Table of Contents
Middle Atlantic Products ICLS-COOL-1 User Manual
Displayed below is the user manual for ICLS-COOL-1 by Middle Atlantic Products which is a product in the Rack Accessories category. This manual has pages.
Related Manuals
I-00244 Rev B
ICLS-COOL
Quiet-Cool Series Closet Cooler
Instruction Sheet
THANK YOU
Thank you for purchasing the Quiet Cool Series ICLS-COOL Closet Cooler. Please read
these instructions thoroughly before installing / assembling this product.
PRODUCT FEATURES
- Extends equipment life.
- Quietly removes heat produced by electronic equipment.
- Thermostatically controlled fans run only when necessary.
- Attractive, solid oak vents can be stained or painted to match any décor.
TM
TM
ICLS-COOL1
ICLS-COOL2
(FRONT) (REAR)
(FRONT) (REAR)
Page 2
SPECIFICATIONS
15-3/4" [399mm]
5-3/4"
[146mm]
MODEL POWER
REQUIREMENTS
ICLS-COOL1
FAN
QUANTITY CFM dBA @ 1 METER
ICLS-COOL2
12VDC @ 200mA
12VDC @ 400mA
2
4
50
50
25
28
15-3/4" [399mm]
PANELS
FRONT VENT PANEL
ICLS-COOL1 - TOP PANEL
ICLS-COOL2 - TOP / BOTTOM PANEL
FRONT VENT PANEL
ICLS-COOL1 - BOTTOM PANEL
15-3/4" [399mm]
5-3/4"
[146mm]
15-3/4" [399mm]
ACTIVE REAR PANEL
ICLS-COOL1 - ACTIVE EXHAUST PANEL
ICLS-COOL2 - ACTIVE EXHAUST / INTAKE PANEL
PASSIVE REAR PANEL
ICLS-COOL1 - PASSIVE INTAKE PANEL
4-1/16"
[103mm]
INLINE FAN CONTROL
1-5/16"
[32mm]
9/16"
[15mm]
1-1/2"
[37mm]
4-1/16"
[103mm]
1-11/16"
[42mm]
(FRONT) (SIDE)
1-11/16"
[42mm]
(FRONT) (SIDE)
1-1/4"
[31mm]
(FRONT) (SIDE)
9/16"
[15mm]
(SIDE)
(FRONT)
JUMPER
TOOLS REQUIRED
- DRILL
- 3/8" [9.5mm] DRILL BIT
- JIGSAW
- #2 PHILLIPS HEAD DRIVER
Page 3
PARTS
FRONT VENT PANEL QTY
ICLS-COOL1 1
ICLS-COOL2 2
FRONT VENT PANEL QTY
ICLS-COOL1 1
ICLS-COOL2 0
ACTIVE EXHAUST PANEL (6 ft cord) QTY
ICLS-COOL1 1
ICLS-COOL2 1
ACTIVE INTAKE PANEL (12 ft cord) QTY
ICLS-COOL1 0
ICLS-COOL2 1
PASSIVE INTAKE PANEL QTY
ICLS-COOL1 1
ICLS-COOL2 0
INLINE FAN CONTROL QTY
ICLS-COOL1 1
ICLS-COOL2 1
WIRE TIE QTY
ICLS-COOL1 5
ICLS-COOL2 10
WIRE TIE MOUNT QTY
ICLS-COOL1 5
ICLS-COOL2 10
TEMPLATE QTY
ICLS-COOL1 1
ICLS-COOL2 1
POWER SUPPLY QTY
ICLS-COOL1 1
ICLS-COOL2 1
SCREW (10-32x2") QTY
ICLS-COOL1 4
ICLS-COOL2 8
SCREW (10-32x1-1/2") QTY
ICLS-COOL1 2
ICLS-COOL2 0
WOOD SCREW (6x3/8") QTY
ICLS-COOL1 2
ICLS-COOL2 2
Page 4
INSTALLATION
1) Determine location for mounting your ICLS-COOL.
NOTE: Rear Intake and Exhaust Panels are labeled accordingly on the inside of the panel.
RECOMMENDED INSTALLATION: Install Active Exhaust first at the highest point available
in the door. Install Passive / Active Intake second at lowest point available
in the door. (Template must be cut to trace for ICLS-COOL1 Passive Intake installation)
2) Using center lines as a guide, trace template on upper section of the door. Mark
four outer corner holes on the template ( ).
3) Using a 3/8"[9.5mm] drill bit, drill 4 clearance holes at
pre-marked corner holes to allow access for jigsaw.
4) Carefully cut out traced section of door.
5) Repeat steps 2 - 4 for the Passive or Active Intake.
NOTE: For ICLS-COOL1 Passive Intake, cut the template as it shows.
(DO NOT cut template for ICLS-COOL2 Active Intake)
6) Place wood panels on outside of door. (A second person may be required to hold wood vent panels in place)
ICLS-COOL1
(FRONT VIEW)
ICLS-COOL2
(FRONT VIEW)
PASSIVE INTAKE
VENT PANEL
ACTIVE INTAKE
VENT PANEL
ACTIVE EXHAUST
VENT PANEL
ACTIVE EXHAUST
VENT PANEL
Page 5
7) Attach rear panels using provided screws.
NOTE: For ICLS-COOL2, position Active Exhaust Panel with wire up. Position Active Intake Panel with wire down
- For ICLS-COOL1, use four 10-32x2 screws to attach Active Exhaust Panel. Use two 10-32x1.5 screws
to attach Passive Intake Panel.
- For ICLS-COOL2, use eight 10-32x2 screws to attach Active Intake Panel and Active Exhaust Panel.
SNUG SCREWS EVENLY
ICLS-COOL1
(REAR VIEW)
ICLS-COOL2
(REAR VIEW)
TIP: If using a raised or recessed panel door, cosmetic fillers or trimming may be required.
COSMETIC
FILLER MOLDING / TRIM
ACTIVE EXHAUST
PANEL ACTIVE EXHAUST
PANEL
PASSIVE INTAKE
PANEL
ACTIVE INTAKE
PANEL
SERVICE
LOOP
Page 6
8) With the door in the full open position, run cabling as shown. Use provided Wire Ties and Wire Tie Mounts
as required. Create a service loop at the top of the door to provide cable strain relief.
NOTE: When running cables make sure they do not get pinched or interfere with door closure.
SERVICE
LOOP
ICLS-COOL1 ICLS-COOL2
Page 7
11) With cabling installed, determine mounting location for Inline Fan Control.
NOTE: Inline Fan Control MUST be mounted at the highest available location.
12) Remove all cables from Inline Fan Control.
13) Install Inline Fan Control at predetermined location using provided Wood Screws.
14) Plug Active Fan Panels and Power Supply to Inline Fan Control.
8) Select appropriate wall plug for your region and install in provided Power Supply.
9) Plug Power Supply into power source.
10) Plug Active Fan Panels into input one and / or two on Inline Fan Control. Plug Power Supply into power input.
INLINE FAN CONTROL
POWER SUPPLY
ACTIVE FAN PANEL(S) CABLES
- THE ICLS-COOL IS NOW READY FOR USE -
INLINE FAN CONTROL OPERATION
- Jumper on two center pins (factory setting) fan will turn on at 87 F [30.6 C] and turn off at 85 F [29.4 C].
- Jumper on two left pins, fan will remain off.
- Jumper on two right pins, fan will remain on.
o
ooo
Page 8
WARRANTY
Middle Atlantic Products, Inc. (the "Company") warrants the ICLS-COOL Closet Cooler to be free
from defects in material or workmanship under normal use and conditions for a period of (3) three
years from date of shipment by the Company.
The Company's entire liability to the purchaser, and the purchaser's (or any other party's) sole and
exclusive remedy, under this warranty shall be limited, at the Company's option, to either (a) return
of and refund of the price paid for, or (b) repair or replacement at the Company's factory of the
products purchased, or any part or parts thereof, which the Company has determined to be
defective after inspection thereof at the Company's factory.
This warranty does not cover damage due to acts of God, accident, misuse, abuse or negligence by
parties other than the Company, or any modification or alteration of the products. In addition, this
warranty does not cover damage due to improper handling, assembly, installation or maintenance.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES OF ANY KIND, EITHER EXPRESSED OR
IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE.
TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, IN NO EVENT SHALL THE COMPANY
BE LIABLE FOR ANY SPECIAL, INCIDENTAL, INDIRECT, OR CONSEQUENTIAL DAMAGES
WHATSOEVER (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS PROFITS,
BUSINESS INTERRUPTION OR ANY OTHER PECUNIARY LOSS) ARISING OUT OF THE USE OF THE
PRODUCTS PURCHASED, EVEN IF THE COMPANY HAS BEEN ADVISED OF THE POSSIBILITY OF
SUCH DAMAGES. THE COMPANY'S LIABILITY TO THE PURCHASER (OR ANY OTHER PARTY)
HEREUNDER, IF ANY, SHALL IN NO EVENT EXCEED THE PURCHASE PRICE OF THE PRODUCTS
PAID TO THE COMPANY.
Corporate Headquarters
Corporate Voice 973-839-1011 - Fax 973-839-1976
International Voice +1 973-839-8821 - Fax +1 973-839-4982
middleatlantic.com - info@middleatlantic.com
Middle Atlantic Canada
Voice 613-836-2501 - Fax 613-836-2690
middleatlantic.ca - customerservicecanada@middleatlantic.ca
Factory Distribution
USA: NJ - CA - IL Canada: ON - BC
At Middle Atlantic Products we are always listening. Your comments are welcome.
Middle Atlantic Products is an ISO 9001 and ISO 14001 Registered Company.
30% Recycled Paper