Eaton 9PX5Ki User Manual
Displayed below is the user manual for 9PX5Ki by Eaton which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals
9SX 5000
9SX 6000
9PX 5000
9PX 6000
9SX EBM 180V
9PX EBM 180V
Installation
and user manual
Copyright © 2012
EATON
All rights reserved.
Service and support:
Call your local service representative
5-6kVA EU_EN
5-6kVA EU_EN
Page 2
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
.
This manual contains important instructions
that should be followed during installation and maintenance of the UPS and batteries.
The 9SX and 9PX models that are covered in this ma nual are intended for installation
in an environment within 0 to 40°C, free of conductive contaminant.
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules
.
These limits are designed to provide reason able protection against
harmful interference when the equipment is operated in a commercial environment
.
This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications
.
Operation of
this equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his ow n expense.
Certification standards
p
Safety: IEC/EN 62040-1 / Ed.1: 2008
.
UL 1778 4
th
edition
p
EMC: IEC/EN 62040-2 / Ed.2: 2006
.
FCC part 15 Class A.
p
Performance: IEC/EN 62040-3 / Ed.2.0: 2011.
p
IEC 61000-4-2 (ESD): level 3.
p
IEC 61000-4-3 (Radiated field): level 3.
p
IEC 61000-4-4 (EFT): level 4.
p
IEC 61000-4-5 (Fast transients): level 4.
p
IEC 61000-4-6 (Electromagnetic field): level 3.
p
IEC 61000-4-8 (Conducted magnetic field): level 4.
Special symbols
The following are examples of symbols used on the UP S or accessories to alert yo u to important
information:
RISK OF ELECTRIC SHOCK
- Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the U PS batte ries in the trash
.
This product contains sealed lead a cid batteries an d must be disposed a s it's explain in this manu al.
For more information, conta ct your local recycling/reuse or hazardo us waste center.
This symbol indicates that you should not discard waste electrical or electronic equip ment (W EEE)
in the trash
.
For proper disposal, contact your local recycling/reuse or hazardo us w aste cen ter.
Information, advice, help.
Refer to the user manual of UPS accessories.
Page 3
5-6kVA EU_EN
SAFETY INSTRUCTIONS
Safety of persons
p
The system ha s its own pow er source (the battery)
.
Consequently, the power outlets may b e energized
even if the systems is disconnected fro m the AC power source
.
Dangerous voltage levels are present
within the system
.
It should be opened exclusively by qualified service personnel.
p
The system must be properly grounded
.
p
The battery supplied with the system contains small amounts of toxic materials
.
To avoid accidents, the directives listed be low must be observed:
- servicing of batteries should be performed or supervised by personnel knowledgeable about batteries
and the required precautions
.
- when replacing batteries, replace with the sa me type and number of batteries or battery packs
.
- do not dispose of batteries in a fire
.
The batteries may explode
.
- batteries constitute a danger (electrical shock, burns)
.
The short-circuit current may be very high.
Precautions must be tak en for all handling:
p
Wear rubber gloves and boots.
p
Do not lay tools or metal parts on top of batteries
.
p
Disconnect charging sour ce prior to connecting or disconnecting battery terminals.
p
Determine if battery is inadvertently grounded
.
If inadvertently grounded, remove source from ground
.
Contact with any part of a grounded batter y can result in electrical shock
.
The likelihood of such shock
can be reduced if such grounds are remo ved during installation and maintenan ce (applicable to
equipment and remote battery supplies n ot having a grounded supply circuit).
Product safety
p
The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
p
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with branch circuit
overcurrent protection for : 30A ra ting, for 5-6kVA mod els in accordance with th e National Electric Code,
ANSI/NFPA 70 (US installations only)
.
The upstream circuit breaker must be easily accessible
.
The unit can be disconne cted from AC power source by opening this circuit breaker.
p
Disconnection and overcurrent protection devices shall be provided by others for permanently
connected AC input/output circuits.
p
Check that the indications on th e rating plate correspond to your AC powered syste m and
to the actual electrical consumption of all the equipment to be connected to the system.
p
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
p
Never install the system near liquids or in an excessively damp environm ent.
p
Never let a foreign bo dy penetrate inside the syste m.
p
Never block the ventilation grates of the system.
p
Never expose the system to direct sunlight or source of heat.
p
If the system must be stored prior to installation, storage must be in a dry place.
p
The admissible storage temperature range is -15ºC to +50ºC.
p
The system is not for use in a compu ter room AS DEFINED IN the standard for the Prot ection
of Information Techn ology Equipment, ANSI/NFPA 75 (US installations only).
Contact Eaton resellers to order a special battery kit if needed to meet the NE code requirement.
Special precautions
All handling operations will require at least two people (unpacking, installation in rack system).
Before and after the installation, if the UPS remains de-e nergized for a long period, th e UP S mu st b e
energized for a period of 24 hour s, at least once every 6 months (for a normal storage tempera ture
less than 25°C).
This charges the battery, thus avoiding possible irreversible damage.
During the replacement of the Battery Module, it is imperative to use the same type and number of
element as the original Battery Module provided with the UPS to maintain an identical level of
performance and safety
.
In case of doubt, don’t hesitate to contact your EATON representative.
All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY
.
There are NO USER SERVICEABLE PARTS inside the UPS.
5-6kVA EU_EN
p
p
p
p
Page 4
Contents
1. Introduction.......................................................................................
6
1.1 Environmental protection...............................................................................................
6
2
. Presentation ......................................................................................
8
2.1
Standard installations .....................................................................................................
8
2.2
Rear panels ....................................................................................................................
9
2.3
Accessories ................................................................................................................. 10
2.4
Control panel
................................................................................................................ 11
2.5
LCD description ...........................................................................................................12
2.6
Display functions .........................................................................................................13
2.7
User settings ...............................................................................................................13
3
. Installation ......................................................................................
15
3.1
Inspecting the equipment ...........................................................................................15
3.2
Unpacking the cabinet .................................................................................................15
3.3
Checking the accessory kit ..........................................................................................16
3.4
Connecting the EBM(s) ............................................................................................... 17
3.5
Connecting other accessories .................................................................................... 17
3.6
Tower installation .........................................................................................................18
3.7
Rack installation ...........................................................................................................19
3.8
Installation requirements .............................................................................................
21
3.9
Installation depending on the system earthing arrangement (SEA).............................
22
4
. Power cables connection ...............................................................
23
4.1
Access to terminal blocks ............................................................................................
23
4.2
Input/Output connection ..............................................................................................
23
5
. Operation.........................................................................................
24
5.1
UPS startup and shutdown ..........................................................................................
24
5.2
Operating modes .........................................................................................................
25
5.3
Transferring the UPS between modes .........................................................................
25
5.4
Set ting High Efficiency mode ......................................................................................
26
5.5
Configuring Bypass settings ........................................................................................
26
5.6
Configuring battery settings ........................................................................................
26
5.7
Retrieving the Event log...............................................................................................
27
5.8
Retrieving the Fault log ................................................................................................
27
6
. Communication ..............................................................................
30
6.1
Communication ports ..................................................................................................
28
7. UPS maintenance............................................................................
32
7.1 Equipment care............................................................................................................
32
7.2 Storing the equipment .................................................................................................
32
7.3 When to replace batteries ...........................................................................................
32
7.4 Replacing batteries ......................................................................................................
33
7.6 Recycling the used equipment ....................................................................................
36
8
. T roubleshooting ..............................................................................
37
8.1
Typical alarms and fa ults ..............................................................................................
37
8.2
Silencing the alarm
......................................................................................................
39
8.3
Service and support .....................................................................................................
39
9
.
Specifications
..................................................................................
40
9.1
Model specifications ....................................................................................................
40
10. Glossary .........................................................................................
43
Page 5
5-6kVA EU_EN
1. Introduction
Thank you for selecting an EATON prod uct to protect your electrical equipment
.
The 9SX and 9PX range has been designed with the utmost care.
We recommend that you tak e the time to read this man ual to tak e full advantag e of the many features
of your UPS (Uninterruptible Power System)
.
Before installing your 9SX a nd 9PX, please read th e booklet presen ting the safety instruction s.
Then follow the indications in this manual
.
To discover the entire range of EATON products and the options available for the 9SX and 9PX range,
we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
1.1 Environmental protection
EATON has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, sep arate the various packing co mponents.
p
The cardboard we use comprises over 50% of recycled cardboard.
p
Sacks and bags are made of polyethylene .
p
Packing materials are recyclable and bear the appropriate identification symbol
Materials
Abbreviations
Polyethylene terephthalat
PET
High-density polyethylene
HDPE
Polyvinyl chloride
PVC
Low-density polyethylene
LDPE
Polypropylene
PP
Polystyrene
PS
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compliance with local regulations.
EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.
Product
The product is made up of r ecyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a pr ocessing center for electrical and
electronic waste.
Battery
The product contains lead- acid batteries that must be proce ssed according to applicable local regulations
concerning batteries
.
The battery may be removed to comply with regulations and in view of correct disposal.
5-6kVA EU_EN
01
PET
01
PET
Number in
the symbols
01
02
03
04
05
06
Page 6
1. Introduction
The Eaton® 9SX and 9PX uninterrup tible power system (UPS) protects your sensitive electronic e quipment
from the most common power problems, including power failures, power sags, power surges, brownouts,
line noise, high voltage spikes, frequency variations, switching transients, and harmonic distortion.
Power outag es can occur when you le ast expect it and power q uality can be erratic
.
These power problems
have the potential to corrupt critical data, destroy unsaved work sessions, and da mage hardware - causing
hours of lost productivity and expensive repairs.
With the Eato n 9SX and 9PX, you can safely eli minate the effects of pow er disturbances and g uard the
integrity of your equipment
.
Providing outstanding performance and reliability, the Eaton 9S X and 9PX’s
unique benefits include:
True online double-conversion technology with high power density, utility frequency independence,
and generator compatibility.
ABM® technology that uses advanced battery management to increase battery service life, opti mize
recharge time, and provide a warning before the end of useful battery life.
Selectable High Efficiency mode of operation.
Standard communication options: one RS-232 communication port, one USB communication port,
and relay output contacts.
Optional connectivity cards with enhanced communication capabilities.
Extended runtime with up to twelve Extended Battery Modules (EBMs) per UPS.
Firmware that is easily upgradable without a service call.
Remote On/Off control through Remote On/Off (ROO) and Remote Power Off (RPO) ports.
Backed by worldwide agency approvals.
Page 7
5-6kVA EU_EN
2
. Presentation
2.1
Standard installations
Tower installation
D
W
H
D
H
W
Weights Dimensions (inch/
mm
)
(lb/
kg
)
D x W x H
106 / 48 27.0 x 17.3 x 5.1 / 685 x 440 x 130
106 / 48 27.0 x 17.3 x 5.1 / 685 x 440 x 130
106 / 48 27.0 x 17.3 x 5.1 / 685 x 440 x 130
106 / 48 27.0 x 17.3 x 5.1 / 685 x 440 x 130
150 / 68 25.4 x 17.3 x 5.1 / 645 x 440 x 130
150 / 68 25.4 x 17.3 x 5.1 / 645 x 440 x 130
5-6kVA EU_EN
Rack installation
Description
9SX 5000
9SX 6000
9PX 5000
9PX 6000
9SX EBM 180V
9PX EBM 180V
Page 8
2
. Presentation
RS232 comm unication port
USB communication port
Dry (relay) contacts communication
port
Connector for ROO (Remote On/Off)
control
Connectors for automatic recognition
of an additional battery module
Connector for Parallel operation
(for 9PX only)
Connector for RPO (Remote Power Off)
control
Slot for optional communic ation card
Connector for additional battery
module
Primary group: 16A outlets for
connection of critical equipment
Group 1: (4) 10A pr ogrammable
outlets for connection of equipment
Group 2: (4) 10A pr ogrammable
outlets for connection of equipment
Input/Output terminal blocks
Connector for HotSwap MBP detection
Connectors for battery modules
(to the UPS or to the other battery
modules)
Connectors for automatic recognition
of battery modules
Page 9
2.2
Rear panels
9SX 5000 / 6000
7
8
4
3
10 11
12
13
14
5
9
1
2
9PX 5000 / 6000
6
7
8
4
3
10 11
12
13
14
5
9
1
2
9SX/9PX EBM 180V (Extended Battery Module)
15
16
5-6kVA EU_EN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Description
Extended battery module
Rack kit 9PX/9SX
Network card
Modbus and network card
Relay card
HotSwap MBP 6000i
Transformer 11000i
Battery Integration System
1.8m cable 180V EBM
3
TFMR11Ki
1
2
Page 10
Input/Output terminal blocks
Normal AC source switch
Input/Output connector to the UPS
Manual Bypass switch
(2) 16A outlets
(3) 10A outlets
Input/Output terminal blocks
50A output circuit breaker
5-6kVA EU_EN
1
2
3
4
5
6
1
2
2
. Presentation
2.3
Accessories
Part number
9SXEBM180RT,
9PXEBM180
9RK
Network-MS
Modbus-MS
Relay-MS
MBP6Ki
TFMR11Ki
BINTSYS
EBMCBL180
MBP6Ki
5
4
6
1
2
2
. Presentation
2.4
Control panel
The UPS has a five-button graphical LCD
.
It provides useful information about the UPS itself, load status,
events, measurements and settings.
Online mode
Fault
indicator (green)
indicator (red)
Battery mode
Bypass mode
indicator (orange)
indicator (orange)
Online mode
50%
100%
2.7kW
30min
3.0kVA
1EBM
Efficiency: 95%
Escape
Up
Down
Enter
On/Off
button
The following table shows the indicator status and description:
Description
The UPS is operating nor mally on Online or on High
Efficiency mode.
On
The UPS is on Battery mode.
On
The UPS is on Bypass mode.
The UPS has an active alarm or fault
.
See trouble-
shooting on page 38 for additional information.
Page 11
Indicator
Green
Orange
Orange
Red
5-6kVA EU_EN
Status
On
On
2
. Presentation
2.5
LCD description
After 5 minutes of ina ctivity, the LCD displays the scree n saver.
The LCD backlight automatically dims after 10 minutes of inactivity
.
Press any button to restore the screen.
Operation status
Online mode
50%
100%
2.7kW 30min
3.0kVA 1EBM
Efficiency: 95%
Efficiency and load group information
The following table describes the status information provided by the UPS
Note:
If other indicator appears, see troubleshooting on page 37 for additional information.
Operation status
Description
Standby mode
Equipment is powered but not
protected by the UPS.
Online mode
The UPS is powering an d protecting
the equipment.
Battery mode
The UPS is powering the equipment
with the battery power
.
Prepare your equipment for
shutdown.
This warning is approximate, and
the actual time to shutdown may
vary significantly
.
Depending on the UPS load
and number o f Extended Battery
Modules (EBMs), the "Battery Low"
warning may occur before the
battery reaches 20% capacity
.
The UPS is powering and
protecting the equipment
Bypass mode
Equipment is powered but not
protected by the UPS.
5-6kVA EU_EN
Load/equipment status
Battery status
1 beep every 10 seconds
End of backup time
1 beep every 3 seconds
High Efficiency mode
Cause
The UPS is Off.
The UPS is operating normally.
A utility failure has occured and
the UPS is on Battery mode.
The UPS is on Battery mode and
the battery is running low.
The UPS is operating on High
Efficiency mode.
An overload or a fault has occurred,
or a command has been received,
and the UPS is in Bypass mode .
Page 1
2
2
. Presentation
2.6
Display functions
Press the Enter (
) button to activate the menu options
.
Use the two middle buttons (
and
) to scroll
through the menu structure
.
Press the Enter (
) button to select an option
.
Press the
button to cancel
or return to the previous menu.
Display information or Menu function
[Load] W VA A pf / [Input/Bypass] V Hz /
[Outpu t/Eff ic ien cy] V Hz % / [Battery] % min V n° /
[DCbus] V / [Average power usage] Wh /
[Cumulat
.
power usage] Wh sinc e date
Transfers the UPS on Bypass mode
Commands the load segments
Starts a manual battery test
Clears active fault
Returns all settings to original values
Clears average power usage measurement
Clears cumul ated power usage measurem ent
Tests dry contact relay outputs
Sets product general param eters
Sets Outpu t parameter s
Sets On/Off conditions
Sets batter y configur ation
Selects faults, alarms and/or events to display
Displays the events stored
Clears events
Displays the faults stored
Clears faults
[Product type/model] / [Part/Serial number] / [UPS/NMC
firmware] / [Com card IPv4], [Com card IPv6], [Com card MAC] /
[Detected accessories]
Links to Eaton registration website
2.7
User settings
The following table displays the option s that can be changed by the user.
Submenu
Available settings
Language
[English] [French] [German] [Spanish]
[Russian] [Portuguese] [Italian]
Menus, stat us, notices and alarms,
UPS fault, Event Log data and
settings are in all supported
Date/ time
Format:
LCD
Modify LCD screen brightness and
contrast to be adap ted to room light
Audible alarm
[Enabled] [Disabled o n battery]
[Enabled]
[Always disabled]
Enable or disable the buzzer
Output voltage
[200V] [208V] [220V] [23 0V] [240V]
[230V]
Frequency converter:
[Enabled] [Disabled]
Frequency settable in frequen cy
converter mode
[Auto start delay]
[Auto shutdown delay]
[Industrial] [Network]
Set UPS behavior regar ding transfer
on Bypass
Sets input voltage hysteresis
from 1 to 10V
[Enabled] [Disabled]
Power the output from Bypass
for high efficiency
Transfer if BP AC NOK
[Enabled] [Disabled]
Allow transfer on Bypass out
of tolerance
Main menu Submenu
Measurements
Control
Go to Bypass
Load segmen ts On/Of
f
Start battery test
Reset fault state
Restore factory set
Reset average power
Reset cumul
.
power
Dry contacts test
Settings
Local settings
In/Out settings
On/Off se ttings
Battery settings
Event log
Event filter
Event list
Reset event list
Fault log
Fault list
Reset fault list
Identification
Register product
if an alarm occur s.
Output frequency
Load segments
Output mode
In/Out settings
Input volt hysteresis
High Efficiency
mode
Bypass transfer
5-6kVA EU_EN
conditions.
Disabled
Group1: [3s] Group2: [6s]
Group1: [Disabled]
Group2: [Disabled]
[Industrial]
[10V]
[Disabled]
[Enabled]
Page 1
3
[International] [US ]
languages.
Default settings
[English]
User selectable when UPS is
powered for the first time.
[International]
Local settings
Available settings
If Bypass transfer is enabled,
Interrupt ti me: [ 10ms] [20ms]
Define break duration when transfer
on Bypass
[10%] … [102%]
Load % when overload al arm occur s
[Unitary UPS] [Hot Standby]
Force slew rate value to 0 .5Hz/s
[Enabled] [Disabled]
Authorize the product to start on
battery powe r.
[Enabled] [Disabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown
sequence will not complete and
restart will occur immediately.
[Enabled] [Disabled]
Authorize the product to restart
automatically when mains recover s
after a complete battery discharge.
[Enabled] [Disabled]
The UPS automatically starts up as
soon as mains power is av ailable
(no need topress the
button).
[Disabled] [100W] … [1000W]
If Enabled, UPS will shutdow n after
5 min
.
of back-up time, if load is less
than threshold.
[Enabled] [Disabled]
If Disabled, LCD and communication
will turn OFF immediatel y after UPS
is OFF
.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled] [Disabled]
If Enabled, shutdown or r estart
commands from software are
authorized.
[Enabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
[0%]
... [100%]
The alarm trigger s when the set
percentage of battery capacity is
reached during back- up time.
[0%]
... [100%]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
[ABM cycling] [Constant charge]
[Auto detection]
[Auto detection]
[Manual EBM set.]
Using standard EBM, UPS
[Manual battery set.]
detects automatically the
[No battery]
number of EBM connected
[Yes] [No]
[Yes]
If set to Yes, the UP S automati cally
prevents battery from deep dischar ge
by adapting end of b ack-up time
voltage threshold
.
Warranty void if set to No.
5-6kVA EU_EN
Submenu
Interrupt time
Overload
prealarm
Redundancy
mode
Cold start
Forced reboot
A
uto restart
A
uto start
Energy saving
Sleep mode
Remote command
Bypass standby
Automatic batte ry
test
Low battery
warning
Restart bat
.
level
Battery settings
Battery charge
mode
External battery
Deep Disch.
protect.
Page 14
Default settings
[10ms]
[102%]
Unitary UPS
[Enabled]
[Enabled]
[Enabled]
[Disabled]
[Disabled]
[Enabled]
[Enabled]
[Enabled]
[Every ABM cyc le]
[20%]
[0%]
[ABM cycling]
2
. Presentation
In/Out settings
On/Off settings
3
.
Installation
3.1
Inspecting the equipment
If any equipment has been damaged during shipment, k eep the shipping cartons and pa cking materials
for the carrier or place of purchase and file a claim for shipping damage
.
If you discover damage after
acceptance, file a claim for concealed d amage.
To file a claim for shipping d amage or concealed da mage:
1) File with the carrier within 15 days of receipt of the equipment;
2) Send a copy of the damage claim within 15 days to your service representative.
Check the battery rech arge date on the shipping carton label
.
If the date has passed and the
batteries were never recharged, do not use the UPS
.
Contact your service representative.
3.2
Unpacking the cabinet
Unpacking the cabinet in a low-temperature environment may cause condensation to occur
in and on the cabinet
.
Do not install the cabinet until the inside and outside of the cabinet are
absolutely dry (hazard of electric shock).
The cabinet is heavy (see page 40)
.
Use caution to unpack and move the cabinet.
Unpack the equipment and remove all the packing materials and shipping carton.
Note:
Do not lift the UPS or EBM fr om the front panel.
Unpacking UPS and Extended Battery Module.
Discard or recycle the pack aging in a responsible manner, or store it for future use.
Place the cabinet in a protected area that has adequate airflow and is free of humidity, flammable gas, and
corrosion.
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
5-6kVA EU_EN Page 15
3
.
Installation
Checking the accessory kit
Verify that the following additional items are included with the UPS:
1
(2) Tower stands
2
Rack kit for 19-inch enclosures (optional)
3
(2) cable glands for Input/Output connection
4
(2) cable locker s for 16A outlets
5
(2) cable locker s for 10A outlets
6
Network-MS communication card
(optional)
7
RS232 communication cable
8
USB communication cable
9
User manual
10
Safety instructions
11
Software CD-ROM
2
If you ordered an optional Extended Battery Module (EBM), verify that the following additional items are inclu ded
with the EBM:
Battery power cable, attached with battery
detection cable
Stabilizer brac ket (4 screws inclu ded)
Rack kit for 19-inch enclosures (optional)
EBM Installation manual.
3
2
Discard the EBM user’s guide if you are installing the EBM with a new UPS at the same time.
Use the UPS user ’ s guide to install bo th the UPS and the EBM.
If you ordered other UPS accessori es, refe r to specific user manu als to check the packing
contents.
5-6kVA EU_EN
3.3
Page 16
9
1
1
0
11
4
5
8
7
3
6
1
2
3
4
4
1
3
.
Installation
3.4
Connecting the EBM(s)
A small amount of arcing may o ccur when connecting an EBM to th e UPS
.
This is normal and
will not harm personnel
.
Insert the EBM cable into the U PS battery connector quickly and fir mly.
1.
Plug the EBM power cable(s) into the battery connector(s)
.
Up to 12 EBMs may be connected
to the UPS.
2
.
Verify that the EBM connections are tig ht and that adequate bend radius an d strain relief exist for
each cable.
3
.
Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
3.5
Connecting other accessories
If you ordered other UPS accessories, refer to specific user manuals to check the connection
to the UPS.
Page 17
5-6kVA EU_EN
3
.
Installation
3.6
Tower installation
If you ordered other UPS accessories, refer to spe cific user manuals to check the towe r installation
with the UPS.
To install the cabinet:
1.
Place the UPS on a flat, stable surface in its final location.
2
.
Always keep 150 mm of free space behind the UPS rear panel.
3
.
If installing additional cabinets, place them next to the UPS in their final location.
Adjustment of the orientation of the LCD panel and of the logo.
Adjustment of the angle of vision of the LCD panel.
5-6kVA EU_EN
p
p
Page 18
3
.
Installation
3.7
Rack installation
If you ordered other UPS accessories, refer to specific user manuals to check the rack installation
with the UPS.
p
Prepare UPS for rack mounting
.
This step requires two people.
The UPS is heavy.
To ease its rack mounting, you can remove the battery pack from the UPS
as explained below.
1.
Remove the center cover of the front panel
2
.
Remove the two scre ws to open the left side of the front panel
3
.
Remove the two screws to pull out the metal protection cover of the battery
A ribbon cable connects the LCD control panel to the UPS
.
Do not pull on the cable or
disconnect it.
Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable
surface
.
Use two hands to support the battery pa ck
.
Set it aside for reinstalling after that the UPS
is rack mounted.
Mount the UPS on rack
Put back the battery pack, screw back the me tal protection cover and the front pa nel,
then clip the center cover.
Page 19
4.
5.
6.
5-6kVA EU_EN
3
.
Installation
p
Rack mounting of UPS, EBM, and accessory modules.
Follow steps 1 to 4 for module mounting on the rails.
1
1
2
3
4
4
The rails and necessary hardware are supplied by EATON.
Page 20
3
5-6kVA EU_EN
3
.
Installation
3.8
Installation requirements
Recommended protective devices and cable cross-sections
1.
Recommended upstream protection
UPS power rating Upstream circuit breaker
5000VA D curve – 32A
6000VA D curve – 32A
2 poles ci rcuit breaker
L1
to UPS Normal AC source
Recommended cable cross-sections
T e rminal wire
Minimum input
Tightening
size rating wire size torque
4-16 mm2 (12-6 AWG) 6 mm2 (10 AWG) 105°C
10 lb in
10 mm2 (8 AWG) 75°C
Copper wire, solid or stranded.
Page 21
N(L2)
G N(L2) L1
2.
5-6kVA EU_EN
Terminal Wire
position
function
L1
Phase
N(L2)
Neutral
(Phase)
Ground
3
.
Installation
3.9
Installation depending on the system earthing arrangement (SEA)
Change in SEA between upstream and downstream or galvanic isolation required
Main low
voltage
switchboard
(MLVS)
Main low
voltage
switchboard
(MLVS)
Page 22
Isolation
transformer
10
Normal AC
o
r
10
Normal AC
8
8
Load
Isolation
transformer
Load
5-6kVA EU_EN
4
. Power cables connection
4.1
Access to terminal blocks
1.
Remove the ter minal blocks cover (one screw)
2
.
Punch the kno ckouts and insert the cables/cond uits inside
High leakage current:
Earth connection essential before co nnecting supply.
4.2
Input/Output connection
This type of connection must be carried out by qualified electrical personnel
Before carrying out any connection, ch eck that the upstream protectio n device (Normal AC
source) is open "O" (Off).
Always connect the ground w ire first
If you ordered a H otSwap MBP, refer to the spe cific user manual to check th e terminal blocks
connection of the UPS with the MBP
.
1
- Insert th e Normal AC cable through the cabl e
gland.
2
- Connect the three cables to the Normal AC
source terminal blocks.
3
- Insert the Output cable through the cable gland.
4
- Connect the three cables to the Outp ut terminal
blocks.
5
- Put back and secure the terminal blocks cover
with the screw.
6
- Tighten the cable glands.
Page 23
5-6kVA EU_EN
5
. Operation
5.1
UPS startup and shutdown
If you ordered a HotSwap MBP, refer to the specific user manual to check the startup sequence
of the UPS with the MBP.
Starting the UPS
Verify that the total equipment ratings do not exceed the UPS capa city to prevent an overload
alarm.
To start the UPS:
1.
If optional EBMs are installed, verify that the EBM are connecte d to the UPS
.
See "Connecting the EBM(s)" on page 17.
2
.
Verify that the UPS terminal bl ocks are connected to AC source.
3
.
Set the upstream circuit breaker (no t provided) to the "I" po sition (On) to switch on the utility power.
The UPS front panel display illuminates and shows EATON logo.
4
.
Verify that the UPS status screen shows
, press
to start.
5
. Press the
button on the UPS front pan el for at least 3 seconds.
The UPS front panel display changes status to "UPS starting
...
".
6
.
Check the UPS front panel display for active alarms or notices
.
Resolve any active alarms before
continuing
.
See "Troubleshooting" on pa ge 37.
If the
indicator is on, do not proceed until all alarms are clear
.
Check the UPS status from the front
panel to view the active alarms
.
Correct the alarms and restart if ne cessary.
7.
Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and
powering the output.
The UPS should be in Online mode.
The internal batteries charge to 90% capacity in less than 3 hours
.
However, Eaton recommends
that the batteries charge for 48 hours after installation or long-term storage.
Starting the UPS on Battery
Before using this feature, the UPS must have been powered by utility power with output enabled
at least once
.
Battery start can be disable d
.
See Coldstart setting in user settings on page 13.
To start the UPS on battery:
1. Press the
button on the UPS front panel until the UPS front panel display illuminates and shows a
status of "UPS starting
...
".
The UPS cycles throu gh Standby mode to Battery mode
.
The
indicator illuminates solid
.
The UPS supplies power to your equipment.
2
.
Check the UPS front panel display for active alarms or notices
.
Resolve any active alarms before
continuing
.
See "Troubleshooting" on pa ge 37.
Check the UPS status from the front pan el to view the active alarms
.
Correct the alarms and restart if
necessary.
UPS shutdown
To shut down the UPS:
1. Press the
button on the UPS front panel
.
The UPS transfers to Standby mode.
2
.
Set the upstream circuit breaker (not provided) to the "O" position (Off) to switch off the utility power.
5-6kVA EU_EN
Page 24
5
. Operation
5.2
Operating modes
The Eaton 9SX an d 9PX front panel indicat es the UP S status through the UPS indicators, see page 13.
Online mode
During Online mode, the
indicator illuminate s solid and the UPS is powered from the utility
.
The UPS monitor s and charges the batteries as n eeded and provides filtered power protection to your
equipment
.
Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack
environment
.
See user settings on page 13.
Battery mode
When the UPS is operating during a power outage, the alarm beeps once every ten seconds and the
indicator illuminates solid
.
The necessary energy is provided by the battery.
When the utility power returns, the UPS transfers to Online mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the audible alarm beeps o nce every 3 seconds
.
This warning is approximate, and the actual time to shutdown may vary significantly.
Shutdown all applications on the connected equipment because automatic UPS shutdown is imminent.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Bypass mode
In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power
.
Battery mode is not available and your equipment is not protected; however, the utility power continues
to be passively filtered by the UPS
.
The
indicator illuminates.
Depending on overloa d conditions, the UPS remains in Bypass mode for at least 5 seconds and will stay
in this mode if three transfers to Bypass occur within 20 minutes.
The UPS transfers to Bypass mode when:
the user activates Bypass mode through th e front panel.
the UPS detects an in ternal failure.
the UPS has a n overtemperature condition.
the UPS has an overload condition listed in table 6 on page 41.
The UPS shuts down after a specified delay for overloa d conditions listed in table 6 on page 41.
The UPS rem ains on to alarm the fault
Standby mode
When the UPS is turned-o ff and remains connected to AC source, the U PS is in Standby mo de.
Depending if Bypass Standby setting is enabled, the output is powered but not protected
.
The battery recharges wh en necessary and the communication ports are powered.
5.3
Transferring the UPS between modes
From Online (or Battery) to Bypass mode.
Press any button to activate the men u options, then select Control
and Go to Bypa ss.
From Bypass to Online (or Battery) mode.
Press any button to activate the men u options, then select Control
and Go back normal.
5-6kVA EU_EN Page 25
5
. Operation
Setting High Efficiency mode
On High Efficiency mode, the UPS operates nor mally on Bypass, transfer s to Online (or Battery) mode in
less than 10 ms when utility fails, and transfers back to Bypass in 5 minutes after utility returns
.
Eaton recom mends to use the HE mo de only to protect I/T equipment.
To set the High Efficiency mode:
1.
Press any button to activate the menu options, then select Se ttings, Output settings, and High
Efficiency mode.
2
.
Select Enabled and Enter to confirm.
Configuring Bypass settings
The following settings are available for configuring Bypass operation.
Bypass transfer out of tolerance
1.
Press any button to activate the menu options, th en select Settings, Output settings, an d Bypass
transfer.
2
.
Select Enable d or Disabled for BP AC NOK, and Enter to confirm
.
If Enabled, the UPS transfers to Bypass even if Bypass AC source is out of tolerance, depending on
output mode
.
If Disabled, the UP S output is shutdown.
Interrupt time
This setting is displayed to define the break duration during transfer to Bypass, only if transfer out of
tolerance is enabled
.
10 ms or 20 ms can be selected.
Configuring battery settings
Automatic battery test
Automatic battery tests are done every w eek in constant charging mode and at each cycle in ABM mode
.
The tests frequency can be modified
.
During the test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds under load.
Battery mode is not displayed and battery low alarm does not activate during a battery test.
The battery te st may be cancelled due to bad conditions, or failed.
Low battery warning
During discharge, the low battery alarm is activated if the battery capacity goes below 20 %
.
This threshold can be modified.
External battery setting
The number of Extended Battery Module is automatically detected, or can be set manually in number of
EBM or in Ah.
Deep discharge protection
This setting is recommended to avoid damaging the battery
.
Warranty is void if deep discharge protection is
disabled.
5-6kVA EU_EN
5.4
5.5
5.6
Page 26
5
. Operation
5.7
Retrieving the Event log
To retrieve the Event log through the display:
1.
Press any button to activate the men u options, then select Event log.
2
.
Scroll through the listed events.
5.8
Retrieving the Fault log
To retrieve the Fault log through the display:
1.
Press any button to activate the men u options, then select Fault log.
2
.
Scroll through the listed faults.
5-6kVA EU_EN Page 27
1. Connect the RS232 16
or USB
17
communication cable to
the serial or USB port on
the computer.
2
.
Connect the other e nd of the
communication cable
16
or
17 to the RS232
1
or USB
2
communication port on
the UPS.
The
UPS
can now communicate
with EATON power management
software.
Relay output contacts
The UPS incorporates four programmable relay outputs; each information is available with a close or open
contact.
5
4
3
2
1
9
8
7
6
n.c
.
n.o
.
n.c
.
n.o
.
n.o
.
n.c
.
n.o
.
n.c.
common
Status active information: (if contact between pin and common is closed)
•
Pin 1: not on Bypass
•
Pin 2: load not protected
•
Pin 3: not low battery
•
Pin 4: not on Battery
•
Pin 5: user common
•
Pin 6: on Bypass
•
Pin 7: low battery
•
Pin 8: load protected
•
Pin 9: on Battery
•
n.o.: contact normally open
•
n.c.: contact normally closed
The relay output contacts must not be connected to any utility connected circuits
.
Reinforced insul ation to the utility is required
.
The relay output contacts have a maximum rating
of 250 Vac/5A.
5-6kVA EU_EN
6
. Communication
6.1
Communication ports
RS232 or USB communication ports
The RS232 a nd USB co mmunication po rts cannot operate simultaneously.
16
17
Page 28
6
. Communication
Remote On/Off
Remote On/Off allows remo te action of
button to switch On/Off the UPS.
Normally open
When contact changes from open to closed, the UPS is switched-on (or stays On).
When contact changes from closed to open, the UPS is switched-off (or stays Off).
On/Off control via
button has priority over the remote control.
Remote Power Off
RPO is used to shutdown the UPS remotely
.
This feature can be u sed for shutting down the load and
the UPS by thermal relay, for instance in the event of room over temperature
.
When RPO is activated,
the UPS shuts down the output and all its power converters immediately
.
The UPS re mains on to alarm the
fault.
The RPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit
.
This circuit must be
separated from any hazardous voltage circuits by reinforced insulation.
The RPO must not be connected to any utility connected circuits
.
Reinforced insulation to the
utility is required
.
The RPO switch must have a minimu m r ating of 27 Vdc and 20 mA and be a
dedicated latching-type switch no t tied in to any other circuit
.
The RPO signal must remain active
for at least 250 ms for proper operation.
To ensure the UPS stops supplying power to the load during any mode of operation, the input
power must be disconne cted from the UPS when the Remote Power Off function is activated.
Leave the RPO connector installed in the RPO port on the UPS even if the RPO function is not
needed.
RPO connections:
Internal power suppl y External power supply
1
3
1
3
1
3
1
3
Normally closed
Normally open
Normally closed
Normally open
Terminal wire size rating is 0.32-4 mm
2
(22-12 AWG).
Suggested wire size is 0.82 mm
2
(18 AWG).
5-6kVA EU_EN Page 2 9
6
. Communication
Remote control connection and test
1
- Check the UPS is shut down and the electrical supply network disconnected.
2
- Remove RPO connector from the UPS by unfitting the screws.
3
- Connect a normally closed volt-free contact between the two pins of connector.
Contact open: shut down of UPS
To return to normal operation, deactivate the external remote shut down
contact and restart the UPS from th e front panel.
1
3
Normally closed
4
- Plug the RPO co nnector into the bac k of the UPS and fix the screws.
5
- Connect and restart the UPS according to the previously described procedures.
6
- Activate the external remote shut down contact to test the function.
Always test the RPO function before applying your critical load to avoid accidental load loss.
Connectivity Cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with
different types of devices
.
The 9SX and 9 PX models have one available communication bay for the
following
connectivity cards:
Network-MS card
- has SNMP and HTTP capabili ties as well as monitoring through a Web
browser interface; connects to Ethernet network
.
In addition, a Environmental Monitoring Probe
can be attached to obtain humidity, temperature, smok e alarm, and security information.
Modbus-MS card
- has connection to Modbus protocol in addition to network management.
Relay-MS card
- has isolated dry contact (Form-C) relay outp uts for UPS status: Utility failure,
Battery low, UPS alarm/OK, or on Bypass.
See on page 21 for the location of the communication bay.
ETHERNET
Setting/Sensor
ETHERNET
Setting/Sensor
100M
10M
UPS data
Reset
100M
10M
UPS data
Reset
Network-MS card
Modbus-MS card
Relay-MS card
5-6kVA EU_EN
Page 30
6
. Communication
Installation of the communication cards
It is not necessary to shutdown
the UPS before installing
a communication card.
4
2
.
Insert the communication
card in the slot.
3
.
Secure the card cover with
the 2 screws
.
Parallel communication port.
This slot is used for Parallel operation (only on 9PX models).
6.2
Eaton Intelligent Power Software suite
Each 9SX and 9PX UPS ships with Eaton Intelligent Power Software suite
.
To begin installing,
see the instructions accompanying the So ftware suite CD.
Eaton Softw are suite provides up-to-date graphics of UPS power and syste m data and power flow
.
It also gives you a complete record of critical power events, and it notifies you of important UPS or power
information
.
If there is a power outage and the 9SX and 9PX UPS battery power becomes low, Eaton Software suite can
automatically shut down your computer system to protect your data before the UPS shutdown occurs.
5-6kVA EU_EN
1.
Remove the slot cove r
secured by screws.
Page 3 1
7. UPS maintenance
7.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and dust free.
If the atmosphere is very dusty, clean the outside of the system with a vacu um cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C (77°F).
If the UPS requires any type of transportation, verify that the UPS is disconnected and turned off.
The batteries are rated for a 3-5 year service life
.
The length of service life varies, depending on
the frequency of usage and ambient temperature
.
Batteries used beyond expected service life
will often have severely reduced runtimes
.
Replace batteries at least every 4 years to keep units
running at peak efficiency.
7.2 Storing the equipment
If you store the equip ment for a long period, recharge the battery every 6 months by connecting the UPS
to utility power
.
The internal ba tteries charge to 90% capacity in less than 3 hour s
.
However, Eaton r ecommends that the batteries charge for 48 hour s after long-term storage
.
Check the battery recharge date on the shipping carton label
.
If the date has passed and the batteries were never recharged, do not use them
.
Contact your servi ce
representative.
7.3 When to replace batteries
When the battery replaceme nt screen is displayed, it is recommended to replace the batteries.
Contact your service representative to order new batteries.
Load not powered
4 years battery
Replacement is
recommended
OK
!
Page 32
Battery replacement
n
5-6kVA EU_EN
7. UPS maintenance
7.4 Replacing batteries
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Batteries can be replaced easily without turning off the UPS or disconnecting the load.
If you prefer to remove input po wer to change the batteries, see "UPS Shutdown" on page 24.
Consider all warnings, cautions, and notes before replacing batteries.
Servicing should be performed by qualified service personnel knowledgeable of batteries and
required precautions
.
Keep unauthorized per sonnel away fr om batteries.
Batteries can present a risk of electrical shock or burn from high short circuit current
.
Observe the following precautions:
1.
Remove watch es, rings, or other metal objects,
2
.
Use tools with insulated handles,
3
.
Do not lay tools or metal parts on top of batteries,
4
.
Wear rubber gloves and boots.
When replacing batteries, re place with th e same type an d number of batteries or battery packs
.
Contact your service representative to order new batteries.
Proper disposal of batteries is required
.
Refer to your local codes for disposal requirements.
Never dispos e of batteries in a fire
.
Batteries may explode when e xposed to flame.
Do not open or mutilate the battery or batteries
.
Released electrolyte is harmful to the skin and
eyes and may be extrem ely toxic.
Determine if the battery is inadvertently grounded
.
If inadvertently grounded, remove source
from ground
. Contact with any part of a grounded battery can result in electrical shock
.
The likelihood of such shock can be reduced if such grounds are removed during installation
and maintenance (applicable to equipment and remote battery supplies not having a grounded
supply circuit).
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors
.
Attempting to alter wiring can cause injury.
Disconnect charging source prior to connecting or disconnecting battery terminals.
Page 33
5-6kVA EU_EN
7. UPS maintenance
Replacing the internal battery
The internal battery is heavy
.
Use caution when handling the heavy batteries.
To replace the battery pack:
1.
Remove the ce nter cover of the front p anel
2
.
Remove the two screw s to open the left side of the front panel
3
.
Remove the two screws to pull out the metal protection cover of the battery
A ribbon cable connects the LCD control panel to the UPS
.
Do not pull on the cable or discon ne ct it.
Pull out the plastic handle of the battery p ack, and slide the pack out slowly on to a flat and stable
surface
.
Use two hands to support the battery pa ck
.
See "Recycling the used e quipment"
on page 36 for proper disposal.
Verify that the replaceme nt batteries have the sa me rating as the batteries being replaced.
Put the new battery pack into the UP S
.
Push the battery pack firmly to ensur e a proper connection.
Screw back the metal protec tion cover and the front panel, then clip the cen ter cover.
Continue to “Testing new batteries” on page 35.
5-6kVA EU_EN
4.
5.
6.
7
.
8.
Page 34
7. UPS maintenance
Replacing the EBM(s)
The EBM is heavy
.
Lifting the cabinet into a rack requires a minimu m of two people.
To replace the EBM(s):
1.
Unplug the EBM power cable and batte ry detection cable from the UPS.
If additional EBM(s) are installed, unplug the EBM po wer cable and battery detection cable
from each EBM.
2
. Replace the EBM(s).
See "Recycling the used equipment" on p age 36 for proper dispo sal.
A small amount of arcing may occur when connecting an EBM to the UPS
.
This is normal and
will not harm personnel
.
Insert the EBM cable into the UPS battery connector quickly and firmly.
3
.
Plug the EBM cable(s) into the battery connector(s)
.
Up to twelve EBMs may be connected to the UPS.
4
.
Verify that the EBM connections are tight and that adequate b end radius and strain relief exist for each
cable.
5
.
Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
Testing ne w batteries
To test new batteries:
1.
Charge the batteries for 48 hours.
2
.
Press any button to activate the menu option s.
3
.
Select Control then Start battery test.
The UPS starts a battery test if the batteries are fully charge d, the UPS is in Normal mode with no
active alarms, and the bypass voltage is acceptable.
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds
.
The front panel displays "Batter y test in progress" and the percentage of the test complete d.
5-6kVA EU_EN Page 35
7. UPS maintenance
7.5 Replacing the UPS equipped with a HotSwap MBP
The HotSwap MBP allows to service or replace the UP S without interrupting the conne cted loads.
Refer to the specific user manual for more information about HotSwap MBP.
To remove the UPS:
1.
Press any button to activate the menu options
.
Select Control then Go to Bypass.
2
.
Check that the UPS is in Bypass mode (Bypass LED should be On).
3
.
Turn the HotSwap MBP switch to the Bypass position: the red LED on the HotSwap MBP goes On,
indicating that the load is now powered directly from utility power.
4
.
Set the Normal AC source switch on the HotSwap MBP to the "O" position and wait for 30s.
5
.
The UPS stops and can now be disconnected.
To reinstall the UPS:
1.
Check that the UPS is correctly connected to the HotSwap MBP.
2
.
Set the Normal AC source switch on the HotSwap MBP to the "I" position.
3
. Press the
button to switch On the U PS.
4
.
Select Control then Go to Bypass.
5
.
Turn the HotSwap MB P switch to the Normal position : the red LED on the HotSwap MBP goes Off,
indicating that the load is now powered by the UPS (Bypass LED should be On).
6
.
Select Control then Go back normal.
7.
Check that the UPS is in Online mode: the load is now protected by the UPS (Online LED should be On).
7.6
Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.
Do not dispose of the battery or batteries in a fire
.
Batteries may explode
.
Proper disposal of
batteries is required
.
Refer to your local codes for disp osal requirements.
Do not open or mutilate the battery or batteries
.
Released electrolyte is harmful to the skin and
eyes
.
It may be toxic.
Do not discard the UPS or the UPS batteries in the trash
.
This product contains sealed, lead acid
batteries and must be disposed of properly
.
For more information, contact your local recycling/
reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash
.
For proper
disposal, contact your local recycling/reus e or hazardous waste cente r.
5-6kVA EU_EN
Page 36
8
. Troubleshooting
The Eaton 9PX and 9S X are designed for durable, automatic operation and also alert you whenever potential
operating problems may occur
.
Usually the alarms shown by the control panel do not mean that the output
power is affected
.
Instead, they are preve ntive alarms intended to alert the user.
Events are silent status information that are recorded into the Event log. Example = "AC freq in
range".
Alarms are recorded into the Event log and displayed on th e LCD status screen with the logo blinking.
Some alarms may be announced by a beep every 3 seconds
.
Example = "Battery low".
Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on
the LCD with a specific message box
.
Example = Out
.
short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.
8.1
Typical alarms and faults
To check the Event log or Fault log :
1.
Press any button on the front panel display to activate the menu options.
2
. Press the
button to select Event log or Fault log.
3
.
Scroll through the listed events or faults.
The following table describes typical conditions.
Conditions
Possible cause
Action
Battery mode
A utility failure has occurred and
The UPS is po wering the equipment
the UP S is in Battery mode
.
with battery power
.
Prepare your
equipment for shutdown.
The UPS is in Battery mode and
This warning is approximate, and the
the battery is running low
.
actual time to shutdown may vary
significantly
.
Depending on the UPS load and
number of Extended Battery Modules
(EBMs), the "Battery Low" warning
may occur b efore the batteries reach
20% capacity.
No battery
The batteries are disconne cted
.
Verify that all batteries are properly
connected
.
If the condition persists, contact your
service representative.
LED is On.
Beep continuous.
Battery fault
The battery te st is failed due to
Verify that all batteries are properly
bad or disconnected batteries,
connected
.
Start a new ba ttery test:
or the battery minimum voltage is
if the condition persists, contact your
reached in ABM cycling mode
.
service representative.
Apply utility pow er for 48 hours to
charge the batteries
.
If the condition
persists, contact your service
representative.
Equipment is powered but not
protected by the UPS.
Check for one of the following alarms:
overtemperature, overload or UPS
failure.
Page 37
LED is On
.
1 beep every 10 sec onds .
Battery low
LED is On.
1 beep every 3 seconds.
LED is On.
Beep continuous.
The UPS does not
The batteries need charging or
provide the expected
service.
backup time.
Bypass mode
An overload or a fault has
occurred, or a command has been
received and the UPS is in Bypass
mode
LED is on.
5-6kVA EU_EN
Remove some of the equipment from
the UPS
.
The UPS continues to operate, but
may switch to Bypass mode or shut
down if the load incr eases.
The alarm resets when the condition
becomes inactive.
If the UPS transferred to Bypass
mode, the UPS will return to normal
operation when the temperature drops
5°C below the warning level.
If the condition persists, shut down
the UPS
.
Clear vents and remove any heat
sources
.
Allow the UPS to cool
.
Ensure the airflow around the UPS is
not restrict ed
. Restart the UPS.
If the condition continues to persist,
contact your service representative.
Check the input connections.
If the UPS Status menu displays the
"Remote Power Off" notice, inactivate
the RPO input.
Connect correctly th e Input/Output
cables.
Led is On.
Beep continuous.
MBP disconnected
The HotSwap MBP i s no more
If the HotSwap MBP is connected
connected to the UPS
.
to the UPS, check that the detection
connector is correctly plugged.
5-6kVA EU_EN
Power requirements e xceed the
UPS capacity (greater than
100% of nominal; see in table 6
on page 41 for specific output
overload ranges).
The UPS internal temperature is
too high or a fan has failed.
A
t the warnin g level, the UPS
generates the alarm b ut remains
in the current operating state.
If the temperature rises an other
10°C, the UPS transfers to Bypass
mode or shuts down if Bypass is
unusable.
The input source is not connected
correctly.
The Remote Power Off (RPO)
switch is active or the RPO
connector is missing.
Input/Output cables are not
connected to the correct terminal
blocks.
Page 38
8
. Troubleshooting
Power overload
LED is On.
Beep continuous.
UPS overtemperature
LED is On.
1 beep every 3 seconds.
The UPS does not start.
Input bad wiring /
Output bad wiring
8
. Troubleshooting
8.2
Silencing the alarm
Press the ESC (Escape) button on the front panel display to silence the alarm
.
Check the alarm condition and
perform t he applica ble action to resol ve the condition
.
If the alarm status cha nges, the alarm beeps again,
overriding the previous alarm silencing.
8.3
Service and support
If you have any questions or problems with the UPS, call your
Local Distributor
or your local service
representative an d ask for a UPS technical represen tative.
Please have the following information ready when you call for service:
Model number
Serial number
Firmware version number
Date of failur e or proble m
Symptom s of failure or problem
Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization (RMA) number
.
This number must
appear on the outsid e of the package and on the Bill Of Lading (if applicable)
.
Use the original pack aging
or request packaging from the Help Desk or distributor
.
Units damaged in shipment as a result of improper
packaging are not cover ed under warranty
.
A replacement or repair unit will be shipped, freight prepaid for all
warrantied units.
For critical applications, immediate replacement may be available
.
Call the
Help Desk
for the
dealer or distributor nearest you.
5-6kVA EU_EN Page 39
9
.
Specifications
Model specifications
Table 1. Power Module model list
Model
Power ratings
9SX5KiRT 5000VA / 4500W
9PX5Ki
5000VA / 4500W
9SX6KiRT 6000VA / 5400W
9PX6Ki
6000VA / 5400W
Table 2. Extended Battery Module model list
Model
Configuration Battery voltage
9SXEBM180RT Rack / Tower 180Vdc
9PXEBM180 Rack / Tower 180Vdc
Table 3. Weights and dimensions
Dimensions D x W x H (mm / in)
685 x 440 x 130 (27.0 x 17.3 x 5.1)
685 x 440 x 130 (27.0 x 17.3 x 5.1)
685 x 440 x 130 (27.0 x 17.3 x 5.1)
685 x 440 x 130 (27.0 x 17.3 x 5.1)
Dimensions D x W x H (mm / in)
645 x 440 x 130 (25.4 x 17.3 x 5.1)
645 x 440 x 13 0 (25.4 x 17.3 x 5.1)
50/60Hz auto-sensing
50Hz : 40-60Hz before transfer to battery
60Hz : 50-70Hz before transfer to battery
-20% / +15% of nominal value (default)
MOV for normal and common mode noise
Default input Selectable input
(Voltage/Current)
Voltage range
230V / 21A 200V, 208 V, 220V,
230V, 240V
230V / 25.2A
Table 5.
Electrical input connections
Model
Input connection Input cable
9SX5KiRT
Hardwired
Not provided
9PX5Ki
9SX6KiRT
9PX6Ki
5-6kVA EU_EN
9.1
Page 40
For power ratings
5000-6000VA
5000-6000VA
Weight (lb / kg)
106 / 48
106 / 48
106 / 48
106 / 48
Weight (lb / kg)
150 / 68
150 / 68
Voltages
at 100% Load
176-276V
Model (UPS)
9SX5KiRT
9PX5Ki
9SX6KiRT
9PX6Ki
Model (EBM)
9SXEBM180RT
9PXEBM180
Table 4.
Electrical input
Nominal frequency
Frequency range
Bypass voltage range
Noise filtering
Model
9SX5KiRT
9PX5Ki
9SX6KiRT
9PX6Ki
9
.
Specifications
Normal mode Battery mode
±1%
±1%
> 98% (High Efficiency mode)
> 91%
> 93%
Sync with line ±5% of nominal line
±0.5% of auto-selected nominal
frequency (outside this range: ±0.5%
frequency
of auto-selected nominal frequency)
200/208/220/230/240V (voltage configurable)
5000/6000VA 4500/5400W
50 or 60Hz, autosensing or configurable as a frequency converter
100-102%
: no alarm
102-110%
: load transfers to Bypass mode after 2 minu tes
110-125%
: load transfers to Bypass mode after 1 minute
125-150%
: load transfers to Bypass mode after 10s
> 150%
: load transfers to Bypass mode after 500ms
100-125%
: no alarm
125-150%
: UPS shuts down after 1 minute
> 150%
: UPS shuts down after 1s
Sinewave
< 2% THDV on linear load
< 5% THDV on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
0.9
3 to 1
Table 7.
Electrical output connections
Output connection Output cable
Hardwired
Not provided
(2) IEC16A
(4) IEC10A group 1
(4) IEC10A group 2
Tab le 8. Environmental and safety
IEC/EN 62040-1: 20 08
IEC/EN 62040-2: 2006 Cat
.
C2
IEC/EN 62040-3: 2011
IEC 60950-1
UL 1778 4th
CSA 22.2
CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
FCC part 15 Class A
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Crit eria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
Page 41
Tab le 6. Electrical output
All models
Voltage regulation
Efficiency
Frequency regulation
Nominal output
Frequency
Output overload
Output overload
(Bypass mode)
Voltage waveform
Harmonic distortion
Transfer time
Power factor
Load crest ratio
Model
9SX5KiRT
9PX5Ki
9SX6KiRT
9PX6Ki
EMC certifications
EMC (Emissions)*
EMC (Immunity)
*
for output cable < 10m.
5-6kVA EU_EN
9
.
Specifications
Agency marki ngs CE / C-Tick / cULus
Operating temperature
0 to 40°C (32 to 104° F) in Online mode, with linear derating for altitude
Note:
thermal protection switches load to Bypass in case of overheating.
Storage temperature
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 14 0°F) without batterie s
Transit temperature -25 to 55°C (-13 to 130°F)
Relative humidity
0 to 95% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level wit h 10% derating per 1000m
Transit altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible noise
< 45 dBA at 1 meter typical
Table 9. Battery
Internal batteries
5000/6000VA: 180Vdc
15 x 12V, 5Ah
63A
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F)
Advanced monitoring for earlier failure detection and warning
External three-pole SBS75G Black connector on UPS for connection to EBM
40cm (1 5.7in)
Table 10. Communication options
(1) available independent communication bay for connectivity cards
Network-MS
Modbus-MS
Relay-MS
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Parallel port (DB15): only for 9PX models
(4) programmable relay outputs (normally open or normally closed)
2 pins jumper (normally open)
3 pins jumper (normally open or normally closed)
5-6kVA EU_EN
EBM
9SXEBM180RT, 9PXEBM180: 180Vdc
2 x 15 x 12V, 5Ah
63A
Rack / Tower
configuration
Fuse
Type
Monitoring
Battery port
EBM battery
cable length
Communication bay
Compatible connectivity
cards
Communication ports
Relay output contacts
Remote On/Off
Remote Power Off
Page 42
10.
Glossary
Bypass AC source
Source supplying the bypass line
.
The equipment can b e transferred to the by-
pass line if an overload occurs on the UPS o utput, for maintenan ce or in
the event of a malfunction.
Frequency converter
Operating mode used to convert the AC-po wer frequen cy betw een the U PS input
and output (50Hz -> 60Hz or 60Hz -> 50Hz).
Low-battery warning
This is a battery-voltage level indicating that battery power is low and that
the user must take action to prevent the imminent break in the supply of power
to the load.
Backup time
Time during which the load can be supplied by the UPS operating on battery
power.
Load
Devices or equipment conn ected to the UPS output.
HE mode
Operating mode by which the load is supplied directly by the AC source if it is
within the tolerances defined by the user
.
This mode reduces the consumption
of electric al pow er
Manual bypass
Rotary switch contr olled by the user, use d to con nect the loads directly to th e
AC source
.
Transfer of the load to the man ual bypass enabl es UPS maintenance
without interrupting the supply of power to the connected loads.
Normal (double
The normal UPS oper ating mode in which the AC source sup plies the UPS which
conversion) mode
in turn supplies the connected loads (after electronic double conversion).
Normal AC source
Normal source of power for the UPS.
Relay contact s
Contacts supplying information to the user in the form of signals.
Uninterruptible Power Supply.
Page 43
UPS
5-6kVA EU_EN
5-6kVA EU_EN
Page 44