Thermostatic Fan Controller
Instruction Sheet
I-00104 Rev J
NOTE: Affix enclosed warning stickers to fans that are to be controlled by FC Series thermostatic fan
controller.
Function: Fan control module varies fan speed based upon temperature to increase fan life while
decreasing noise & power consumption.
Status LEDs:
AUTO: Illuminated whenever switch is in the "AUTO" position.
ON: Illuminated whenever fan is operating. The LED will "blink" in proportion to fan speed, from
2 blinks per second to constant.
Mode Settings: Disconnect power by removing plug before removing cover (See warning above)
Mode 1: Fan speed proportional to temperature (factory set)
Mode 2: “Complete On” (On or Off, not proportional). (See Figure A)
This mode is selected by removing pluggable jumper (JP2) on the circuit
board. To access jumper on circuit board 2 screws on face of unit must be
removed.
1) To reduce the risk of electrical shock, disconnect power before servicing.
Switch does not disconnect power, disconnect source before removing cover.
2) To be used indoors in dry location only.
3) IF BACK-UP POWER IS SUPPLIED BY A UPS: A UPS with a ”modified square wave” or
other ”simulated sine wave” output could potentially damage this device and or the fans it controls.
A UPS with a ”pure sine wave” output is required.
AVERTISSEMENT
1) Afin de réduire le risque de chocs éléctriques, veuillez débrancher du réseau avant la maintenance.
Le commutateur ne débranche pas du réseau, veuillez débrancher la source avant d'enlever le
couvercle.
2) Uniquement pour l'utilisation dans des endroits secs.
3) Si l’alimentation de secours est effectuée par une UPS: Une UPS qui n’utilise pas un signal de
sortie Sinus pur peut endommager ou détruire cet appareil ou les ventilateurs branchés. L’utilisation
d’une UPS avec un signal de sortie Sinus pur est obligatoire.
DIE VERWARNUNG
1) Zur Vermeidung des Risikos von Stromschlägen, das Gerät vor Wartungsarbeiten stromlos setzen.
Ausschalten nimmt die Spannung nicht weg. Deshalb vor dem Öffnen des Gehäuses die Netzleitung
trennen.
2) Nur für die Verwendung in trockener Umgebung geeignet.
3) Wenn Notstromversorgung durch eine UPS erfolgt: Eine UPS, die nicht mit einem reinen
Sinus Ausgangssignal arbeitet, kann dieses Gerät oder die angeschlossenen Ventilatoren beschädigen
oder zerstören. Es muss eine UPS mit reinem Sinus Ausgangssignal verwendet werden.
ADVERTENCIA
1) Desconectar antes de hacerle servicio para reducir el riesgo de descarga eléctrica. Apagarlo no
desconecta la electricidad, desconecte la fuente antes de quitar la tapa.
2) Para ser usados solo en lugares secos.
3) Si Hay un respaldo de electricidad suministrado por un sistema ininterrumpido de electricidad:
Un Sistema Ininterrumpido de Electricidad con una “onda cuadrada modificada” u otra
“onda sinusoidal simulada” podría potencialmente dañar este artefacto y/o los ventiladores
o abanicos que este controla. Se requiere un UPS con una salida de “onda sinusoidal pura”.
SPECIFICATIONS:
Protection: 4 AMP Fuse (User Serviceable)
Power Input: 100-240 VAC - 50/60HZ (Nominal)
Power Output: (4) IEC-C13 outlets. Variable output, 60 to 240VAC @ 1.5 AMP Max Combined Load
WARNINGS:
Page 2
Placement of probe: In order to achieve proper temperature sensing, the probe should
be installed near the top of the rack. The probe is provided with a 1.5 meter lead.
WARRANTY
Middle Atlantic Products, Inc. (the "Company") warrants the FC-4-IEC Thermostatic Fan Controller to be free from defects in material or workmanship under normal use and conditions
for a period of (3) three years from date of shipment by the company.
The Company's entire liability to the purchaser, and the purchaser's (or any other party's) sole and exclusive remedy, under this warranty shall be limited, at the Company's option, to
either (a) return of and refund of the price paid for, or (b) repair or replacement at the Company's factory of the products purchased, or any part or parts thereof, which the Company
has determined to be defective after inspection thereof at the Company's factory. This warranty does not cover damage due to acts of God,accident, misuse, abuse or negligence by
parties other than the Company, or any modification or alteration of the products. In addition, this warranty does not cover damage due to improper handling, assembly, installation or
maintenance.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES OF ANY KIND, EITHER EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, IN NO EVENT SHALL THE COMPANY BE LIABLE FOR ANY SPECIAL, INCIDENTAL, INDIRECT, OR
CONSEQUENTIAL DAMAGES WHATSOEVER (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION OR ANY
OTHER PECUNIARY LOSS) ARISING OUT OF THE USE OF THE PRODUCTS PURCHASED, EVEN IF THE COMPANY HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH
DAMAGES. THE COMPANY'S LIABILITY TO THE PURCHASER (OR ANY OTHER PARTY) HEREUNDER, IF ANY, SHALL IN NO EVENT EXCEED THE PURCHASE PRICE OF
THE PRODUCTS PAID TO THE COMPANY.
Corporate Headquarters
Corporate Voice 973-839-1011 - Fax 973-839-1976 / International Voice +1 973-839-8821 - Fax +1 973-839-4982
middleatlantic.com - info@middleatlantic.com
Middle Atlantic Canada
Voice 613-836-2501 - Fax 613-836-2690 / middleatlantic.ca - customerservicecanada@middleatlantic.ca
Factory Distribution
USA: NJ - CA - IL Canada: ON - BC
At Middle Atlantic Products we are always listening. Your comments are welcome.
Middle Atlantic Products is an ISO 9001 and ISO 14001 Registered Company.
FIGURE B
Control Switch
Probe
Raised lacing points for
cable tie mounting.
Fuse Holder
Supplemental
Grounding Point
AUTO
Thermostatic
fan control
OFF
Fan power
is off
ON
Fan on full
speed
Control Switch Position (Figure B)
Remove For
“Complete On” Mode
Temperature
Setting
Jumper
Top of PC Board
Temperature Setting: (See Figure A)
A 3 position pluggable jumper (JP1) on circuit board is provided
to shift the temperature control range per table below. To access
jumper on circuit board 2 screws on face of unit must be removed.
PC Board
Access Screw
PC Board
Access Screw
FIGURE A
SLOW FULL SPEED
Position #1 32oC (90oF) 38oC (100oF)
Position #3 29oC (85oF) 35oC (95oF) (factory set)
Position #5 27oC (80oF) 32oC (90oF)
JP1 Jumper Settings