x H
5PX1000IRT2UG2 43.2 / 19,6 17.6x17.2x3.4 / 448x438x85,5
5PX1500IRT2UG2 49.4 / 22,4 17.6x17.2x3.4 / 448x438x85,5
5PX2200IRT2UG2 62.2 / 28,2 23.7x17.2x3.4 / 603x438x85,5
5PX2200IRT3UG2 60.6 / 27,5 19x17.2x5.1 / 483x438x129
5PX3000IRT2UG2 69.9 / 31,7 23.7x17.2x3.4 / 603x438x85,5
5PX3000IRT3UG2 68.6 / 31,1 19x17.2x5.1 / 483x438x129
Description (EBM) Weights (lb / kg) Dimentions (inch / mm) D x W x H
5PXEBM48RT2UG2 61.3 / 27,8 17.6x17.2x3.4 / 448x438x85,5
5PXEBM72RT2UG2 89.1 / 40,4 23.7x17.2x3.4 / 603x438x85,5
5PXEBM72RT3UG2 87.5 / 39,7 19x17.2x5.1 / 483x438x129
614-40094-00
8
4.2 Rear panel
5PX1000IRT2UG2 - 5PX1500IRT2UG2
5PX2200IRT2UG2 - 5PX3000IRT2UG2
5PX2200IRT3UG2 - 5PX3000IRT3UG2
5PXEBM48RT2UG2 - 5PXEBM72RT2UG2
5PXEBM72RT3UG2
① UPS
② Input AC power source
③Primary group (critical equipment)
④Outlet group (programmable outlets)
⑤ USB communication port
⑥RS232 communication port
⑦Relay output contact
⑧Connector for ROO (Remote On/Off) control and RPO
(Remote Power Off)
⑨Slot for optional communication card
⑩Connector for additional External Battery Module
⑪Connector for automatic recognition of an additional
battery module
⑫ Ground screw
614-40094-00
9
1.
2.
4.3 Optional accessories
Part number Description
5PXEBM48RT2UG2
5PXEBM72RT2UG2
5PXEBM72RT3UG2
Extended Battery Module
Network-M2 Eaton Gigabit Network Card (SNMP v1/v3 and IP v4/v6 // Ethernet 10/100/1000BaseT)
INDGW-M2 Eaton Industrial Gateway Card (Modbus TCP / RTU)
Relay-MS Eaton Relay card (1 x RS232 or 5 x Relay output)
INDRELAY-MS Eaton Industrial relay card (5x relay outputs with dry contacts for remote alarm information)
EMPDT1H1C2
Environmental Monitoring Probe Gen2
Compatibility : Gigabit Network Card (Network-M2) / Industrial Gateway Card (INDGW-M2) / Eaton
ePDU G3/G3+
MBP3KIF
MBP3KID
MBP3KI
HotSwap external maintenance bypass 4 FR
HotSwap external maintenance bypass 4 DIN
HotSwap external maintenance bypass 6 IEC
EFLX8F
EFLX8D
EFLX12I
FlexPDU 8 FR
FlexPDU 8 DIN
FlexPDU 8 IEC
5 Installation
5.1 Inspecting the equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or
place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for
concealed damage.
To file a claim for shipping damage or concealed damage:
File with the carrier within 15 days of receipt of the equipment;
Send a copy of the damage claim within 15 days to your service representative.
Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never
recharged, do not use the UPS. Contact your service representative.
614-40094-00
10
Package content
Verify that the following additional items are included
with the UPS:
① UPS
⑬ Connection cable to AC power source (2200VA &
3000VA models only)
⑭Connection cables for the protected equipment
⑮RS232 communication cable
⑯USB communication cable
⑰ Safety instructions
⑱Quick start
⑲Cable locking systems
⑳Rack kit for 19-inch 4-post enclosures
㉑Two supports for tower position (tower feet)
㉒Communication card (optional)
㉓ FlexPDU module(optional)
㉔ Connection cables between FlexPDU module and UPS(
optional)
㉕HotSwap MBP module (optional)
㉖Connection cables between HotSwap MBP module
and UPS (optional)
614-40094-00
11
5.2 Recommended positions
Installation in tower position
If you ordered other UPS accessories, refer to specific user manuals to check the tower installation with the UPS.
To install the UPS:
Place the UPS on a flat, stable surface in its final location.Always keep 6" or 150 mm of free space behind the UPS rear
panel for ventilation.
If installing additional EBM, place them next to the UPS in their final location.
Follow steps 1 to 5 to adjust the orientation of the LCD panel and of the logo.
614-40094-00
12
Installation in rack position
Follow steps 1 to 4 for module mounting on the rails.
The rails and necessary hardware are supplied by Eaton.
5.3 EBM connection
Tour installation
A small amount of arcing may occur when
connecting an EBM to the UPS. This is normal and will
not harm personnel. Insert the EBM cable into the UPS
battery connector quickly and firmly.
1.Attach the UPS and the EBMs to each other using the
supplied mounting plate. Up to 4 EBMs may be
connected to the UPS.
2. Connect the EBMs power cable and the attached
battery detection cable as shown in the picture.
3. Verify that the EBM connections are tight and that
adequate bend radius and strain relief exist for each
cable.
614-40094-00
13
Rack installation
A small amount of arcing may occur when
connecting an EBM to the UPS. This is normal and will
not harm personnel. Insert the EBM cable into the UPS
battery connector quickly and firmly.
To increase stability, it is preferable to place the
EBM below the UPS.
1. Fix the rail on the back of the rack.
2. Fix the rail on the front of the rack using the two holes
at the bottom.
3. Fix the ears plate to the UPS.
4. Place the UPS on the rails and fix the ears plate to the
top hole of the rail.
5. Connect the EBM power cable as shown in the picture.
6. Connect the RJ45 battery detection cable of the first
EBM between the EBM and the UPS connector "Batt
detection" (11). For any additional EBM, connect the
battery detection cable to the previous EBM.
Verify that the EBM connections are tight and that
adequate bend radius and strain relief exist for each
cable.
614-40094-00
14
5.4 UPS connection
Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source
and the true electrical consumption of the total load.
1.For the 5PX 1000 / 1500, connect the UPS input socket
(2) to the AC power source using the cable of the
protected equipment.
For the 5PX2200/ 3000, connect the UPS input socket (2)
to the AC-power source using the cable (13) supplied.
2.Connect the loads to the UPSusing the cables (14).It is
preferable to connect thepriority loads to the
outletsmarked (3) and the non-priorityloads to the
outlets Group1, Group2 (4) that can be programmed.
For the 5PX2200/ 3000 models, connect any high-power
devicesor matching Power Distribution Unit (PDU) to
the16Aoutlet.
Fit the connection securingsystem that prevents the
plugsfrom being pulled outaccidentally.
3.To program shutdown and startup of the Group1 and
Group2 outlets in order to extend battery runtime and
perform scheduled shutdowns, please see the "In/Out
settings" section.
5.5 Connection with a FlexPDU (Power Distribution Unit) optional module
1.5PX 1000 / 1500 : Use the power cable of the protected
equipment.
5PX2200/ 3000 connect the UPS input socket to the AC
power source using the cable (13) supplied.
2.Connect the input socket on the FlexPDU module (40)
to the UPS outlet (3) using the cable (24) supplied. The
cable and the connectorsare marked in red.
3.Connect the equipment to the outlets (41) on the
FlexPDU module. These outlets differ, depending on the
version of the FlexPDU module.
4. Fit the connection securingsystem that prevents the
plugsfrom being pulled outaccidentally.
5.6 Connection with a HotSwap MBP (Maintenance ByPass) optional module
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connectedloads
(HotSwap function).
614-40094-00
15
1.Connect the input socket (48) onthe HotSwap MBP
module to theAC power source using the cable(13)
supplied.
2.Connect the UPS input socket (2)to the “UPS
Input” (47) on theHotSwap MBP module, using thecable
(26) supplied. This cableand the connector are
markedblue.
3.Connect the UPS outlet (3) to the “UPS Output” (46)
on the HotSwap MBP module, using the cable (26)
supplied. This cable and the connector are marked in
red.
4. Connect the equipment to the outlets(42) on the
HotSwapMBP module.
These outlets differ,depending on the version of
theHotSwap MBP module.
Caution :Do not use UPS outlets(4) to supply
equipmentbecause use of switch (45) on theHotSwap
MBP module would cutsupply to the equipment.
HotSwap MBP module operation
The HotSwap MBP module has a rotaryswitch (45) with
two positions:
Normal: the load is supplied by the UPS,LED (43) is on.
Bypass: the load is supplied directly bythe AC power
source. LED (44)is on.Load is not protected.
UPS start-up with the HotSwap MBP module
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2.Start the UPS by pressing the button on the UPScontrol panel. LED (43) "UPS ON - OK to switch"on the HotSwap
MBP module goes ON (otherwise,there is a connection errorbetween the HotSwap MBP module and the UPS).
3. Set switch (45) to Normal position.The red LED onthe HotSwap MBP module goes OFF.
HotSwap MBP module test
1. Set switch (45) to Bypass position and check that the load is still supplied.
2. Set switch (45) back to Normal position.
614-40094-00
16
6 Interfaces and communication
6.1 Control panel
The screen provides useful information about the UPS itself, load status,events, measurements and settings.
The LED bar ⑨ has been implemented to provide a quick visual reference of UPS status "at-a-glance".
① Power ON indicator (green)
② On battery indicator (orange)
③ Alarm Indicator (red)
④Escape
⑤ Up
⑥ Down
⑦ Enter
⑧ On/Off button
⑨ Led bar
Led indicator
The following table shows the indicator status and description :
Indicator Status Description
Green On The UPS is "On" and the load is protected.
Orange On The UPS is in battery mode and the load is protected.
Flashing The battery voltage is below the warning level.
Red On The UPS has an active alarm or fault. See troubleshooting page for additional
information.
Led bar
Static blue The UPS is "On" and the load is protected.
Flashing blue The UPS is on battery or the battery service age warning is reached.
Static red The UPS has an active alarm or fault.
Flashing red The UPS output has stopped due to a fault.
614-40094-00
17
6.2 LCD description
① Load status and measurements
② Equipment status icon
③ Status / Message
④Battery status
As default, or after 5 minutes of inactivity, the LCD displays the screen saver.
The backlight LCD automatically dims after 5 minutes of inactivity. Press any button to restore the screen.
Note. If other indicator appears, see troubleshooting page for additional information.
The following table describes the status information provided by the UPS :
Operation status Possible cause Action
Standby mode
The UPS is OFF, waiting for start-up
command from user
Equipment is not power until button is pressed
during start up and the green "normal mode" LED
indicator is illuminated.
Normal mode
The UPS is operating normally. The UPS is powering and protecting the equipment.
In AVR mode
No beep
The UPS is operating normally but the
utility voltage is outside Normal mode
thresholds.
The UPS is powering the equipment through the
Automatic Voltage Regulation device. The equipment is
still normally protected.
On Battery
One beep every 10
seconds
A utility failure has occurred and the
UPS is in Battery mode.
The UPS is powering the equipment with battery
power. Prepare your equipment for shutdown.
End of backup time
1 beep every 3
seconds
The UPS is in Battery mode and the
battery is running low.
This warning is approximate, and the actual time to
shutdown may vary significantly. Depending on the
UPS Load, the "Battery Low" warning may occur before
the battery reaches 20% capacity remaining.
614-40094-00
18
6.3 Display functions
Press the Enter (⮠) button to activate the menu options. Use the two middle buttons (⯅ and ⯆) to scrollthrough the
menu structure. Press the Enter (⮠) button to select an option. Press the (ESC) button to cancelor return to the previous
menu.
Menu map for display functions
Main menu Submenu Display information or Menu function
Measurements -
Load: [Total Load/Load (Primary)/Load (Group 1)/Load (Group 2)] : W, A, VA, pF
[Input/Output] : V, f
[Efficiency] : %
[Battery Info] : %, min, V, number of EBM, Age service, Age Warning
[Average power usage] : Total, Primary, Group 1, Group 2
[Cumulative power] : Total, Since Primary, Since Group 1, Since Group 2
Control
Load Segments
Group 1: ON / OFF
Group 2: ON / OFF
These commands overrule user settings for load segments.
Start battery test Starts a manual battery test (possible if load >10% and battery >80%)
Change battery Disable charger, Replace battery, Update settings
Connectivity test Dry contacts test, Relay card test, Line failure test, Battery low test
Functions reset Reset fault state, Reset power usage, Reset battery life, Card reset, Restore
factory settings
Settings
Local settings Sets product general parameters, see User settings
Input / output
settings Sets input and output parameters
ON / OFF settings Sets ON / OFF conditions
Battery settings Sets battery configuration
Communication
settings
Sets communication parameters (input/output signals, remote signals, IPV4
address)
Event log
View Alarms Displays the alarms stored
View Events Displays the events stored
View All Displays the faults and events stored
Reset All Clears the faults and events stored
Fault log
Fault list Displays the faults stored
Reset fault list Clears faults
Identification Type / Model / Part Number / Serial Number / UPS Firmware / NMC Firmware /
IPV4 Address / IPV6 Address / Com card MAC Address
614-40094-00
19
Main menu Submenu Display information or Menu function
Registration Links to Eaton registration website
614-40094-00
20
6.4 User settings
The following table displays the options that can be changed by the user.
Submenu Available settings Default settings
Local
settings
Language
[English] [Français] [Deutsch] [Español] [Русский]
[Português] [Italiano] [Simplified Chinese] [Japanese]
Menus, status, notices and alarms, UPS fault, Event Log
data and settings are in all supported languages.
[English]
Automatic message for user
configuration when UPS is
powered for the first time.
Date / time Format: [International] [US] [International]
LCD Modify LCD screen brightness and contrast to be adapted
to room light conditions. [0]
Audible
alarm
[Enabled] [Disabled on battery] [Always disabled]
Enable or disable the buzzer if an alarm occurs. [Enabled]
Level: [0-8] [6]
Protected
access
[Enabled] [Disabled]
Allow the user to lock the settings modification. Password
is: 0577 [Disabled]
In/Out
settings
Output
voltage [200 V] [208 V] [220 V] [230 V] [240 V] [230 V]
Input
thresholds
[Normal] [Extended]
Extended mode authorises lower input
voltage(150V)without transferring to battery.
This can be used if the load can withstand low voltage
supply.
[Normal]
Sensitivity
[High] [Low]
Low sensitivity extend the range of input frequency
accepted before transferring to battery.
[High]
Load
segments
[Auto start delay] UPS:[No delay]; Group1:[3s];
Group2:[6s]
[Auto shutdown delay] UPS:[Disabled]; Group1:
[Disabled]; Group2:[Disabled]
Overload
prealarm
[10%] … [105%]
Load % when overload alarm occurs [105%]
ON/OFF
settings Start/Restart
[Cold start]
[Auto restart]
[Auto start]
[Cold start] : ON
[Auto restart] : ON
[Auto start] : OFF
614-40094-00
21
Submenu Available settings Default settings
Forced
reboot
[Yes] [No]
[Timer] [10s] … [180s]
When mains recovers during a shutdown sequence:
If set to Enabled, shutdown sequence will complete and
wait 10 seconds prior to restart,
If set to Disabled, shutdown sequence will not complete,
UPS stays on.
[Yes]
[10s]
Energy saving
(W,%, delay)
[Yes] [No]
[Time] [1min] … [15min]
[Level] [10W] … [1000W-3000W]
If Enabled, UPS will shut-down after defined duration of
back-up time, if load is less than set value.
[No]
[5min]
[100W]
Sleep Mode
[Enabled] [Disabled]
[Timer] [10min] … [120min]
If Disabled, LCD and communication will turn OFF
immediately after UPS is OFF.
If Enabled, LCD and communication stays ON for the set
time period after UPS is OFF (default 90 min).
[Enabled]
[90min]
Site Wiring
Fault
[Enabled] [Disabled]
Prevents the UPS from starting if the phase and neutral
wires are swapped.
[Disabled]
Power Off
alert
[Yes] [No]
If enabled, activates a confirmation screen that requires
user confirmation after pressing the power button, before
UPS shutdown occurs.
[Yes]
Battery
settings
Auto battery
test
In ABM® cycling mode: [No test] [Every ABM® cycle]
In constant charge mode: [No test] [Daily] [Weekly]
[Monthly]
[Every ABM® cycle]
[Weekly]
Battery age
warning
[Enabled] [Disabled]
[6-120]
If Enabled, the UPS displays a battery replacement
reminder through the front LCD and any installed network
communication card after the indicated timeframe has
elapsed (default 48 months).
[Enable]
[48 Month]
Low battery
warning
[Capacity] [0%] … [100%]
[Runtime] [0min] … [60min]
The alarm triggers when the set percentage of battery
capacity or remaining back-up time is reached.
[0%]
[3min]
Restart batt.
level
[0%] ... [100%]
Automatic restart will occur only when the set percentage
of battery charge is reached, and "Auto Restart" is enabled
and set to ON. A setting of 0% allows immediate automatic
restart when utility returns after a UPS shutdown due to
an extended power outage.
[0%]
614-40094-00
22
Submenu Available settings Default settings
Battery
charge mode [ABM® cycling] [Constant charge] [ABM® cycling]
External
battery [Auto detection] [Manual EBM set.] [Manual battery set.]
[Auto detection]
Using standard EBM, UPS
automatically detects the
number of EBM connected
Deep disch.
protect.
[Enabled] [Disabled]
If set to Enable, the UPS operates within the normal design
range of the battery during discharge.
If set to Disable, the UPS allows deeper battery discharge
to extend battery runtime at the expense of long-term
battery life (warranty is also void if set to disable).
[Enable]
Comm
settings
Input signals
[ROO] [RPO] [DB9-4]
Sets Input signals parameters (function, delay, operation)
through external contact connectors or RS232 port.
ROO port:
- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdown
commands]
- [Delay]: [0s] … [999s]
- [Active]: [Open] [Closed]
RPO port:
- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdown
commands]
- [Delay]: [0s] … [999s]
- [Active]: [Open] [Closed]
DB9-4 port:
- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdown
Commands]
- [Delay]: [0s] … [999s]
- [Active]: [Low] [High]
[No]
[0s]
[Closed]
[No]
[0s]
[Open]
[No]
[0s]
[High]
Outputs
signals
[Relay] [DB9-1] [DB9-7] [DB9-8]
Sets events or fault that will actuate Output signal
parameters through external contact connector or RS232
port
[Relay]: [On bat] [Low bat] [Bat fault] [UPS OK] [Load
protected] [Load powered] [General alarm] [OVL pre-
alarm] [Batt Disconn]
[DB9-1]: [On bat] [Low bat] [Bat fault] [UPS OK] [Load
protected] [Load powered] [General alarm] [OVL pre-
alarm] [Batt Disconn]
[DB9-7]: [On bat] [Low bat] [Bat fault] [UPS OK] [Load
protected] [Load powered] [General alarm] [OVL pre-
alarm] [Batt Disconn]
[DB9-8]: [On bat] [Low bat] [Bat fault] [UPS OK] [Load
protected] [Load powered] [General alarm] [OVL pre-
alarm] [Batt Disconn]
[Relay] : [Bat fault]
[DB9-1] : [Low bat]
[DB9-7] : [UPS OK]
[DB9-8] : [On bat]
614-40094-00
23
1.
2.
Submenu Available settings Default settings
Remote
command
[Yes] [No]
If Enabled, shutdown or restart commands from software
are authorized.
[Yes]
Shutdown
commands
[Send CMD] [Output OFF] [OFF delay] [restart]
Sets events or fault that will actuate Output signal
parameters through external contact connector or RS232
port
[Send CMD]: [Yes] [No]
[Output OFF]: [No] [UPS] [Group 1]
[Group 2] [Group 1 + 2]
[OFF delay]: [0s] …[999s]
[Restart]: [Yes] [No]
For a proper server shutdown please make sure that the
Output OFF delay is long enough
Send CMD: [No]
Output OFF: [No]
OFF delay: [0s]
Restart: [Yes]
On battery
notice delay
[0s] ... [99s]
Sets delay before providing an on battery notice to
software. [0s]
General
alarm
[On battery] [Battery fault] [Overload pre-alarm] [Internal
fault] [Ambient temp.] [Fan lock] [Current limit] [Short
circuit] [Inverter overload] [Power overload] [Low battery]
[UPS OK] [Load protected] [Load powered]
Defines which event or fault will generate a general alarm
through Output signal screen.
[Internal fault]
Set Comm
Card IPv4
[DHCP] : [Yes] [No]
[IP Adress] [Subnet mask] [Gateway]
The UPS does not display the IPv4 settings menu by
default, you can activate it by a communication
command.
[Yes]
XXX.XXX.XXX.XXX
6.5 Communication ports
Connection of RS232/USB communication port
Connect the RS232 (15) or USB (16) communication
cable to the serial or USB port on the computer
equipment.
Connect the other end of the communication cable
(15) or (16) to the USB (5) or RS232 (6)
communication port on the UPS.
The UPS can now communicate with Eatonpower
management software.
You can improve the remote monitoring and power
managment of the UPS by adding acommunication
cardcompatible with the 5PXproduct.
614-40094-00
24
•
•
•
1.
2.
3.
Characteristics of the contact RS232 communication port
Contact characteristics
(optocoupler)
Voltage: 48 V DC max
Current: 25 mA max
Power: 1.2 W
Pin Signal Direction Function
1 Bat low Output Low Battery Output
2 TxD Output Transmit to external device
3 RxD Input Receive from external device
4 I/P SIG Input -
5 GNDS - Signal Common tied to chassis
6 PNP Input Plug and Play
7 UPS OK Output UPS OK
8 BAT mode Output UPS on battery mode
9 +5V Output Power supply for external
signal or options
Installation of the communication cards
It is not necessary to shutdownthe UPS before
installinga communication card.
Remove the slot cover (9)secured by screws.
Insert the communicationcard in the slot.
Secure the card cover withthe two screws to
connect the comm card to the ground.
614-40094-00
25
•
•
•
•
6.6 UPS remote control functions
Connectivity cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with differenttypes of
devices. The5PXmodels have one available communication bay for the following connectivity cards:
Gigabit Network card(Network-M2) : provides a Gigabit Ethernet connection and enables secure UPS monitoring
over HTTPS web browser interface, SNMP v1/v3 protocol and email alarms. In addition, up to 3 Environmental
Monitoring Probes can be attached to obtain humidity, temperature, smoke alarm, and security information.
Industrial Gateway card(INDGW-M2) :Provides Modbus RTU and Modbus TCP communication support in addition
to the same secure UPS monitoring, management and sensor capability as the Gigabit Network card.
Relay-MS card: provides isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery low, UPS
alarm/OK, or on Bypass.
INDRELAY-MS : The Industrial relay Card-MS (INDRELAY-MS) provides a simple way to remotely input UPS information
to an alarm system, PLC or a computer system via dry contacts. It offers five isolated dry contact outputs and one
isolated dry contact input.
Programmable signal inputs
The 5PX incorporates several programmable signal inputs: oneRemote Power Off (RPO) input terminal, one RemoteOn/
Off (ROO) input terminal, one RS-232 input (pin-4).
Signalinputs can be configured (see Settings > Comm settings > Signal Input) to have one of the following functions:
Function Description
No No function. (Please choose a function if you want to use input signal.)
RPO Remote Power off (RPO) is used to shutdown the UPS remotely.
ROO Remote On/Off allows remote action of a button or other interface to switch On/
Off the UPS. (Cold start is prohibited while using the ROO function.)
Building alarm Active input generates an alarm “building alarm”.
614-40094-00
26
•
•
•
•
•
•
1.
Function Description
Shutdown commands
Active input turns UPS output (or outlet groups) off after a user defined
shutdown delay but keeps on charging batteries according to a selected charging
scheme; inactive input does not abort shutdown countdown. Depending on the
“Restart” parameter (see Settings > Comm Settings > Shutdown commands) the
unit may startup automatically.
Warning: signal inputs have no function by default; please choose a function through the LCD(Settings > Com
settings > Input signals).
See below 2 examples of configuration with RPO terminal used as RPO function and ROO terminal use asROO function:
Remote Power Off (RPO)
RPO is used to shutdown the UPS remotely when the contact is open. This feature can be used for shuttingdown the load
and the UPS by thermal relay, for example, in the event of room over temperature. When RPO is activated, the UPS turns
off the output and shuts down all power converters immediately (except for logic power).The UPS remains "ON" to alarm
the fault.
The RPO circuit is a safety extra low voltage (SELV) circuit. This circuit must be separated from anyhazardous voltage
circuits by reinforced insulation.
The RPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The
RPO switch must be a dedicated latching-type switch not tied into any other circuit. The RPO signal must remain
active for at least 250 ms for proper operation.
To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be
disconnected from the UPS when the Remote Power Off function is activated.
RPO connections:
RPO Comments
Connector type Terminal, 14 AWG Maximum
wires
Terminal rating 60 V DC/30 V AC 20 mA max
Remote On/Off (ROO)
Remote On/Off allows remote action of button to switch On/Off the UPS.
When contact changes from open to closed, the UPS is switched-on (or stays On).
When contact changes from closed to open, the UPS is switched-off (or stays Off).
On/Off control via button has priority over the remote control.
The ROO function is only active after the first use of the "Remote OFF" function.
ROO Comments
Connector type Terminal, 14 AWG Maximum
wires
Terminal rating 60 V DC/30 V AC 20 mA max
Remote control connection and test
Check the UPS is shut down and the electrical supply network disconnected.
614-40094-00
27
2.
3.
4.
5.
6.
Remove RPO connector from the UPS by removing the screws.
Connect a normally closed volt-free contact between the two pins of connector.
Normally closed
Contact open: shut down of UPS.
To return to normal operation, deactivate the external remote shut
down contactand restart the UPS from the front panel.
Plug the RPO connector into the back of the UPS and fix the screws.
Connect and restart the UPS according to the previously described procedures.
Activate the external remote shut down contact to test the function.
Always test the RPO function before applying your critical load to avoid accidental load loss.
Programmable signal outputs
The5PX incorporates several programmable signal outputs: one relay output and two optocoupler outputs (DB9 pins 1
and 8).Signal outputs can be configured (see Settings > Comm settings > Output Signals) to report thefollowing
information:
Signal Default assignment Description
On battery (On Bat) DB9-Pin 8 UPS is in battery mode
Low battery (Low Bat) DB9-Pin 1 UPS is in battery mode and has reached the low
battery alarm threshold
Battery fault (1) Relay output Battery fault
UPS OK DB9-Pin 7 Load is powered with no alarm
Load protected - UPS is on inverter, with no alarm and ready to go to
battery
Load powered - Load is powered
General alarm -
Choose events that will trigger this alarm trough
the LCD (Settings > Comm settings > General
alarm).
For more information on possible events please
look at User settings
OVL pre-alarm - Overload pre-alarm
Bat disconn - Battery is disconnected
(1) Relay output:
614-40094-00
28
1.
2.
6.7 Eaton Intelligent Power Software suite
Eaton Intelligent Power Software suite is available from eaton.com/downloads.
Eaton Software suite provides up-to-date graphics of UPS power and system data and power flow.
It also gives you a complete record of critical power events, and it notifies you of important UPS or powerinformation.
If there is a power outage and the 5PX UPS battery power becomes low, Eaton Software suite can automaticallyshut
down your computer system to protect your data before the UPS shutdown occurs.
6.8 Cybersecurity
Eaton is committed to minimizing the Cybersecurity risk in its products and employs cybersecurity bestpractices and the
latest cybersecurity technologies in its products and solutions, making them more secure,reliable and competitive for
our customers. Eaton also offers Cybersecurity Best Practices whitepapers to itscustomers, referenced at
www.eaton.com/cybersecurity.
7 Operation
7.1 Start-up and normal operation
Check that the indications on the name plate located on the back of the UPS meets to the AC power source and the
true electrical consumption of the total load.
Battery charge
The UPS charges the battery as soon as it is connected to the AC outlet, whether the ON/OFF button is pressedor not. It is
recommended that the UPS be permanently connected to the AC power supply toensure the best possible autonomy.
On the first startup of the UPS, you will need to configure the output voltage and time of the UPS.
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. The UPS front panel display illuminates and shows Eaton logo.
3. Verify that the UPS status screen shows .
4. Press the button on the UPS front panel for at least two seconds.
5. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing; if the
indicator is on, do not proceed until all alarms are clear (see "Troubleshooting" section). Check the UPS status from the
front panel to view the active alarms. Correct the alarms and restart if necessary.
6. Verify that the indicator illuminates solid, indicating that the UPS is operating normally and any loads are powered
and protected. The UPS should be in Normal mode.
7.2 Starting the UPS on battery
Before using this feature, the UPS must have been powered by utility power with output enabled at leastonce.
Battery start can be disabled. See the "Cold start" setting in "ON/OFF Settings".
To start the UPS on battery:
When the UPS is disconnected from the AC power source, press the button on the UPS front panel.
The UPS transfers from Standby mode to Battery mode. The indicator illuminates solid.
The UPS supplies power to your equipment.
Check the UPS front panel display for active alarms or notices besides the "Battery mode" and related notifications
that indicates missing utility power. Resolve any active alarms before continuing. See "Troubleshooting".
Check the UPS status from the front panel to view the active alarms. Correct the alarms and restartif necessary.
614-40094-00
29
•
•
•
•
•
7.3 UPS shutdown
To shut down the UPS:
Press the button on the front panel for three seconds.
A confirmation message will appear. When confirmed, the UPS starts to beep and shows a status of "UPS shutting OFF...".
The UPS thentransfers to Standby mode, and the indicator turns off.
7.4 Operating modes
The Eaton5PX front panel indicates the UPS status through the UPS indicators located above the LCD screen.
Normal mode
When the green sinewave symbol is illuminated, the UPS is providing protected AC power output.The UPS monitors and
charges the batteries as needed and providespower protection to yourequipment.
Battery mode
When the UPS is operating during a power outage, the alarm beeps once every ten seconds and theindicator illuminates
solid. The necessary energy is provided by the battery.
When the utility power returns, the UPS transfers to Normal mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the audible alarm beeps once every three seconds.
This warning is approximate, and the actual time to shutdown may vary significantly; gracefully shutdown all applications
on connected equipment due to imminent UPS shutdown.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Low-battery warning
The indicator illuminates solid.
The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all applications on the connected equipment becauseautomatic UPS
shutdown is imminent.
End of battery backup time
LCD displays "End of backup time".
All the LEDs go OFF.
The audible alarm stops.
7.5 Return of AC input power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart functionhas been
disabled) and the load is supplied again.
7.6 Configuring battery settings
Automatic battery test
Automatic battery tests are done every week in constant charging mode and at each cycle in ABM® mode. Thetests
frequency can be modified.
During the test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds under load.
Battery mode is not displayed and battery low alarm does not activate during a battery test.
The battery test may be postponed due to bad conditions, or failed if battery is not ok.
Low battery warning
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than the
setting capacity threshold (0% by default).
This threshold can be modified.
External battery setting
614-40094-00
30
1.
2.
1.
2.
The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM or in
Ah.
Deep discharge protection
This setting is recommended to avoid damaging the battery. Warranty is void if deep discharge protection is
disabled.
7.7 Retrieving the event log
To retrieve the event log through the display:
Press any button to activate the menu options, then select event log.
Scroll through the listed events.
7.8 Retrieving the fault log
To retrieve the fault log through the display:
Press any button to activate the menu options, then select fault log.
Scroll through the listed faults.
8 UPS maintenance
8.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very
dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25 °C (77 °F).
The batteries are rated for a 3-5 year service life. The length of service life varies, depending on the frequency of usage
and ambient temperature (life divided by 2 each 10 °C above 25 °C).
If the UPS requires any type of transportation, verify that the UPS is turned off.
Batteries used beyond expected service life will often have severely reduced runtimes. Replace batteries at least every 4
years to keep units running at peak performance.
Batteries runtime will be reduced at low temperature (below 10 °C).
8.2 Storing the equipment
If you store the equipment for a long period, recharge the battery every 6 months by connecting the UPS toutility power.
The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommendsthat the batteries charge
for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never
recharged, do not use them. Contact your servicerepresentative.
614-40094-00
31
•
•
a.
b.
c.
d.
•
•
•
•
•
•
•
8.3 When to replace batteries
Eaton UPS batteries have an expected life span of 3-5 years.
After 4 years of operation, the UPS will provide a battery replacement notification reminding you that your batteries are
nearing the end of their useful life. You should take proactive steps to ensure you replace your batteries for optimal
operation and reliability.
Contact your service representative to order new batteries.
Battery recommended replacement date and reference can be accessed through the LCD (Measurements > Battery).
8.4 Replacing batteries
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
For battery replacement, follow Eatoninstructions provided onwww.eaton.eu/BatteryServices.
Batteries can be replaced easily without turning off the UPS or disconnecting the load.
Consider all warnings, cautions, and notes before replacing batteries.
Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions.
Keep unauthorized personnel away from batteries.
Batteries can present a risk of electrical shock or burn from high short circuit current.
Observe the following precautions:
Remove watches, rings, or other metal objects,
Use tools with insulated handles,
Do not lay tools or metal parts on top of batteries,
Wear rubber gloves and boots.
When replacing batteries, replace with the same type and number of batteries or battery packs. Contact your service
representative to order new batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes and may be
extremely toxic.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact
with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can
cause injury.
Disconnect charging source prior to connecting or disconnecting battery terminals.
614-40094-00
32
Replacing the internal battery :
The internal battery is heavy. Use caution when handling the heavy batteries.
A Phillips head screwdriver is needed to perform this procedure
1 - Pull off the front panel by pressing the tabs on both
sides.
2 - Disconnect the battery pack byseparating the
connectors(never pull on the wires).
3 - Remove the metal protection coverin front of the
battery (three screws or two screws for 3U models).
4 - Pull the plastic tab to removethe battery pack and
replace it.
614-40094-00
33
1.
2.
3.
1.
2.
1.
2.
3.
Warning: take care not to reverse the polarity + (red) and - (black) when connecting the batteries as this
willdestroy the device.
Testing new batteries :
To test new batteries:
Charge the batteries for 48 hours.
Press any button to activate the menu options.
Select Control then Start battery test. The UPS starts a battery test if the batteries are fully charged, the UPS is in
Normal mode with no active alarms, and the bypass voltage is acceptable. During the battery test, the UPS transfers
to Battery mode and discharges the batteries for 10 seconds. The front panel displays "Battery test in progress" and
the percentage of the test completed.
8.5 Replacing the UPS equipped with a HotSwap MBP
The HotSwap MBP module makes itpossible to service
or even replacethe UPS without affecting the
connectedloads (HotSwap function).
Maintenance
Set switch (45) to Bypass position.The red LED on the
HotSwap MBPmodule goes ON, indicating that
theload is supplied directly with AC inputsource
power.
Stop the UPS by pressing the button on the UPS
control panel. LED (43) "UPS ON - OK to switch" goes
OFF, the UPS can now be disconnected and replaced.
Return to normal operation
Check that the UPS is correctly connected to the
HotSwap MBP module.
Start the UPS by pressing the button on the UPS
control panel.LED (43) "UPS ON - OK to switch"
onthe HotSwap MBP module goes ON(otherwise,
there is a connection errorbetween the HotSwap
MBP moduleand the UPS).
Set switch (45) to Normal position.The red LED on
the HotSwap MBPmodule goes OFF.
8.6 Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the usedequipment.
eaton.com/recycling
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required.
Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid batteries andmust
be disposed of properly. For more information, contact your local recycling/reuse or hazardous wastecenter.
614-40094-00
34
•
•
•
1.
2.
3.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact yourlocal
recycling/reuse or hazardous waste center.
9 Troubleshooting
TheEaton5PXis designed for reliable, autonomous operation while providing you with notifications and alerts whenever
a potential operational or performance issue occurs.
Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are
preventive alarms intended to alert the user.
Events are silent status information that are recorded into the Event log. Example = "AC freq in range".
Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking. Some alarms
may be announced by a beep every 3 seconds. Example = "Battery low".
Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on the LCD with a
specific message box. Example = Out. short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.
9.1 Typical alarms and faults
To check the Event log or Fault log:
Press any button on the front panel display to activate the menu options.
Press the down button to select Event log or Fault log.
Scroll through the listed events or faults.
614-40094-00
35
The following table describes typical conditions:
Conditions Possible cause Action
Battery mode
LED is On.
1 beep every 10 seconds
A utility failure has occurred and the UPS is
in battery mode.
The UPS is powering the equipment with
battery power. Prepare your equipment for
shutdown.
Battery low
LED is On.
1 beep every 3 seconds
The UPS is in Battery mode and the battery
is running low.
This warning is approximate, and the
actual time to shutdown may vary
significantly. Depending on the UPS load
and number of Extended Battery Modules
(EBMs), the "Battery Low" warning may
occur before the batteries reach 20%
capacity.
No battery
LED is On
Beep continuous
The batteries are disconnected.
Verify that all batteries are properly
connected. If the condition persists,
contact your service representative.
Battery fault
LED is On.
Beep continuous
The battery test is failed due to bad or
disconnected batteries.
Verify that all batteries are properly
connected. If the condition persists,
contact your service representative.
The UPS does not provide
the expected backup time. The batteries need charging or service.
Apply utility power for 48 hours to charge
the batteries. If the condition persists,
contact your service representative.
Power Overload
LED is On
Power requirements exceed the UPS
capacity (greater than 100% of nominal;
see “User Settings” for specific output
overload ranges).
Remove some of the equipment from the
UPS. The UPS continues to operate, but
may shut down if the load increases. The
alarm resets when the condition becomes
inactive.
UPS overtemperature
LED is On
1 beep every 3 seconds
The UPS internal temperature is too high or
a fan has failed. At the warning level, the
UPS generates the alarm but remains in the
current operating state. If the temperature
rises another 10°C, the UPS shuts down.
Clear vents and remove any heat sources.
Allow the UPS to cool. Ensure the airflow
around the UPS is not restricted. Restart
the UPS. If the condition continues to
persist, contact your service
representative.
The UPS does not start
The input source is not connected correctly. Check the input and battery connections.
The Remote Power Off (RPO) switch is active
or the RPO connector is missing.
If the UPS Status menu displays the
"Remote Power Off" notice, deactivate the
RPO input.
614-40094-00
36
•
•
•
•
•
•
9.2 Silencing the alarm
Press the ESC (Escape) button on the front panel display to silence the alarm. Check the alarm condition andperform the
applicable action to resolve the condition. If the alarm status changes, the alarm beeps again,overriding the previous
alarm silencing.
9.3 Service and support
If you have any question or problem with the UPS, call Eaton or your local service representative in your country / region.
Please have the following information ready when you call for service:
Model number
Serial number
Firmware version number
Date of failure or problem
Symptoms of failure or problem
Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization (RMA) number. This number must appear on the
outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the
Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A
replacement or repair unit will be shipped freight prepaid for all warrantied units.
For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor
nearest you.
10 Specification and technical characteristics
5PX 1000 / 1500 models :
5PX 2200 / 3000models :
10.1 UPS model list
Description Catalog Number Power rating Configuration
Eaton 5PX 1000i RT2U G2 5PX1000IRT2UG2 1000W/1000VA Rack / Tower
Eaton 5PX 1500i RT2U G2 5PX1500IRT2UG2 1500W/1500VA Rack / Tower
Eaton 5PX 2200i RT2U G2 5PX2200IRT2UG2 2200W/2200VA Rack / Tower
614-40094-00
37
Description Catalog Number Power rating Configuration
Eaton 5PX 2200i RT3U G2 5PX2200IRT3UG2 2200W/2200VA Rack / Tower
Eaton 5PX 3000i RT2U G2 5PX3000IRT2UG2 3000W/3000VA Rack / Tower
Eaton 5PX 3000i RT3U G2 5PX3000IRT3UG2 3000W/3000VA Rack / Tower
10.2 Extended Battery Module model list
Model Catalog Number Configuration Battery voltage Use with
Eaton 5PX EBM 48V
RT2U G2 5PXEBM48RT2UG2 Rack / Tower 48Vdc 5PX1000IRT2UG2,
5PX1500IRT2UG2
Eaton 5PX EBM 72V
RT2U G2 5PXEBM72RT2UG2 Rack / Tower 72Vdc 5PX2200IRT2UG2,
5PX3000IRT2UG2
Eaton 5PX EBM 72V
RT3U G2 5PXEBM72RT3UG2 Rack / Tower 72Vdc 5PX2200IRT3UG2,
5PX3000IRT3UG2
10.3 Weights and dimensions
Description (UPS) Weights (lb / kg) Dimentions (inch / mm) D x W x H
5PX1000IRT2UG2 43.2 / 19,6 17.6x17.2x3.4 / 448x438x85,5
5PX1500IRT2UG2 49.4 / 22,4 17.6x17.2x3.4 / 448x438x85,5
5PX2200IRT2UG2 62.2 / 28,2 23.7x17.2x3.4 / 603x438x85,5
5PX2200IRT3UG2 60.6 / 27,5 19x17.2x5.1 / 483x438x129
5PX3000IRT2UG2 69.9 / 31,7 23.7x17.2x3.4 / 603x438x85,5
5PX3000IRT3UG2 68.6 / 31,1 19x17.2x5.1 / 483x438x129
Description (EBM) Weights (lb / kg) Dimentions (inch / mm) D x W x H
5PXEBM48RT2UG2 61.3 / 27,8 17.6x17.2x3.4 / 448x438x85,5
5PXEBM72RT2UG2 89.1 / 40,4 23.7x17.2x3.4 / 603x438x85,5
5PXEBM72RT3UG2 87.5 / 39,7 19x17.2x5.1 / 483x438x129
10.4 Electrical input
Default frequency 50Hz
Nominal frequency 50/60Hz
Frequency range 47-70Hz
614-40094-00
38
Catalog Number Default input
(Voltage/Current) Input nominal voltages Input voltage window
5PX1000IRT2UG2 230V/10A
200-240V
160-294V
adjustable to 150~294
5PX1500IRT2UG2 230V/10A
5PX2200IRT2UG2 230V/16A
5PX2200IRT3UG2 230V/16A
5PX3000IRT2UG2 230V/16A
5PX3000IRT3UG2 230V/16A
10.5 Electrical input connections
Catalog Number Input connection Input cable
5PX1000IRT2UG2 IEC C14-10A Not provided
5PX1500IRT2UG2
5PX2200IRT2UG2
IEC C20-16A Schuko 16A to IEC320/16A
5PX2200IRT3UG2
5PX3000IRT2UG2
5PX3000IRT3UG2
10.6 Electrical output
All models Normal mode Battery mode
Voltage regulation Boost : Vin*1.15
Buck : Vin*0.87 (-10% ,6%)
Efficiency >96% 1000-2200 > 82%
3000 > 85%
Frequency regulation +/-0.1 Hz
Nominal output 200/208/220/230/240V
Frequency Follows input frequency 50/60Hz
Output overload
[105%,120%] 30min
[120%,150%]5min
>150% 10S
[105% ~110%] 10s
[110%~150%]1s,
>150% 0.15s
614-40094-00
39
All models Normal mode Battery mode
Short circuit current limitationin battery
mode
Model Current
limitation
1000 31A
1500 38A
2200 38A
3000 64A
Transfer time Utility Outage: 1-4ms for normal mode, >5ms for sensitive mode
Utility abnormal: <10ms for normal mode ,<25ms for sensitive mode
10.7 Electrical output connection
Catalog Number Output conection Output cable
5PX1000IRT2UG2 (4) IEC10A Primary group
(2) IEC10A Group 1
(2) IEC10A Group 2
(2) IEC10A
5PX1500IRT2UG2
5PX2200IRT2UG2
(4) IEC10A + (1) IEC16A Primary group
(2) IEC10A + (1) IEC16A Group 1
(2) IEC10A Group 2
5PX2200IRT3UG2
5PX3000IRT2UG2
5PX3000IRT3UG2
10.8 Battery
Internal batteries EBM
Specifications
1000VA: 48Vdc - 4 x 12V, 7Ah (9Ah max)
1500VA: 48Vdc - 4 x 12V, 9Ah
2200VA: 72Vdc - 6 x 12V, 7Ah (9Ah max)
3000VA: 72Vdc - 6 x 12V, 9Ah
5PXEBM48RT2UG2: 48Vdc - 2 x 4 x 12V, 2 x 9Ah
5PXEBM72RT2UG2: 72Vdc - 2 x 6 x 12V, 2 x 9Ah
5PXEBM72RT3UG2: 72Vdc - 2 x 6 x 12V, 2 x 9Ah
Type Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-5 year float service life at
25°C (77°F).
Monitoring Advanced monitoring for earlier failure detection and warning
EBM battery cable
length
2U EBM cable length:350mm/13.78in
3U EBM cable length:530mm/20.87in
614-40094-00
40
10.9 Environmental and safety
Standards
IEC/EN 62040-1:2008+A1:2013
EN IEC 62040-2: 2018
IEC 62040-2: 2016
FCC CFR Title 47, Part 15, Subpart B
IEC/EN 62040-3
IEC 62040-1:2017
UL1778 5th edition
CSA 22.2
EMC (Emissions)
EN IEC 62040-2: 2018 C1
EN 62040-2: 2006 C1
IEC 62040-2: 2016 C1
EN 55011:Class B
CISPR11 Class B
CISPR32 Class B
FCC part 15 Class B
EMC (Immunity)
IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV Air Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): 4 kV
IEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV Common Mode
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
Agency markings
CE, cTUVus, EAC, Cm, Ukr, UKCA,
KC (only on 5PX1500IRT2UG2, 5PX2200IRT2UG2, 5PX3000IRT2UG2,
5PX3000IRT3UG2)
Operating temperature 0 to 40 °C (32 to 104 °F)
Storage temperature -15 to 50°C (5 to 122 °F)
Relative humidity 20 to 90 % (without condensation)
Operating altitude Up to 3,000 meters (9,843 ft) above sea level, no derating for 40°c
(104°F) room temperature
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise Line mode:<40dB Buck/boost mode:<45 dB
Batt. Mode: <45dB, 50dB for 3K
11 Glossary
AVR
The Automatic Voltage Regulationmaintains a constant voltage level for
electrical equipment loads when the voltage falls outside the voltage tolerance
range.
Backup time
Time during which the load can be supplied by the UPS operating on
batterypower.
EBM
Extended Battery Module
614-40094-00
41
Low-battery warning
This is a battery-voltage level indicating that battery power is low and that the
user must take action before the UPS shuts down.
Load
Devices or equipment connected to the UPS output.
Normal mode
The normal UPS operating mode in which the AC source supplies the UPS which,
in turn, provides AC power to the connected loads.
Normal AC source
Normal source of power for the UPS.
OVL
Overload.When the load exceeds 100% of the maximum load of the UPS.
Relay contacts
Contacts supplying information to the user in the form of signals.
UPS
Uninterruptible Power System.