DATASHEET - PKZM0-0,63-T
Transformer-protective circuit-breaker, 3p, Ir=0.4-0.63A, screw
connection
Part no. PKZM0-0,63-T
Catalog No. 088910
Alternate Catalog
No.
XTPTP63BC1NL
EL-Nummer
(Norway)
4355152
Delivery program
Product range PKZM0...T transformer-protective circuit-breakers up to 25 A
Basic function Transformer protection
Notes Also suitable for motors with efficiency class IE3.
IE3-ready devices are identified by the logo on their packaging.
Connection technique Screw terminals
Contact sequence
Rated uninterrupted current IuA 0.63
Setting range
Overload releases IrA 0.4 - 0.63
short-circuit release
max. Irm A 12
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Notes For the protection of transformers with a high inrush current.
Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15mm height.
Technical data
General
Standards IEC/EN 60947, VDE 0660
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Storage °C - 40 - 80
Open °C -25 - +55
Enclosed °C - 25 - 40
Mounting position
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 25
Altitude m Max. 2000
10/08/2020 Eaton 088910 ED2020 V73.0 EN 1 / 9
Terminal capacity main cable
Screw terminals
Solid mm21 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule to DIN 46228 mm21 x (1 - 6)
2 x (1 - 6)
Solid or stranded AWG 18 - 10
Stripping length mm 10
Specified tightening torque for terminal screws
Main cable Nm 1.7
Control circuit cables Nm 1
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree III/3
Rated operational voltage UeV AC 690
Rated uninterrupted current = rated operational current Iu = IeA 0.63
Rated frequency f Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 4.71
Lifespan, mechanical Operations x 1060.1
Lifespan, electrical (AC-3 at 400 V)
Lifespan, electrical Operations x 1060.1
Max. operating frequency Ops/h 40
Short-circuit rating
DC
Short-circuit rating kA 60
Motor switching capacity
AC-3 (up to 690V) A 0.63
DC-5 (up to 250V) A 0.63 (3 contacts in series)
Trip blocks
Temperature compensation
to IEC/EN 60947, VDE 0660 °C - 5 … 40
Operating range °C - 25 … 55
Temperature compensation residual error for T > 40 °C ≦ 0.25 %/K
Setting range of overload releases x Iu0.6 - 1
short-circuit release Basic device, fixed: 20 x Iu
Short-circuit release tolerance ± 20%
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation InA 0.63
Heat dissipation per pole, current-dependent Pvid W 1.72
Equipment heat dissipation, current-dependent Pvid W 4.71
Static heat dissipation, non-current-dependent Pvs W 0
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10/08/2020 Eaton 088910 ED2020 V73.0 EN 2 / 9
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system
protection (ecl@ss10.0.1-27-37-04-09 [AJZ716013])
Rated permanent current Iu A 0.63
Rated voltage V 690 - 690
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz kA 150
Overload release current setting A 0.63 - 0.63
Adjustment range short-term delayed short-circuit release A 0 - 0
Adjustment range undelayed short-circuit release A 12 - 12
Integrated earth fault protection No
Type of electrical connection of main circuit Screw connection
Device construction Other
Suitable for DIN rail (top hat rail) mounting Yes
DIN rail (top hat rail) mounting optional Yes
Number of auxiliary contacts as normally closed contact 0
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as change-over contact 0
With switched-off indicator Yes
With under voltage release No
Number of poles 3
Position of connection for main current circuit Other
Type of control element Turn button
Complete device with protection unit Yes
Motor drive integrated No
Motor drive optional No
Degree of protection (IP) IP20
Approvals
Specially designed for North America No
10/08/2020 Eaton 088910 ED2020 V73.0 EN 3 / 9
Characteristics
1: Standard auxiliary contact
2: Trip-indicating auxiliary contact
3: Shunt releases, undervoltage releases
10/08/2020 Eaton 088910 ED2020 V73.0 EN 4 / 9
Tripping characteristics motor-protector circuit breaker PKZM0, PKZM0-...T (not for PKM0-...), PKZM01
10/08/2020 Eaton 088910 ED2020 V73.0 EN 5 / 9
Let-through current
10/08/2020 Eaton 088910 ED2020 V73.0 EN 6 / 9
① 1 half-cycle
Let-through energy
10/08/2020 Eaton 088910 ED2020 V73.0 EN 7 / 9
Dimensions
Motor-protective circuit-breaker with standard auxiliary contact
PKZM0-…(+NHI-E-…-PKZ0)
PKZM0-…-T(+NHI-E-…-PKZ0)
PKM0-…(+NHI-E-…-PKZ0)
Motor-protective circuit-breakers with lockable rotary handles
PKZM0-…+AK-PKZ0
10/08/2020 Eaton 088910 ED2020 V73.0 EN 8 / 9
Motor-protective circuit-breakers with early-make auxiliary contacts
PKZM0-…+VHI-…-PKZ0
Additional product information (links)
IL03407011Z (AWA1210-1925) Motor-protective circuit-breaker
IL03407011Z (AWA1210-1925) Motor-protective
circuit-breaker
https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407011Z2018_04.pdf
'IL03402034Z (AWA121-1945) Motor-protective circuit-breaker, Starter
'IL03402034Z (AWA121-1945) Motor-protective
circuit-breaker, Starter
https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL03402034Z2018_06.pdf
MN03402003Z (AWB1210-1458) PKZM0 motor-protective circuit-breakers, overload monitoring of Ex e motors
MN03402003Z (AWB1210-1458) PKZM0
motor-protective circuit-breakers, overload
monitoring of Ex e motors - Deutsch / English
https://es-assets.eaton.com/DOCUMENTATION/AWB_MANUALS/MN03402003Z_DE_EN.pdf
Schaltvermögen https://de.ecat.eaton.com/flip-cat/?edition=MOTCONT1_DE#page_3/44
Motor starters and "Special Purpose Ratings"
for the North American market
http://www.eaton.eu/ecm/groups/public/@pub/@europe/@electrical/documents/content/pct_3258146.pdf
Busbar Component Adapters for modern
Industrial control panels
http://www.moeller.net/binary/ver_techpapers/ver960en.pdf
10/08/2020 Eaton Industries GmbH
http://www.eaton.eu
© 10/2020 by Eaton Industries GmbH
Eaton 088910 ED2020 V73.0 EN
9 / 9