Table of Contents
- Important Safety Information
- Chapter 1: GXT5 Description
- Chapter 2: Installation
- Chapter 3: Operating the UPS
- Chapter 4: Operation and Display Panel
- Chapter 5: Maintenance
- Chapter 6: Troubleshooting
- Chapter 7: Specifications
- Appendix I: Open Source Software Legal Notices
- Appendix II:Technical Support
- 1_GXT5_Description
- _bookmark1
- 1.1__UPS_Features_and_Available_Models
- _bookmark2
- _bookmark3
- 1.2__Front_Panels
- _bookmark4
- 1.3__Rear_Panels
- _bookmark5
- 1.4__Battery_Cabinet
- _bookmark6
- 1.5__Major_Internal_Components_and_Opera
- _bookmark7
- 1.6__UPS_States_and_Operating_Modes
- _bookmark10
- 1.6.1__Normal_Mode
- _bookmark11
- 1.6.2__Bypass_Mode
- _bookmark12
- 1.6.3__Battery_Mode
- _bookmark13
- 1.6.5__ECO_Mode
- _bookmark15
- 2.1__Unpacking_and_Inspection
- _bookmark17
- 2.2__Pre-installation_Preparation
- _bookmark18
- 2.2.1__Installation_Clearances
- _bookmark19
- 2.3__Installing_the_UPS
- _bookmark20
- 2.3.1__Tower_Installation
- _bookmark21
- _bookmark22
- 2.3.2__Rack_Installation
- _bookmark23
- 2.4__Installing_External_Battery_Cabinet
- _bookmark24
- 2.7__Communication_Connections
- _bookmark30
- 2.7.1__Connecting_IntelliSlot_Communicat
- _bookmark31
- 2.7.2__Connecting_to_the_Dry-contact_Por
- _bookmark32
- _bookmark33
- 2.7.3__Connecting_a_Remote_Emergency_Pow
- _bookmark35
- _bookmark36
- 2.7.4__Connecting_a_USB_Cable
- _bookmark37
- 3_Operating_the_UPS
- _bookmark39
- 3.1__Silencing_the_Audible_Alarm
- _bookmark40
- 3.4__Transferring_from_Normal_to_Bypass_
- _bookmark43
- 3.5__Transferring_from_Bypass_to_Normal_
- _bookmark44
- 3.6__Shutting-down_the_UPS_Completely
- _bookmark45
- 3.7__Remote_Emergency_Power-off_(REPO)
- _bookmark46
- 3.8__Auto_and_Manually_Restarting
- _bookmark47
- 4_Operation_and_Display_Panel
- _bookmark48
- 4_Operation_and_Display_Panel
- _bookmark48
- _bookmark49
- _bookmark50
- _bookmark51
- 4.1__LED_Indicators
- _bookmark52
- 4.2__LCD_Menu_and_Screens
- _bookmark53
- 4.2.1__Start-up_and_Flow_Screens
- _bookmark54
- _bookmark55
- 4.2.2__Main_Menu
- _bookmark56
- _bookmark57
- _bookmark58
- _bookmark59
- _bookmark60
- _bookmark61
- _bookmark62
- _bookmark63
- _bookmark65
- 4.3.1__Settings_Prompts
- _bookmark67
- 4.3.2__Changing_the_Password
- _bookmark68
- _bookmark69
- 4.3.3__Selecting_the_Display_Language
- _bookmark70
- 4.3.4__Setting_the_Date_and_Time
- _bookmark71
- _bookmark75
- _bookmark76
- 5.2__Charging_Batteries
- _bookmark77
- 5.3__Checking_UPS_Operation
- _bookmark78
- 6_Troubleshooting
- _bookmark80
- 6.1__Symptoms_that_Require_Troubleshooti
- _bookmark81
- 6.2__Audible_Alarm_(Buzzer)
- _bookmark82
- _bookmark83
- 6.2.1__Faults
- _bookmark84
- 6.3__Troubleshooting_UPS_Issues
- _bookmark86
- _bookmark87
- _bookmark89
Vertiv GXT5 EXTERNAL BP 1.5KVA 2KVA User Manual
Displayed below is the user manual for GXT5 EXTERNAL BP 1.5KVA 2KVA by Vertiv which is a product in the UPS Battery Cabinets category. This manual has pages.
Related Manuals
Liebert®
GXT5™ UPS
230 V Input, 230 V Output
I
Installer/User Guide
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/ for additional assistance.
The information contained in this document is subject to change
without notice and may not be suitable for all applications.
While every precaution has been taken to ensure the accuracy
and completeness of this document, Vertiv assumes no
responsibility and disclaims all liability for damages resulting
from use of this information or for any errors or omissions. Refer
to other local practices or building codes as applicable for the
correct methods, tools, and materials to be used in performing
procedures not specifically described in this document.
The products covered by this instruction manual are
manufactured and/or sold by Vertiv. This document is the
property of Vertiv and contains confidential and proprietary
information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions
regarding usage of trademark names should be directed to the
original manufacturer.
Vertiv | Liebert® GXT5™ | Installer/User Guide i
Table of Contents
Important Safety Information ������������������������������������������������������������������������������������������������������������������������������������������������������ 1
Chapter 1: GXT5 Description �����������������������������������������������������������������������������������������������������������������������������������������������������������������3
1�1� UPS Features and Available Models �������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 3
1�2� Front Panels ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������4
1�3� Rear Panels �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������5
1�4� Removable Power Distribution Box ���������������������������������������������������������������������������������������������������������������������������������������������������������������������� 12
1�5� Internal Battery Packs ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������13
1�6� Battery Cabinet �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������14
1�7� Major Internal Components and Operating Principle ��������������������������������������������������������������������������������������������������������������������������� 14
1�7�1� Maintenance Bypass �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������15
1�8� UPS States and Operating Modes���������������������������������������������������������������������������������������������������������������������������������������������������������������������������16
1�8�1� Normal Mode ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 16
1�8�2� Bypass Mode ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������17
1�8�3� Battery Mode ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������18
1�8�4� ECO Mode �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������19
1�8�5� Maintenance Bypass Mode ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������19
Chapter 2: Installation �����������������������������������������������������������������������������������������������������������������������������������������������������������������������21
2�1� Unpacking and Inspection ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 21
2�2� Pre-installation Preparation ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������ 21
2�2�1� Installation Clearances ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 21
2�3� Installing the UPS ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������22
2�3�1� Tower Installation �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������22
2�3�2� Rack Installation �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������22
Vertiv | Liebert® GXT5™ | Installer/User Guideii
2�4� Installing External Battery Cabinets ����������������������������������������������������������������������������������������������������������������������������������������������������������������������23
2�5� Installing a Power distribution Box �����������������������������������������������������������������������������������������������������������������������������������������������������������������������26
2�6� Hardwired Input/Output Connections ��������������������������������������������������������������������������������������������������������������������������������������������������������������27
2�6�1� Branch Circuit Breaker ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 28
2�6�2� Terminal-block Connections �����������������������������������������������������������������������������������������������������������������������������������������������������������������������30
2�6�3� Connecting to Terminal Blocks on 5-kVA and 6-kVA model ���������������������������������������������������������������������������������������� 31
2�6�4� Connecting to Terminal Blocks on 8-kVA and 10-kVA models ���������������������������������������������������������������������������������� 31
2�6�5� Connecting to Terminal Blocks on 16-kVA and 20-kVA models �������������������������������������������������������������������������������32
2�7� Communication Connections �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������33
2�7�1� Connecting IntelliSlot Communication ���������������������������������������������������������������������������������������������������������������������������������������������� 33
2�7�2� Connecting to the Dry-contact Port ����������������������������������������������������������������������������������������������������������������������������������������������������������������������34
2�7�3� Connecting a Remote Emergency Power-o (REPO) Switch ������������������������������������������������������������������������������������� 36
2�7�4� Connecting a USB Cable ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 37
2�7�5� Connecting CLI Communication Cables ������������������������������������������������������������������������������������������������������������������������������������������� 37
2�8� Installing a Parallel System �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������37
2�8�1� First-time Start-up of a Parallel System ��������������������������������������������������������������������������������������������������������������������������������������������� 39
2�8�2� Commissioning Parallel System ���������������������������������������������������������������������������������������������������������������������������������������������������������������40
2�8�3� Adding a Single UPS to the Parallel System ����������������������������������������������������������������������������������������������������������������������������������41
Chapter 3: Operating the UPS �������������������������������������������������������������������������������������������������������������������������������������������������43
3�1� Silencing the Audible Alarm ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������ 43
3�2� Starting-up the UPS ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������43
3�3� Transferring to Battery Mode �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������44
3�4� Transferring from Normal to Bypass Mode ������������������������������������������������������������������������������������������������������������������������������������������������44
3�5� Transferring from Bypass to Normal Mode ������������������������������������������������������������������������������������������������������������������������������������������������� 44
3�6� Shutting-down the UPS Completely ��������������������������������������������������������������������������������������������������������������������������������������������������������������������45
Vertiv | Liebert® GXT5™ | Installer/User Guide iii
3�7� Remote Emergency Power-o (REPO) �����������������������������������������������������������������������������������������������������������������������������������������������������������45
Chapter 4: Operation and Display Panel ����������������������������������������������������������������������������������������������������������������������� 47
4�1� LED Indicators ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������49
4�2� LCD Menu and Screens ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������49
4�2�1� Start-up and Flow Screens ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 49
4�2�2� Main Menu �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������50
4�2�3� Status Screen ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������51
4�2�4� Settings Submenu ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������54
4�2�5� Control Screen ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 63
4�2�6� Log Screen �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������64
4�2�7� About Screen �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 66
4�3� Editing Display and Operation Settings ������������������������������������������������������������������������������������������������������������������������������������������������������������������������ 69
4�3�1� Settings Prompts �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������69
4�3�2� Changing the Password �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������70
4�3�3� Selecting the Display Language ���������������������������������������������������������������������������������������������������������������������������������������������������������������70
4�3�4� Setting the Date and Time ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������71
Chapter 5: Maintenance �����������������������������������������������������������������������������������������������������������������������������������������������������������������73
5�1� Replacing Batteries ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 73
5�2� Charging Batteries �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 76
5�3� Checking UPS Operation ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 76
5�4� Cleaning the UPS ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������ 76
5�5� Replacing the Power-distribution Box ���������������������������������������������������������������������������������������������������������������������������������������������������������������77
5�6� Firmware Updates ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 79
5�6�1� Updating Firmware with RDU101 Card Connection ��������������������������������������������������������������������������������������������������������������� 79
5�7� Updating DSP Firmware via RDU101 ������������������������������������������������������������������������������������������������������������������������������������������������������������������ 82
Vertiv | Liebert® GXT5™ | Installer/User Guideiv
5�8� Updating Firmware with a CLI Connection ��������������������������������������������������������������������������������������������������������������������������������������������������84
Chapter 6: Troubleshooting �������������������������������������������������������������������������������������������������������������������������������������������������������87
6�1� Symptoms that Require Troubleshooting �������������������������������������������������������������������������������������������������������������������������������������������������������������������87
6�2� Audible Alarm (Buzzer) �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������87
6�2�1� Faults ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 88
6�3� Troubleshooting UPS Issues �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������88
Chapter 7: Specifications ��������������������������������������������������������������������������������������������������������������������������������������������������������������89
7�1� Battery Run Times �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 100
Appendix I: Open Source Software Legal Notices ����������������������������������������������������������������������������������������107
Appendix II: Technical Support ������������������������������������������������������������������������������������������������������������������������������������������ 109
Vertiv | Liebert® GXT5™ | Installer/User Guide 1
Important Safety Information
IMPORTANT! This manual contains important safety instructions that must be followed during the installation
and maintenance of the UPS and batteries. Read this manual thoroughly and the safety and regulatory
information, available at https://www.vertiv.com/ComplianceRegulatoryInfo, before attempting to install,
connect to supply, or operate this UPS.
Important Safety Information2
This page is intentionally left blank�
Vertiv | Liebert® GXT5™ | Installer/User Guide 3
Chapter 1: GXT5 Description
The Liebert® GXT5 is a compact, online uninterruptible power system (UPS) that continuously conditions and
regulates its output voltage� The Liebert® GXT5 supplies microcomputers and other sensitive equipment with
clean sine-wave input power�
Upon generation, AC power is clean and stable� However, during transmission and distribution it is subject to
voltage sags, spikes, and complete failure that may interrupt computer operations, cause data loss, and damage
equipment�
The Liebert® GXT5 protects equipment from these disturbances� The Liebert® GXT5 continuously charges its
batteries from the mains, enabling it to supply power to connected loads, even when the mains fail�
1.1. UPS Features and Available Models
The GXT5 includes the following features� Table 1-1 below, lists the available models and power ratings�
• Enhanced load capacity with an output power factor of 1�
• Optional tower or rack installation to meet varying installation requirements�
• Parallel-connection capability for 10-kVA, 16-kVA, and 20-kVA models achieves up to 2 + 1 parallel redundant
power�
• Adapts to areas with unstable power-mains supply via high-frequency double-conversion topology structure,
with high input-power factor, wide input-voltage range, and output immune to grid interference�
• Programmable terminals on 10-kVA and lower models protect key devices when load is heavy�
• Operation and display panel with model-specific color LCD oers simple configuration and control of the UPS�
• ECO power-supply mode and smart-sleep mode help you save the maximum amount of energy�
Table 1-1 UPS Models and Power Ratings
MODEL NUMBER NOMINAL POWER RATING @ 230 V INPUT
GXT5-750IRT2UXL
750 VA/750 W
GXT5-750IRT2UXLE
GXT5-1000IRT2UXL
1000 VA/1000 W
GXT5-1000IRT2UXLE
GXT5-1500IRT2UXL
1500 VA/1500 W
GXT5-1500IRT2UXLE
GXT5-2000IRT2UXL
2000 VA/2000 W
GXT5-2000IRT2UXLE
GXT5-3000IRT2UXL
3000 VA/3000 W
GXT5-3000IRT2UXLE
GXT5 Description4
Table 1-1 UPS Models and Power Ratings
MODEL NUMBER NOMINAL POWER RATING @ 230 V INPUT
GXT5-5000IRT5UXLN
5 kVA/5 kW
GXT5-5000IRT5UXLE
GXT5-6000IRT5UXLN
6 kVA/6 kW
GXT5-6000IRT5UXLE
GXT5-8000IRT5UXLN
8 kVA/8 kW
GXT5-8000IRT5UXLE
GXT5-10KIRT5UXLN
10 kVA/10 kW
GXT5-10KIRT5UXLE
GXT5-16KIRT9UXLN
16 kVA/16 kW
GXT5-16KIRT9UXLE
GXT5-20KIRT9UXLN
20 kVA/20 kW
GXT5-20KIRT9UXLE
1.2. Front Panels
The various GXT5 models have the same general appearance, with the main dierence being the receptacle
types on the rear panel� Figure 1-1 below, shows the 5-kVA to 10-kVA model in a tower and a rack configuration�
When mounted in a rack, all units are turned 90 degrees�
Figure 1-1 Front View
ITEM DESCRIPTION
1 Operation/Display panel
2 Upper bezel
3 Lower bezel/battery-access door
Vertiv | Liebert® GXT5™ | Installer/User Guide 5
1.3. Rear Panels
The following figures detail the rear-panel features for each GXT5 model�
Figure 1-2 GXT5-750/1000IRT2UXL (XLE) Rear Panel
ITEM DESCRIPTION
1 Liebert® IntelliSlot™ port
2 Ventilation Hole
3 External-battery-cabinet connector
4 Input circuit-breaker reset button, 10-A
5 Non-programmable C13 output receptacles
6 Programmable C13 output receptacles
7 C14 input-power plug and cable
8 Terminal-block communication connectors
9 RS-232 port - RJ-45/RJ-11 connection used for command line interface
10 RS-485 port - RJ-45 connection used for external temperature sensors
11 USB port
GXT5 Description6
Figure 1-3 GXT5-1500IRT2UXL (XLE) Rear Panel
ITEM DESCRIPTION
1 Liebert® IntelliSlot™ port
2 Ventilation Hole
3 External-battery-cabinet connector
4 Input circuit-breaker reset button, 10-A
5 Non-programmable C13 output receptacles
6 Programmable C13 output receptacles
7 C14 input-power plug and cable
8 Terminal- block/Dry-contact communication connectors
9 RS-232 port - RJ-45/RJ-11 connection used for command line interface
10 RS-485 port - RJ-45 connection used for external temperature sensors
11 USB port
Vertiv | Liebert® GXT5™ | Installer/User Guide 7
Figure 1-4 GXT5-2000IRT2UXL (XLE) Rear Panel
ITEM DESCRIPTION
1 Liebert® IntelliSlot™ port
2 Ventilation Hole
3 External-battery-cabinet connector
4 Non-programmable C13 output receptacles
5 Programmable C13 output receptacles
6 C20 input-power plug and cable
7 Input circuit-breaker reset button, 16-A
8 Terminal-block/Dry-contact communication connectors
9 RS-232 port - RJ-45/RJ-11 connection used for command line interface
10 RS-485 port - RJ-45 connection used for external temperature sensors
11 USB port
GXT5 Description8
Figure 1-5 GXT5-3000IRT2UXL (XLE) Rear Panel
ITEM DESCRIPTION
1 Liebert® IntelliSlot™ port
2 Ventilation Hole
3 External-battery-cabinet connector
4 Non-programmable C19 output receptacle
5 Output circuit-breaker reset buttons, 10-A
6 Non-programmable C13 output receptacles
7 Programmable C13 output receptacles
8 C20 Input-power plug and cable
9 Input circuit-breaker reset button, 20-A
10 Terminal-block/Dry-contact communication connectors
11 RS-232 port - RJ-45/RJ-11 connection used for command line interface
12 RS-485 port - RJ-45 connection used for external temperature sensors
13 USB port
Vertiv | Liebert® GXT5™ | Installer/User Guide 9
Figure 1-6 GXT5-5000/6000IRT5UXLN (XLE) Rear Panel
ITEM DESCRIPTION
1 Liebert® IntelliSlot™ port
2 Terminal-block communication connectors
3 USB port
4 RS-485 port - RJ-45 connection used for external temperature sensors
5 RS-232 port - RJ-45/RJ-11 connection used for command line interface
6 REPO connector
7 External-battery-cabinet connector
8 C19 output receptacles (x2)
9 Programmable C13 output receptacles (x2)
10 C19 output overload protector (x2)
11 Programmable output circuit breaker, 10-A (x2)
12 Output circuit breaker - Controls terminal block output and non-programmable output receptacles
13 Maintenance bypass breaker
14 Removable junction box with cable entry for hard-wire I/O
15 Input circuit breaker
GXT5 Description10
Figure 1-7 GXT5-8000/10KIRT5UXLN (XLE) Rear Panel
ITEM DESCRIPTION
1 Liebert® IntelliSlot™ port
2 Terminal- block communication connectors
3 USB port
4 RS-485 port - RJ-45 connection used for external temperature sensors
5 RS-232 port - RJ-45/RJ-11 connection used for command line interface
6 REPO connector
7 DB9 ports - Used for communication when operating in a parallel system, see 2�8� Installing a Parallel System
8 External-battery-cabinet connector
9 C19 output receptacles (x3)
10 Overload protector, 15-A (x3)
11 Programmable C19 output receptacle
12 Programmable C13 output receptacles
13 Programmable output breakers
14 Output circuit breaker - Controls terminal block output and non-programmable output receptacles
15 Maintenance bypass breaker
16 Removable junction box with cable entry for hard-wire I/O
17 Input circuit breaker
Vertiv | Liebert® GXT5™ | Installer/User Guide 11
Figure 1-8 GXT5-16K/20KIRT9UXLN (XLE) Rear Panel
ITEM DESCRIPTION
1 Liebert® IntelliSlot™ port
2 Terminal-block communication connectors
3 RS-485 port - RJ-45 connection used for external temperature sensors
4 USB port
5 RS-232 port - RJ-45/RJ-11 connection used for command line interface
6 REPO connector
7 DB9 ports - Used for communication when operating in a parallel system, see 2�8� Installing a Parallel System
8 Input circuit breaker
9 Bypass circuit breaker
10 Knock-outs/cable-entry for hard-wire I/O
11 Output circuit breaker
12 POD breaker
13 Cover for optional POD-installation location
14 External-battery-cabinet connector
GXT5 Description12
1.4. Removable Power Distribution Box
The 16-kVA and 20-kVA do not ship with an installed power-distribution box (POD)� The optional PODs for the
16-kVA and 20-kVA models are:
• PD2-108 for models ending in "N" only (North America)
• PD2-200
• PD2-201
• PD2-202
• PD2-204 for models ending in "E" only (European Union)
The 5-kVA to 10-kVA models ship with the POD installed� This POD includes the input circuit breaker for the UPS,
and the features for each POD are detailed in the following figures�
Figure 1-9 PD5-CE6HDWRMBS for GXT5-5000/6000IRT5UXLN (XLE)
ITEM DESCRIPTION
1 POD Panel view (on rear of unit)
2 POD inner-surface view
3 Quick connect
Vertiv | Liebert® GXT5™ | Installer/User Guide 13
Figure 1-10 PD5-CE10HDWRMBS for GXT5-8000/10KIRT5UXLN (XLE)
ITEM DESCRIPTION
1 POD Panel view (on rear of unit)
2 POD inner-surface view
3 Quick connect
1.5. Internal Battery Packs
An example of the GXT5 internal battery packs is shown in Figure 1-11 below� They are located behind the access
door on the front of the UPS� 3-kVA and below units have 1 battery pack, 5-kVA and 10-kVA units have 2 battery
packs, and 16-kVA to 20-kVA units have 4 battery packs� The battery pack size varies based on:
Figure 1-11 Internal Battery Pack
ITEM.DESCRIPTION
1 Handle
2 Connector
GXT5 Description14
1.6. Battery Cabinet
Optional battery cabinets are available for the UPS, and include a single battery-connector cable� Up to 10 battery
cabinets may be connected in parallel to the UPS, and up to 6 can be detected using EBC - detection� See Table
7-8 on page 98 and Table 7-9 on page 99 for the cabinet specifications� For approximate battery run times
with additional EBCs, see Battery Run Times on page 100� See Installing External Battery Cabinets on page
23, to connect the cabinets�
Figure 1-12 Battery Cabinet
ITEM.DESCRIPTION
1 Battery connectors
2 Isolation breaker
1.7. Major Internal Components and Operating Principle
Figure 1-13 below, shows the UPS operating principle� Table 1-2 below describes the function of the major
components in the UPS�
NOTE: Figure 1-13 below, is one example of basic operation. The actual I/O connections for the various models
may be divided into dierent types. See Hardwired Input/Output Connections on page 27.
Figure 1-13 Basic Operating Principle Diagram
Vertiv | Liebert® GXT5™ | Installer/User Guide 15
Table 1-2 Major Components
ITEM COMPONENT OPERATION/FUNCTION
1
Transient Voltage Surge
Suppression (TVSS)
and EMI/RFI Filters
Provide surge protection� Filter electromagnetic interference (EMI) and radio frequency interference (RFI)� Minimize
surges or interference present in the utility power and protect devices connected on the same branch as the UPS�
2 Battery Charger Regulates input AC power to continuously float-charge the batteries� Batteries are charged when the UPS is plugged
in, even when not powered-on�
3 Batteries
Valve-regulated, non-spillable, lead-acid batteries�
NOTE: To maintain battery design life, operate the UPS in an ambient temperature of 59 °F to 77 °F (15 °C to 25
°C).
4DC-to-DC
Converter
Raises the DC voltage from the battery to the optimum operating voltage for the inverter� This allows the
inverter to operate continuously at its optimum eiciency and voltage, thus increasing reliability�
5
Rectifier/Power
Factor
Correction
(PFC) Circuit
In normal operation, converts utility AC power to regulated DC power for use by the inverter while ensuring that
the wave shape of the input current used by the UPS is near ideal� Extracting this sine-wave input current ensures
eicient use of utility power and reduces reflected harmonic distortion making cleaner power available to devices
that are not protected by the UPS�
6 Inverter
In normal operation, inverts the DC output of the PFC circuit into precise, regulated sine-wave AC power� When utility
power fails, the inverter receives DC power from the DC-to-DC converter� In either operating mode, the UPS inverter
remains on-line, generating clean, precise, regulated AC-output power�
7 Internal Bypass
In the unlikely event of UPS failure such as overload or over-temperature, automatically transfers the connected load
to bypass�
To manually transfer the connected load from inverter to bypass, see Transferring from Normal to Bypass Mode on
page 44�
8 Outlet group Output receptacles�
1.7.1. Maintenance Bypass
On 5-kVA to 10-kVA models, the UPS includes manual maintenance bypass in a removable section of the rear of
the UPS� Maintenance bypass keeps connected equipment powered with utility power and allows replacement of
the UPS in the event of a UPS malfunction�
NOTE: The bypass power path does not protect the connected equipment from disturbances in the utility
power supply.
GXT5 Description16
1.8. UPS States and Operating Modes
NOTE: See LED Indicators on page 49, for description of the run-indicator and alarm-indicator LEDs
mentioned in this section.
1.8.1. Normal Mode
When utility power is normal, Normal mode employs the rectifier and inverter to provide voltage- and frequency-
stabilized power to the load� The charger charges the battery in normal mode� On the front- panel display, the
run-indicator (green) is ON, the alarm indicator is OFF, and the buzzer is silent� Figure 1-14 shows the diagram of
normal mode�
Figure 1-14 Normal-mode Operation
ITEM DESCRIPTION
1 Mains/Utility input (by-pass input)
2 Rectifier/PFC
3 Inverter
4 Battery charger
5 Battery
6 Bypass static switch
7 UPS output
Vertiv | Liebert® GXT5™ | Installer/User Guide 17
1.8.2. Bypass Mode
Bypass mode supplies power to the load from the bypass source (utility power) if an overload or fault occurs during
normal operation� On the front-panel display, the run indicator (green) is ON, the alarm indicator (yellow) is ON, and
the buzzer beeps once each seconds� The LCD “Flow” screen displays “On Bypass�” Figure 1-15 shows the diagram
of bypass mode�
NOTE: If utility power fails or if the utility voltage goes outside of the permissible range during bypass-mode
operation, the UPS shuts down and no output is supplied to the load.
Figure 1-15 Bypass-mode Operation
ITEM DESCRIPTION
1 Mains/Utility input (by-pass input)
2 Rectifier/PFC
3 Inverter
4 Battery charger
5 Battery
6 Bypass static switch
7 UPS output
GXT5 Description18
1.8.3. Battery Mode
Battery mode supplies battery power to the load if utility power fails or if the utility voltage goes outside of the
permissible range� On the front-panel display, the run indicator (green) is ON, the alarm indicator (yellow) is ON,
and the buzzer beeps once each second� The LCD “Flow” screen displays “On Battery�” Figure 1-16 shows the
diagram of battery mode�
NOTE: The batteries are fully-charged before shipment. However, transportation and storage inevitably
cause some loss of capacity. To ensure adequate back-up time, it is recommended to charge the batteries for
atleast 8 hours before first start-up.
NOTE: If utility power fails and the batteries are charged, you may cold-start the UPS in battery mode and use
battery power to extend system availability for a time.
Figure 1-16 Battery-mode Operation
ITEM DESCRIPTION
1 Mains/Utility input (by-pass input)
2 Rectifier/PFC
3 Inverter
4 Battery charger
5 Battery
6 Bypass static switch
7 UPS output
Vertiv | Liebert® GXT5™ | Installer/User Guide 19
1.8.4. ECO Mode
NOTE: ECO mode is only available on a single-UPS system.
The energy-saving ECO mode reduces power consumption by powering the load via bypass if the bypass voltage
is normal or by powering the load via the inverter when the bypass voltage is abnormal� You can use ECO mode to
power equipment that is not sensitive to power-grid quality to via bypass and reduce power consumption�
NOTE: During ECO mode, if a bypass-failure or abnormal-bypass-voltage notification appears when the output
is not overloaded, the UPS will transfer to Normal Mode. However, if a notification showing bypass failure
or abnormal bypass voltage appears when the output is overloaded, the UPS will shut down the bypass and
therefore the load will shut down.
1.8.5. Maintenance Bypass Mode
Integrated maintenance bypass is available on 5 kVA or larger UPS models� For smaller models, an optional
MicroPOD may be purchased to provide this functionality if needed�
NOTE: 5-kVA to 10-kVA models include a circuit breaker to switch the load to bypass. On 16-kVA to 20-kVA
models, a dry contact may be used to trigger maintenance bypass.
Used when the UPS requires maintenance or repair, Maintenance-bypass mode powers the connected equipment
with utility power while electrically isolating the internal UPS components�
NOTICE
• Risk of power interruption� Can damage the connected equipment�
• If utility power fails or if its quality is out of range while the UPS is in Maintenance Bypass Mode, the UPS
may shut down without notice and shut-o output power to the load�
NOTE: The UPS has no user-serviceable parts. If the UPS malfunctions and requires service, visit http://www.
Vertiv.com/en-us/support/ or contact your local Vertiv representative.
GXT5 Description20
Figure 1-17 Maintenance Bypass-mode Operation
ITEM DESCRIPTION
1 Mains/Utility input (by-pass input)
2 Rectifier/PFC
3 Inverter
4 Battery charger
5 Battery
6 Bypass static switch
7 UPS output
8 Maintenance by-pass
Vertiv | Liebert® GXT5™ | Installer/User Guide 21
Chapter 2: Installation
Do not start the UPS until after the installation is finished, the system is commissioned by an authorized engineer,
and the external-input circuit breakers are closed�
WARNING! Risk of electric shock
Can cause equipment damage, injury and death. Before beginning installation, verify that all external overcurrent
protection devices are open (O), and that they are locked-out and tagged appropriately to prevent activation
during the installation, verify with a voltmeter that power is O and wear appropriate, OSHA-approved
personal protective equipment (PPE) per NFPA 70E. Failure to comply can cause serious injury or death. Before
proceeding with installation, read all instructions. Follow all local codes
.
2.1. Unpacking and Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage� If any shipping damage is found, report it to the carrier and your local
Vertiv representative immediately�
• Check the accessories included against the packing list� If there is any discrepancy, contact your local Vertiv
representative immediately�
CAUTION
The UPS is heavy (see Specifications on page 89, for the weight). Take proper precautions when lifting or
moving the unit.
2.2. Pre-installation Preparation
• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned O� The installation
environment should meet the specifications listed in Specifications on page 89�
• Place the UPS in an area of unrestricted air-flow around the unit, away from water, flammable liquids, gases,
corrosives, and conductive contaminants� Avoid direct sunlight�
NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.
2.2.1. Installation Clearances
Maintain at least 4 in� (100 mm) clearance in the front and rear of the UPS� Do not obstruct the air inlets on the
front panel and rear panel of the UPS� Blocking the air inlets reduces ventilation and heat dissipation, shortening
the service life of the unit�
Installation22
2.3. Installing the UPS
The UPS may be installed as a tower or in a rack, depending on available space and use considerations� Determine
the type of installation and follow the appropriate instructions� See Tower Installation or Rack Installation below�
NOTE: When installing the UPS or making input and output connections, comply with all relevant safety
codes and standards.
2.3.1. Tower Installation
To install the UPS as a tower:
1� Take the support bases out of the accessories box�
Figure 2-1 Support bases
NO. DESCRIPTION
1 Support bases
2 Spacers with connectors
2� If optional, Liebert® external battery cabinets will be connected, take out the spacers shipped with the battery
cabinet�
3� Connect the spacers and the support bases as shown in Figure 2-1 above� Each GXT5 requires 2 support bases,
one in the front and one in the rear�
4� Place the GXT5 and any battery cabinets on the 2 support bases�
2.3.2. Rack Installation
When installed in a rack enclosure, the GXT5 UPS and external battery cabinets (EBC) must be supported by
a shelf or rack-mount rails� Because dierent rack-mount options install in various ways, refer to the installation
instructions provided with the rack-mount kit�
CAUTION
The GXT5 is heavy. The UPS must be installed as near the bottom of a rack as possible. If placed too high, it can
make the rack top-heavy and prone to tipping over. For unit weights, see Specifications on page 89.
Vertiv | Liebert® GXT5™ | Installer/User Guide 23
2.4. Installing External Battery Cabinets
Optional, external battery cabinets (EBC) may be connected in parallel to the UPS to provide additional battery
run time� For approximate battery run times with additional EBCs, see Battery Run Times on page 100� External
battery cabinets are placed on one side of the UPS in a tower configuration or stacked beneath the UPS in a rack
configuration� Up to 10 EBCs may be connected to the UPS, and up to 6 may be detected using EBC-detection�
WARNING! Risk of electric shock
Can cause injury or death. Disconnect all local and remote electric power supplies before working with the UPS.
Ensure that the unit is shut down and power has been disconnected before beginning any maintenance.
CAUTION
The external battery cabinet(s) are heavy, see Specifications on page 89. Take proper precautions when
lifting them.
To install the EBC(s):
1� Inspect the EBC for freight damage� Report damage to the carrier and your local dealer or Vertiv representative�
2� For tower installation:
• An additional set of support-base extensions ships with each EBC�
• See the steps in Tower Installation, to connect the support extenders and install the bases�
- or –
3� For rack installation:
• Rack-mount hardware ships with the EBC�
• Refer to the instructions included with the rack-mount kit to install�
NOTE: Optional slide rails and securing hardware are sold separately. Please contact your Vertiv representative
for options and Vertiv Technical Support for assistance.
4� Verify that the EBC breaker is in the “O” position�
5� Connect the supplied EBC cable(s) to the rear of the cabinet, then to the rear of the UPS, see Figure 2-2�
6� Turn the EBC breaker to the “On” position�
7� Verify the circuit breaker on the EBC is in the “On” position�
The additional back-up run time is now enabled�
NOTE: When removing an EBC, turn o the circuit breaker on the rear of the cabinet before disconnecting the
cable.
NOTE: If shipping or storing the UPS for an extended time, disconnect the EBC(s) to minimize stand-by current
drain on the batteries and help maintain design life.
Installation26
2.5. Installing a Power distribution Box
WARNING! Risk of electric shock
Can cause equipment damage, injury and death. Before beginning installation, verify that all external overcurrent
protection devices are open (O), and that they are locked-out and tagged appropriately to prevent activation
during the installation, verify with a voltmeter that power is O and wear appropriate, OSHA-approved
personal protective equipment (PPE) per NFPA 70E. Failure to comply can cause serious injury or death. Before
proceeding with installation, read all instructions. Follow all local codes.
The 5-kVA to 10-kVA models ship with a removable power-distribution box (POD) installed, see Terminal-block
Connections on page 30, to make the electrical connections to the UPS� For removal, see the appropriate
procedures in Maintenance on page 73�
For 16-kVA to 20-kVA models, the POD ships separately and must be attached to the rear of the UPS� See Removable
Power Distribution Box on page 12, for the POD options compatible with your GXT5 model�
NOTE: Do not operate the UPS with the POD removed. To shut o all power to the POD and to the load, utility
input power must be disconnected.
To attach the POD on 16-kVA to 20-kVA units:
1� On the rear of the unit, unscrew the two fixing screws from the POD-location cover, see Figure 2-4, and
remove the cover�
2� Insert the POD receptacles into the ports, and connect the PP75 terminal�
3� Align the POD with the installation hole, then insert and secure the POD�
Vertiv | Liebert® GXT5™ | Installer/User Guide 27
Figure 2-4 POD-location cover on 16-kVA to 20-kVA models
ITEM DESCRIPTION
1 Fixing Screws
2.6. Hardwired Input/Output Connections
WARNING! Risk of electric shock
Can cause equipment damage, injury and death. Before beginning installation, verify that all external over-
current protection devices are open (O), and that they are locked-out and tagged appropriately to prevent
activation during the installation, verify with a voltmeter that power is O and wear appropriate, OSHA-
approved personal protective equipment (PPE) per NFPA 70E. Failure to comply can cause serious injury or
death. Before proceeding with installation, read all instructions. Follow all local codes.
Table 2-1 lists the four types of I/O connection are available depending on the UPS model� Some models oer more
than one type�
Table 2-1 I/O Connection Types by Model
MODEL LINES IN/OUT CONFIGURATION
5-kVA, 6-kVA 1-in 1-out Common source
8-kVA, 10-kVA 1-in 1-out Common Source or Split bypass
16-kVA, 20-kVA 1-in 1-out or 3-in 1-out Common Source or Split bypass
Installation28
2.6.1. Branch Circuit Breaker
The installer must provide an upstream branch circuit breaker, see Table 2-2 below, for the ratings� The input circuit
breaker on the distribution box and the output circuit breaker on the rear of the power distribution box disconnect
all power between the main cabinet and the distribution box� Figure 2-4 shows a diagram of the circuit breakers�
Observe the following guidelines and specifications when making the hard-wire input and output connections:
• Provide circuit-breaker protection according to local codes� The mains disconnect should be within sight of the
UPS or have an appropriate lock-out�
• We recommend using a Class D circuit breaker�
• Maintain service space around the UPS or use flexible conduit�
• Provide output-distributions panels, circuit-breaker protection, or emergency disconnects according to local
codes�
• Do not install input and output wiring in the same conduit�
Table 2-2 Branch circuit breaker rating
UNIT RATING RECOMMENDED BREAKER RATING
750 VA
10 A1000 VA
1500 VA
2000 VA 16 A
3000 VA 20 A
5 KVA 40 A
6 KVA 50 A
8 KVA 63 A
10 KVA
16 KVA 1-phase: 140 A
3-phase: 50 A
20 KVA 1-phase: 160 A
3-phase: 63 A
Vertiv | Liebert® GXT5™ | Installer/User Guide 29
Figure 2-5 Circuit-breakers diagram
ITEM DESCRIPTION
1 Mains/Utility
2 External branch Circuit Breaker
3 Input
4 Maintenance Bypass Circuit Breaker
5 Output
6 Input Circuit Breaker
7 Output Circuit Breaker
8 UPS-PFC, battery inverter
Installation30
2.6.2. Terminal-block Connections
On 5-kVA and 10-kVA models, the hard-wire connections to the terminal blocks are made through knockouts on
the POD attached to the rear of the unit� See Removable Power Distribution Box on page 12, for the location
of the input/output knockouts on your GXT5 model� Models below 3000 VA use input cords with plugs instead of
terminal block connections�
Table 2-3 below details the electrical-connection specifications�
Table 2-3 Terminal-block electrical specifications
UPS MODEL
RECOMMENDED EXTERNAL
OVER-CURRENT PROTEC-
TION
RECOMMENDED WIRE
SIZE (INCLUDING GROUND
WIRE) (75°C COPPER WIRE)
MAXIMUM WIRE SIZE
ACCEPTED BY TERMINAL
BLOCK
TERMINAL
TIGHTENING
TORQUE
GXT5-5000IRT5UXLN 40 A
8 AWG
6 AWG 20 in�-lb (2�26 Nm)
GXT5-5000IRT5UXLE
GXT5-6000IRT5UXLN 50 A
GXT5-6000IRT5UXLE
GXT5-8000IRT5UXLN
63 A 6 AWG
GXT5-8000IRT5UXLE
GXT5-10KIRT5UXLN
GXT5-10KIRT5UXLE
GXT5-16KIRT9UXLN 1-phase: 140 A
3-phase: 50 A
35 mm2 (1 AWG) 53�5 mm2 (1/0 AWG) 110 in�-lb (12�4 Nm)
GXT5-16KIRT9UXLE
GXT5-20KIRT9UXLN 1-phase: 160 A
3-phase: 63 A
GXT5-20KIRT9UXLE
To make the terminal-block connections:
1� Loosen the screws from the cable-entry/conduit-box cover, and pull the cables through the knockout leaving
some slack for connection�
NOTE: We recommend using the knockouts to install input and output wiring in separate conduit. You must
use a suitable cable gland or risk electric shock.
2� Referring to the appropriate terminal-block connection instructions, connect the cables to the corresponding
input/output terminals and use a torque wrench to turn the screw clockwise until tightened as specified in Table
2-3 above�
• Connecting to Terminal Blocks on 5-kVA and 6-kVA model on next page
• Connecting to Terminal Blocks on 8-kVA and 10-kVA models on next page
• Connecting to Terminal Blocks on 16-kVA and 20-kVA models on page 32
3� Re-install the cable-entry/conduit-box cover, and tighten the screws�
Vertiv | Liebert® GXT5™ | Installer/User Guide 31
2.6.3. Connecting to Terminal Blocks on 5-kVA and 6-kVA model
These models oer a single type of I/O connection, 1-in 1-out common source� Figure 2-6 below, shows the terminal
block� Refer to the details in Terminal-block Connections on page 30, when making the connections�
Figure 2-6 Terminal Block 5 kVA and 6 kVA Models
ITEM DESCRIPTION
1 Output
2 Input
2.6.4. Connecting to Terminal Blocks on 8-kVA and 10-kVA models
These models oer a single type of I/O connection� A single shorting cable ships installed on the on the terminal
block� Refer to the details in Terminal-block Connections on page 30, when making the connections� Figure 2-7
below, shows the shorting cable installed for a split-bypass connection�
Figure 2-7 Terminal Block 8 kVA to 10 kVA Models
ITEM DESCRIPTION
1 Output
2 Bypass
3 Input
4 Shorting cable (installed at factory)
Installation32
2.6.5. Connecting to Terminal Blocks on 16-kVA and 20-kVA models
These models oer a four types of I/O connection� One shorting cable (W01) ships installed on the terminal block�
Two additional shorting cables are included with the accessories to wire the dierent types Figure 2-8 below,
shows the terminal block� Refer to the details in Terminal-block Connections on page 30, when making the
connections�
• Figure 2-8 below, shows the 3-in 1-out common-source connection
• Figure 2-9 below, shows the 1-in 1-out split-bypass connection
• Figure 2-10 below, shows the 1-in 1-out common-source connection
Figure 2-8 3-in 1-out Common-source Connection, 16-kVA and 20-kVA models
ITEM DESCRIPTION
1 Output
2 Bypass
3 Input
4 Shorting cable (W01), installed at factory
Figure 2-9 1-in 1-out Split-bypass Connection, 16-kVA and 20-kVA models
ITEM DESCRIPTION
1 Output
2 Bypass
3 Input
4 Shorting cable (W02), included with accessories
Vertiv | Liebert® GXT5™ | Installer/User Guide 33
Figure 2-10 1-in 1-out Common-source Connection, 16-kVA and 20-kVA models
ITEM DESCRIPTION
1 Output
2 Bypass
3 Input
4 Shorting cable (W03), included with accessories
2.7. Communication Connections
The UPS oers several communication interfaces and ports�
NOTE: We recommend that signal-cable lengths be less than 10 ft (3 m), and are kept away from power
cabling.
2.7.1. Connecting IntelliSlot Communication
The Liebert® IntelliSlot™ RDU101 provides SNMP and/or RS-485 monitoring of the UPS across the network and/
or building management system�
See the appropriate figure for your model in Rear Panels on page 5, for the location of the card port�
To install an IntelliSlot Card:
1� Remove the screws from the slot cover plate and remove the plate�
2� Insert the card into the slot, and secure with the screws that held the cover plate�
To make connections to the card, refer to the Installer/User Guide for the appropriate IntelliSlot card available at
www�vertiv�com�
Installation34
2.7.2. Connecting to the Dry-contact Port
The UPS includes a dry-contact port� See the appropriate figure for your model in Rear Panels on page 5, for
the location of the port� Figure 2-11 below, shows the ports and Table 2-4 describes each port�
The I/O dry contact port ratings are 125 Vac, 0�5 A; 30 Vdc, 1 A�
Figure 2-11 Dry-contact Port and Pin Layout
NOTE: Pins 7 and 8 are shorted before delivery.
NOTE: The emergency power-o (EPO) action of the UPS closes the rectifier, inverter and static bypass,
but it cannot disconnect the UPS mains input inside. To completely disconnect the UPS, disconnect the
upstream input circuit breaker when generating the EPO. For details on REPO connection and operation, see
Connecting a Remote Emergency Power-o (REPO) Switch on page 36.
Vertiv | Liebert® GXT5™ | Installer/User Guide 35
Table 2-4 Dry-contact Connection and Pin-out Descriptions
PORT
NO.
PORT
NAME
PIN
NO. PIN NAME DESCRIPTION
1
Input 1
1 Remote Comms Shutdown 1
User configurable dry-contact input that can be set to trigger the events below� The user
can also select the dry-contact as either NO or NC� (See System Parameter Options on
page 59) When NO, Pins 1 and 2 are shorted to trigger the event� When NC, Pins 1 and
2 are opened to trigger the event�
Options are:
• Disable (default)
• Battery mode shutdown - If the UPS is running on batteries and this input is triggered,
the UPS shuts down
• Any mode shutdown - If this input is triggered, the UPS shuts down regardless of current
operating mode
2 Signal Ground Signal Ground
2
Input 2
3 Remote Comms Shutdown 2
User configurable dry-contact input that can be set to trigger the events below� The user
can also select the dry-contact as either NO or NC� (See System Parameter Options on
page 59) When NO, Pins 3 and 4 are shorted to trigger the event� When NC, Pins 3 and
4 are opened to trigger the event�
Options are:
• Disable (default)
• Battery mode shutdown - If the UPS is running on batteries and this input is triggered,
the UPS shuts down
• Any mode shutdown - If this input is triggered, the UPS shuts down regardless of current
operating mode
4 Signal Ground Signal Ground
3 Battery
Detection
5 EBC Detection Automatically detects number of external- battery cabinets when pins 5 and 6 are
connected to the detection port, see Installing External Battery Cabinets on page 23�
6 EBC Detection Automatically detects number of external- battery cabinets when pins 5 and 6 are
connected to the detection port, see Installing External Battery Cabinets on page 23�
REPO REPO
Input
7+5V REPO power supply, 5-Vdc 100-mA
8 REPO Coil -NC
NC, activated when Pin 7 and Pin 8 is open
NOTE: For details on REPO connection and operation, see Connecting a Remote
Emergency Power-o (REPO) Switch.
5 Output 5 9, 10 Remote Fault Alert 5
User configurable dry-contact output that can be set to alert the user to the faults below�
The user can also select the dry-contact as either NO or NC� (See System Parameter
Options on page 59) When NO, Pins 9 and 10 are shorted when the fault occurs� When
NC, Pins 9 and 10 are opened when the fault occurs�
Options are:
• Low battery (default)
• On battery
• On bypass
• UPS fault
6 Output 6 11, 12 Remote Fault Alert 6
User configurable dry-contact output that can be set to alert the user to the faults below�
The user can also select the dry-contact as either NO or NC� (See System Parameter
Options on page 59) When NO, Pins 11 and 12 are shorted when the fault occurs� When
NC, Pins 11 and 12 are opened when the fault occurs�
Options are:
• Low battery
• On battery
• On bypass
• UPS fault (default)
Installation36
2.7.3. Connecting a Remote Emergency Power-o (REPO) Switch
The UPS includes an EPO connection in the dry-contact port� See the appropriate figure for your model in Rear
Panels on page 5, for the location of the port�
UPS ships with a REPO jumper installed, allowing the UPS to operate as a normally-closed switch system (fail-safe)�
Opening the circuit disables the UPS� To connect a REPO switch that opens the circuit to shut down the rectifier
and inverter and power-o the UPS, use a cable from the remote switch to plug into the REPO-port on the UPS�
In normal conditions, the REPO switch cannot cut o the UPS input power� When the REPO switch trips, the UPS
generates an alarm and immediately cuts-o output power� When the emergency condition is resolved, the UPS
will not return to normal operation until you reset the REPO switch and manually power- on the UPS�
To make the cable for the REPO connection:
Figure 2-12 below, shows the cable required to make the connection� We recommend using 18 AWG to 22 AWG
(0�82 mm2 to 0�33 mm2) copper-core cable�
1� Remove the insulation from the end of two cables�
2� Insert the stripped end into the plug terminals 1 and 2 respectively, then press down the terminals� Make sure
that the cables are secure in the plug to prevent failure because of loose contact�
To connect a UPS to the REPO switch.
CAUTION
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be shielded and run
separately from power cables.
1� Connect one end of the cable to the remote switch, see Figure 2-12 below�
2� Remove the factory-installed jumper from pins 7 and 8 of the dry-contact port on the UPS
3� Connect the plug to pins 7 and 8�
Figure 2-12 Cable/Plug for Connecting REPO switch to UPS REPO port
ITEM DESCRIPTION
1 Terminal 1
2 Terminal 2
3 Plug (connects to REPO port on UPS)
4 REPO switch
Vertiv | Liebert® GXT5™ | Installer/User Guide 37
2.7.4. Connecting a USB Cable
The UPS includes a USB connector� See the appropriate figure for your model in Rear Panels on page 5, for the
location of the port�
The standard, B-type USB port connects the UPS to a network server or other computer system� The USB port
supports HID/CDC protocol� The CDC protocol is reserved for service software� To use the HID protocol for
monitoring, get Power Assist from www�vertiv�com�
2.7.5. Connecting CLI Communication Cables
The UPS supports the Vertiv command-line interface for operation with Vertiv ACS and other third-party
monitoring protocols� The RJ-45 port (labeled “R232”) is used for CLI connection� See the appropriate figure for
your model in Rear Panels on page 5, for the location of the port� The pin-out, described in below table is
consistent with the ACS pin-out�
ITEM DESCRIPTION
1 NC
2 NC
3 TXD (out)
4 GND
5 NC
6 RXD (in)
7 NC
8 NC
2.8. Installing a Parallel System
10-kVA, 16-kVA, and 20-kVA models may be configured in a parallel system� The UPS parallel system provides
support to the following options:
• 3 active systems
• 2 active systems
• 2 active systems plus 1 redundant system
• 1 active system plus 1 redundant system
All electrical requirements, including external-distribution panel and branch circuit breaker, apply to each UPS in
a parallel system, which are then connected in ring configuration for redundancy and additional reliability� System
load information can be accessed via any controller/display in the system�
Installation38
The following are requirements for the parallel-connected system:
• Each UPS must have the same capacity and must be connected to the same mains/utility source�
• If a residual-current detector (RCD) is required, if must be correctly-set and installed before the same
neutral-line input terminal� See safety and regulatory information, available at https://www�vertiv�com/
ComplianceRegulatoryInfo�
• The output of each ups must be connected to the same output bus�
• The parameter configuration for each UPS must be identical�
• Because the parallel system is not fitted with auxiliary-contact detection devices for the output circuit breaker
or the maintenance-bypass circuit breaker of each UPS, You must strictly-follow the procedures for transferring
between operating modes when removing a single UPS from the parallel system before maintenance and when
adding a single UPS after maintenance� Failure to observe the procedures may aect the reliability of the load
power supply�
Figure 2-13 on the next page shows an example of the 10-kVA model connected as a 2 + 1 parallel system connected
in a ring configuration�
NOTE: 8-kVA and lower models do not support paralleling at this time.
NOTE: You must use Vertiv parallel cables for the connection.
NOTE: If a fault occurs during parallel-system operation, shut-o the system and make sure the cables are
connected correctly, see Figure 2-13 on the next page.
CAUTION! Risk of improper disconnection
Can equipment damage. Do not disconnect parallel-system cables while the system is operating.
Vertiv | Liebert® GXT5™ | Installer/User Guide 39
Figure 2-13 Connection of 2 + 1 Parallel System
ITEM DESCRIPTION
1 Upper connector
2 Lower connector
2.8.1. First-time Start-up of a Parallel System
IMPORTANT! Do not start the UPS until after the installation is finished, the system is commissioned by an
authorized engineer, and the external input circuit breakers are closed.
CAUTION
Starting the UPS applies mains/utility power to the output terminals. Make sure that the load power is safe and
ready to accept power. If the load is not ready, isolate the load with the output terminal.
The “Parallel” parameters for each UPS in the system must be set and synchronized at first start-up�
To start and set parameters for the parallel system:
1� Make sure that the output CBs of all units in the parallel system are open (o), then close (turn on) the input CB
on each UPS� Each UPS powers on, a self-check screen displays, and the alarm/run indicators are lit for about 5
seconds�
2� Wait about 30 seconds to allow the rectifier start-up to finish, then at each UPS, set the parallel parameters as
follows:
NOTE: If the “Parallel Comm Fail” Alarm displays, clear it and proceed. Communication should not fail after
the parallel settings are synchronized.
Installation40
• On the display, press Enter to display the Main Menu, then use the arrow buttons to select Settings, and
press Enter�
NOTE: To adjust the settings, you must enter a password. See Editing Display and Operation Settings on
page 69, for details on entering the password and editing the setting parameters.
• Use the arrow buttons to select the Parallel tab, then press Enter to display the parameters list�
• Select and Enter each parameter setting, and then use last item in the list, Sync parallel parameters, to
validate the settings� For a full description of UPS display functions and settings, see Operation and Display
Panel on page 47�
3� After confirming the parallel parameters and each UPS is operating normally, commission the parallel system,
see Commissioning Parallel System below�
2.8.2. Commissioning Parallel System
CAUTION
When powering-on the parallel system, confirm that the external output CB for each UPS is closed and that all
of the inverter output is connected in parallel.
CAUTION
To avoid load power failure, confirm that the system is working normally, then feed power to the load.
To commission the parallel system:
1� Close the external output CB and input CB on each UPS, then wait about 30 seconds to allow the rectifier start-
up to finish�
2� At the first UPS, press the power button for 2 seconds and note that the run indicator (green) is lit, then measure
the output voltage and verify that it is normal�
3� Repeat step 2 for each UPS in the parallel system�
Vertiv | Liebert® GXT5™ | Installer/User Guide 41
2.8.3. Adding a Single UPS to the Parallel System
CAUTION
When adding or replacing a UPS in the parallel system, make sure that all parallel- cabling is correct before
powering on the additional/replacement unit.
NOTE: You may also use this procedure when replacing a faulty UPS in the system. The dierence is noted in
the procedure steps.
1� Connect the power cables and parallel-communication cables, and make sure that they are properly connected,
without any short-circuits�
2� Refer to Commissioning Parallel System on the previous page, to verify operation of the added unit then
completely power-o the added UPS�
3� At any other UPS in the system, update the parallel parameters as follows:
• On the display, press Enter to display the Main Menu, then use the arrow buttons to select Settings, and
press Enter�
• Use the arrow buttons to select the Parallel tab, then press Enter to display the parameters list�
• Set the system count from N to N + 1, and then use last item in the list, Sync parallel parameters�
NOTE: If your are replacing a unit, do not update the system count, just sync the parallel parameters.
4� On the added UPS, close the input and output breakers, wait about 30 seconds to allow the rectifier start-up to
finish, then power-on the inverter�
5� Make sure that there are no alarms and that the UPS and the parallel system are operating normally�
Installation42
This page is intentionally left blank�
Vertiv | Liebert® GXT5™ | Installer/User Guide 43
Chapter 3: Operating the UPS
3.1. Silencing the Audible Alarm
The audible alarm may sound during UPS operation� To silence the alarm, press and hold the ESC button for 2
seconds� The button is located on the front-panel display, see Operation and Display Panel on page 47�
3.2. Starting-up the UPS
IMPORTANT! Do not start the UPS until after the installation is finished, the system is commissioned by an
authorized engineer, and the external input circuit breakers are closed.
CAUTION
Starting the UPS applies mains/utility power to the output terminals. Make sure that the load power is safe and
ready to accept power. If the load is not ready, isolate the load with the output terminal.
The UPS starts in Normal Mode�
To start the UPS:
1� If included on your UPS model, make sure the maintenance-bypass switch is in the open (o) position and
that the guard is secured in place�
2� Ensure that the REPO connector on the rear of the unit has a jumper between pins 7-8 or that it is properly
wired to an Emergency Power- O circuit (normally closed)�
3� Make sure the breaker supplying power to the UPS is closed and close the input breaker on the rear of the
UPS if included on your UPS model or if necessary press the input circuit breaker reset buttons at the rear of
the UPS�
4� If included on your UPS model, close the bypass breaker on the rear of the UPS�
5� Close all output breakers on the rear of the UPS (or in an external panel board, if used)�
6� If external battery cabinets are attached, close the breakers on the rear of each cabinet�
7� Power-on the UPS by pressing and holding the power button on the operation and display panel until the
confirmation dialog appears� Use the Up/ Down arrows to select YES, then press Enter�
8� If this is the first-time start-up of the UPS, the Start-up Guidance wizard opens to set the basic parameters of
the UPS� Follow the prompts�
For detailed description of UPS display functions and settings, see Operation and Display Panel on page 47�
Operating the UPS44
3.3. Transferring to Battery Mode
The UPS operates in Normal mode unless the mains/utility power fails or it is performing a battery self test, then it
automatically transfers to Battery mode for the back-up time available or the mains/utility power is restored� Once
input power is restored, the UPS returns to Normal mode�
NOTE: Battery back-up run times are listed in Battery Run Times on page 100.
3.4. Transferring from Normal to Bypass Mode
Press and hold the power button for 2 seconds�
If the bypass power is within normal operating range, the option to continue to turn-on or turn-o the UPS displays:
a� Use the arrow buttons to select To the Bypass or Turn o UPS, and press Enter�
b� Use the arrow buttons to select No or Yes, then press Enter to confirm�
If the bypass power is outside normal operating range, the option turn-o the UPS displays� Use the arrow buttons
to select No or Yes, then press Enter to confirm�
3.5. Transferring from Bypass to Normal Mode
Press and hold the power button for 2 seconds�
If the UPS is operating normally, without faults, the option to continue to turn-on or turn-o the UPS displays:
a� Use the arrow buttons to select Turn on UPS or Turn o UPS, and press Enter�
b� Use the arrow buttons to select No or Yes, then press Enter to confirm�
NOTE: The UPS automatically switches back to normal mode after an “overheated” or “overloaded” fault is
cleared and normal power is restored.
Vertiv | Liebert® GXT5™ | Installer/User Guide 45
3.6. Shutting-down the UPS Completely
WARNING! Risk of electric shock
Can cause injury or death. Disconnect all local and remote electric power supplies before working with the UPS.
Ensure that the unit is shut down and power has been disconnected before beginning any maintenance.
For 5-kVA to 10-kVA models, transfer to Bypass mode, see Transferring from Normal to Bypass Mode above� Then,
if power to the load is not needed, open the MCB�
For systems with direct power distribution, isolate the UPS from AC power by disconnecting the external input
MCB� If the main and bypass are independently powered, close the two input MCBs�
3.7. Remote Emergency Power-o (REPO)
REPO turns o the UPS in emergency conditions such as fire or flood� When an emergency occurs, the REPO
switch turns o the rectifier and inverter and stops powering the load immediately� The battery stops charging and
discharging�
To manually power-o in an emergency, disconnect the terminal connecting the REPO port on the rear of the UPS�
If mains/utility power is present, the UPS control circuit remains active even though output power is disabled� To
remove all mains/utility power, disconnect the external main-input circuit breaker�
46
This page is intentionally left blank�
Vertiv | Liebert® GXT5™ | Installer/User Guide 47
Chapter 4: Operation and Display Panel
The operation/display panel includes LED indicators, function keys, and an LCD interface to configure and control
UPS operation�
Figure 4-1 UPS Front-panel Display
ITEM DESCRIPTION
1 Run indicator LED, see LED Indicators on page 49�
2 Alarm indicator LED, see LED Indicators on page 49�
3 Power button, see Table 4-1 on the next page�
4 Menu keys, see Table 4-1 on the next page�
5 LCD panel�
Operation and Display Panel48
Table 4-1 Display-panel Button Functions and Descriptions
BUTTON FUNCTION DESCRIPTION
Enter Confirm or enter selection�
Up Move to previous page, increase value, move left�
Down Move to next page, decrease value, move right�
Escape Go back�
Power Power-on the UPS, power-o the UPS, transfer to Bypass Mode�
NOTE: While the UPS is operating, the LCD will dim and display a screen saver if there is no active alarm
or user interaction for two minutes, see Figure 4-2. After 4 minutes of inactivity, the display will blank to
conserve power. If an alarm or fault occurs or if any button is pressed, the UPS-flow screen displays.
Figure 4-2 LCD Screen Saver
Vertiv | Liebert® GXT5™ | Installer/User Guide 49
4.1. LED Indicators
The LEDs on the front-panel display indicate operation and alarm statuses of the UPS�
NOTE: When an alarm is indicated, an alarm message is logged on page 64, describes the alarm messages
you may see. When a fault is indicated, front-panel display list the fault, which are described in Table 6-2 on
page 55.
Table 4-2 LED Functions
INDICATOR LED COLOR LED STATE INDICATES
Run indicator Green
On UPS output on
Blinking Inverter is starting
O UPS has no output
Alarm indicator
Yellow On Alarm occurs
Red On Fault occurs
None O No alarm, no fault
4.2. LCD Menu and Screens
The menu-driven LCD user interface lets you browse the UPS status, view operating parameters, customize
settings, control operation, and view alarm/event history� Use the function keys to navigate through the menu, and
view statuses or select settings in the screens�
4.2.1. Start-up and Flow Screens
At start-up, the UPS executes a system test and displays the Vertiv logo screen for about 10 seconds, shown
in Figure 4-1 on page 47� After the test completes, an overview screen shows status information, the active
(green) power path, and the inactive power path (gray)�
NOTE: Figure 4-3 is an example flow screen and does not reflect the actual values that you may see on your
unit.
Figure 4-3 UPS Flow Screen
Operation and Display Panel50
4.2.2. Main Menu
To access the main menu, press Enter while at the flow screen� Table 4-3 below, describes the menu options, and
Figure 4-4 below, describes the display�
Use the arrow buttons to select the sub-menu options, and press Enter to open the sub menu� Press ESC to return
to the flow�
Table 4-3 Menu Options
SUB MENU DESCRIPTION
Status Voltage, current, frequency, and parameters for UPS components, see Status Screen on the facing page�
Settings Display and system parameter settings, see Settings Submenu on page 54�
Control UPS controls, see Control Screen on page 63�
Log Current alarms and event history, see Log Screen on page 64�
About Product and network information, see About Screen on page 66�
Maintenance Service-only, service-password protected page for use only by Vertiv service representatives�
Figure 4-4 Main Menu
ITEM DESCRIPTION
1 ECO-mode indicator
2 Ambient Temperature
3 Date and Time
Vertiv | Liebert® GXT5™ | Installer/User Guide 51
4.2.3. Status Screen
The status screen displays voltages, currents, frequencies, and parameters on individual tabs for input, bypass,
battery, output, and load status�
To view the UPS status information:
1� At the main menu, select the Status icon, and press Enter�
2� Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the status
information for the selected tab�
Figure 4-5 Status-screen tabs
ITEM DESCRIPTION
1 Screen tabs with Input tab selected
NOTE: Multiple phases are shown in multiple columns. For example, a unit with 3-phase input will display 3
columns of status data.
Input Status Options
L-N voltage (V)
Line-neutral voltage of input power�
L-N current (A)
Line-neutral current of input power�
Frequency (Hz)
Frequency of input of input power�
L-L voltage(V)
Line-line voltage of input power�
Operation and Display Panel52
Power Factor
Power factor of the input power�
Energy (kWh)
Input power�
Input black count
The number times that the input voltage was lost or dropped below 60 VAC (black out)� Resets to 0 when
UPS is powered down�
Input brown count
The number of times that the input voltage was too low to support the load and the UPS was forced to
switch to battery power (brown out)� Resets to 0 when the UPS is powered down�
Bypass Status Options
L-N voltage (V)
Line-neutral voltage of bypass power�
Frequency (Hz)
Frequency of bypass power�
L-L voltage(V)
Line-line voltage of bypass power�
Battery Status Options
Battery status
Current battery state: charging, discharging, or fully-charged�
Battery voltage (V)
Voltage of battery power�
Battery current (A)
Current of battery power�
Backup time (Min)
Amount of back-up time remaining for battery�
Remaining capacity (%)
Percent of capacity remaining for battery�
Discharge count
Number of discharges for the battery module�
Vertiv | Liebert® GXT5™ | Installer/User Guide 53
Total discharge time (Min)
Number of minutes until battery is fully discharged�
Battery running time (Day)
Number of days the batteries have been in operation�
Battery replacement time
Date of last time battery was replaced�
External battery cabinet group No.
Number of external battery cabinets connected�
Battery average temp (°C)
Average temperature of the battery�
Battery highest temp (°C)
Highest temperature battery has reached�
Battery lowest temp (°C)
Lowest temperature battery has reached�
Output Status Options
L-N voltage (V)
Line-neutral voltage of output power�
L-N Current (A)
Line-neutral current of output power�
Frequency (Hz)
Frequency of output power�
L-L voltage(V)
Line-line voltage of output power�
Energy (kWh)
Output power�
Load Status Options
Sout (kVA)
Apparent output power�
Pout (kW)
Active output power�
Operation and Display Panel54
Power Factor
Power factor of output power�
Load percent (%)
Percentage of recent power rated to output power�
4.2.4. Settings Submenu
The settings screen consists of tabs that list UPS settings for configuration and adjusting parameters with tabs for:
• Output
• Battery
• Parallel
• Monitoring
NOTE: Do not change parameter settings or reset to factory defaults when powering-o the UPS.
To modify UPS settings:
1� At the main menu, select the Settings icon, and press Enter�
2� Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the parameter
list for the selected tab�
Output Parameter Options
Voltage selection
Nominal voltage setting� Set the nominal system voltage to match the input voltage of the UPS�
• 200 V
• 208 V
• 220 V
• 230 V
• 240 V
• Autodetect
Startup on bypass
Allows the UPS to start-up in bypass mode�
• Enable = Start the UPS in bypass mode
• Disable = Start the UPS in normal mode�
Vertiv | Liebert® GXT5™ | Installer/User Guide 55
Frequency selection
Selects the frequency of the output�
• Auto, Bypass enabled = Automatically detects frequency of utility/mains power and sets the nominal
frequency to match and bypass mode is enabled (default)�
• Auto, Bypass disabled = Automatically detects frequency of utility/mains power and sets the nominal
frequency to match and bypass mode is disabled�
• Frequency converter 50 Hz = Bypass mode is disabled and the UPS provides 50-Hz output from any
qualified utility/mains power�
• Frequency converter 60 Hz = Bypass mode is disabled and the UPS provides 60-Hz output from any
qualified utility/mains power�
Bypass voltage upper limit
Sets the percentage that the input voltage may be above the selected output voltage setting and remain
in Bypass mode�
• +10% (default)
• +15%
• +20%
Bypass voltage lower limit
Sets the percentage that the input voltage may be below the selected output voltage setting and remain
in Bypass mode�
• -10% (default)
• -15%
• -20%
Run mode
Selects Normal or ECO operation for the UPS�
• Normal = Connected load is always powered through the UPS inverter� ECO mode is disabled�
• ECO mode = ECO mode is enabled� The UPS inverter is bypassed, and the connected load is powered
by utility/mains power within the selected ECO voltage and frequency tolerances�
Operation and Display Panel56
Battery Parameter Options
External battery AH
Sets the amp-hour rating of the external battery� This should only be adjusted when using third-party
external batteries with “External battery cabinet group No�” set to 0� It is calculated automatically when using
Vertiv EBCs using the setting of “External battery cabinet group No�”�
• 0 - 300 Ah (default of 0)
External battery cabinet group No.
Sets the number of attached external battery cabinets or allows the number of EBCs to be detected
automatically with Autodetect� Autodetect is used only for Vertiv EBCs� If more than 6 Vertiv EBCs are
connected, autodetect does not function and this must be set manually� For third-party external batteries, set
this option to 0 and use “External battery AH” setting above�
• 0 - 10
• Autotest (default)
Low battery time
Sounds an alarm when the selected amount of time remaining for the UPS to operate in Battery mode�
• 2 - 30 minutes (default of 2)
Battery periodic test enable
The UPS can periodically self-test the battery�
• Enable
• Disable (default)
Battery periodic test interval
Sets the length of time between periodic test�
• 8, 12, 16, 20, or 26 weeks (default is 8)
Battery periodic test weekday
Sets the day of the week that the battery periodic test is performed�
• Sunday - Saturday (Wednesday is default)
Battery periodic test time
Sets the time that the battery periodic test is performed�
• 00:00 - 23:59 (default is 00:00)
Batt. note duration (month)
Sets the length of time after the batteries are replaced to generate an alarm to remind the user to replace
the batteries�
• Disable (default)
• 1 - 72 months
Vertiv | Liebert® GXT5™ | Installer/User Guide 57
Dischg protect time
Sets the maximum discharge time for the UPS� The default setting is the maximum allowing the battery
to fully discharge� This can be set lower to limit the amount of time the UPS will provide battery protection after
which it will shut down� If the discharge time remaining on the battery is lower than the setting value, it will have
no eect�
• 1 - 4320 minutes (default of 4320)
Equal charge enable
Sets the charge mode of the battery� Equal charge mode is a quick charge mode that can reduce the
amount of time needed to charge the battery� Float charge mode can have a longer battery life�
• Enable = Equal charge mode
• Disable = Float charge mode (default)
Max chg curr
Sets the maximum charge current for the battery� A higher charge current will charge the battery more
quickly but can shorten battery life� A lower value will lengthen the battery charge time and can increase battery
life� The load is always prioritized and the charge current will be decreased internally if necessary to support the
load�
• 0�9 - 13 A (default of 2�2)
NOTE The maximum setting of this value always shows as 13A on the display however it varies based on
internal battery size and the number of EBCs connected. If the value does not save after it is selected, it is
too high for the model.
Temp compensation
When enabled, the UPS will adjust the charging voltage of the batteries based on temperature in order to
preserve battery life� It will increase the voltage if the UPS is operating in a cold environment� It will decrease the
voltage if the UPS is operating in a warm environment�
• Enable
• Disable (default)
Replace battery
Activates newly-installed battery packs after replacement and reset all battery statistics for new battery
packs�
• Provides a confirmation window with Yes/No options to confirm replacement of batteries�
Operation and Display Panel58
Monitor Settings Options
Language
Selects the language of the display, see Selecting the Display Language on page 70�
• English (default)
• French
• Portuguese
• Spanish
• Chinese
• German
• Japanese
• Russian
Date
Selects the current date for the UPS display, YYYY-MM-DD� See Setting the Date and Time on page
71�
Time
Select the current time for the UPS display, HH:MM:SS� See Setting the Date and Time on page 71�
Display orientation
Selects the orientation of the display for use in rack or tower configuration�
• Auto-rotate = Automatically rotates based on the detected orientation of the UPS�
• Horizontal = Screen rotated for rack use�
• Vertical = Screen rotated for tower use�
Audible alarm
If enabled, the UPS will beep when an alarm is generated� If disabled, it will be silent� See Audible Alarm
(Buzzer) on page 69�
• Enable (default)
• Disable
Change settings password
Opens the dialog to change the password used to access and update the UPS parameter settings, see
Changing the Password on page 70�
Vertiv | Liebert® GXT5™ | Installer/User Guide 59
System Parameter Options
Auto restart
Allows the automatic restart of the UPS when input power is restored after a complete shutdown of the UPS
system�
• Enable = The UPS will restart automatically when the input power is restored after a complete shut
down� (default)
• Disable = The UPS will not restart automatically
Auto restart delay
Length of time to elapse before an automatic restart after input power is restored�
• 0 - 999 seconds (default 0)
Guaranteed shutdown
Forces a continued shutdown of the UPS after the Low Battery alarm threshold is reached, even if input
power is restored during this time� This can be used to ensure connected equipment shuts down completely after
receiving a signal to shutdown from an external monitoring device before power is re-applied� This ensures that once
the equipment begins to shut down, it is brought down completely before power is applied again�
• Enable (default)
• Disable
Start with no battery
Allows the UPS to start when the battery has reached the end of discharge (EOD)� This can be used to turn
on the UPS and power the attached load without battery protection when utility power has been restored after the
battery was fully depleted� It works in conjunction with the Auto restart setting above�
• Enable (with Auto restart enable) = The UPS will power the load with no user intervention when
mains power returns after the battery has been fully depleted
• Enable (with Auto restart disabled) = The UPS will start up and allow the user to turn on the output
when power returns after the battery has been fully depleted
• Disable = The UPS cannot start with a fully depleted battery (default)
Remote control
Allows the UPS to be controlled remotely via the CLI or RDU101 card�
• Enable (default)
• Disable
Any mode shutdown auto restart enable
Automatically restart the UPS after an “Any mode shutdown” signal is received� When the UPS is shut down
via dry-contact inputs 1 or 2, it will restart automatically if this option is enabled�
• Enable
• Disable (default)
Operation and Display Panel60
Output contact NO/NC
Selects the states of the dry contact outputs 5 and 6�
• Normally open (default)
• Normally closed
Input contact NO/NC
Selects the states of the dry contact inputs 1 and 2�
• Normally open (default)
• Normally closed
Dry contact 5 (Output)
Selects the output of dry-contact 5�
• Low battery = The contacts switch when the UPS reaches the amount of time left on battery
configurable from “Low battery time”� (default)
• On bypass = The contacts switch when the UPS is running in bypass mode
• On battery = The contacts switch when the UPS is running on battery
• UPS fault = The contacts switch when a UPS fault has occurred
Dry contact 6 (Output)
Selects the output of dry contact 6�
• Low battery = The contacts switch when the UPS reaches the amount of time left on battery
configurable from “Low battery time”�
• On bypass = The contacts switch when the UPS is running in bypass mode
• On battery = The contacts switch when the UPS is running on battery
• UPS fault = The contacts switch when a UPS fault has occurred� (default)
Dry contact 1 (Input)
Selects the action taken by the UPS when the input of dry-contact 1 is triggered�
• Disable (default)
• Battery mode shutdown = If the UPS is running on batteries and this input is triggered, the UPS shuts
down
• Any mode shutdown = If this input is triggered, the UPS shuts down regardless of current operating
mode
Dry contact 2 (Input)
Selects the action taken by the UPS when the input of dry-contact 2 is triggered�
• Disable (default)
• Battery mode shutdown = If the UPS is running on batteries and this input is triggered, the UPS shuts
down
• Any mode shutdown = If this input is triggered, the UPS shuts down regardless of current operating
mode
Vertiv | Liebert® GXT5™ | Installer/User Guide 61
Sleep mode
Allows the UPS to turn o the output on a weekly schedule� For instance, turn on every Monday at 1:00
and o every Friday at 23:00�
• Enable
• Disable (default)
Sleep mode cycle time
Sets the amount of weeks that the UPS will sleep� If set to 52, the UPS will sleep every week permanently
without stopping after 52 weeks� This option is only shown when sleep mode is enabled�
• 0 - 52 (default of 0)
Power on day of week
Sets the day of week to turn on the UPS� This option is only shown when sleep mode is enabled�
• Sunday-Saturday (default Monday)
Power on time
Sets the time of day to power on the UPS on the selected day� This option is only shown when sleep mode
is enabled�
• 00:00 - 23:59 (default 00:00)
Power o day of week
Sets the day of week to turn o the UPS� This option is only shown when sleep mode is enabled�
• Sunday-Saturday (default Friday)
Power o time
Sets the time of day to power o the UPS on the selected day� This option is only shown when sleep mode
is enabled�
• 00:00 - 23:59 (default 00:00)
IT system compatibility
When this option is enabled, the “Input phase reversed” and “Input ground lost” alarms are disabled�
• Enable
• Disable (default)
Outlet Parameter Options
Apply the same settings as outlet 1
Available on outlets 2 through 4, this applies the settings for Outlet1 to this outlet� This lets you apply the
settings for Outlet1 and apply identical settings to any other programmable outlet�
Turn on/o outlet
Turns on or turns o the outlet based on the current state� Provides a confirmation window with Yes/No
options to confirm turning on the outlet�
Operation and Display Panel62
Turn on delay
Length of time before outlet turns on after UPS start-up�
• 0 to 30 minutes (default is 0)
Turn o when UPS overloads
Sets whether or not to turn o the outlet if the UPS is overloaded while on battery power� This can be
used to disable lower priority equipment in the event of an overload while in battery mode�
• Yes
• No (default)
Outlet settings based on discharging time
Threshold of turning o the outlet
Length of time that the outlet is powered after the batteries begin to discharge� Select the checkbox to
enable or disable (default) the option�
• 0 to 30 minutes (default is 5)
Turn on when power returns for
Length of time after the mains input power returns before turning on the outlet� Select the checkbox to
enable (default) or disable the option�
• 0 to 30 minutes (default is 5)
Outlet settings based on backup time
Threshold of turning o the outlet
When the selected amount of time remains on battery mode, the outlet is turned o� Select the checkbox
to enable or disable (default) the option�
• 0 to 30 minutes (default is 5)
Turn on when power returns for
Length of time after the mains input power returns before turning on the outlet� Select the checkbox to
enable or disable (default) the option�
• 0 to 30 minutes (default is 0)
Outlet settings based on capacity
Threshold of turning o the outlet
When the selected percentage of capacity remains in battery mode, the outlet turns o� Select the
checkbox to enable or disable (default) the option�
• 20 to 80% (default is 20%)
Vertiv | Liebert® GXT5™ | Installer/User Guide 63
Turn on when power returns
Length of time after the mains input power returns before turning on the outlet� Select the checkbox to
enable or disable (default) the option�
• 0 to 30 minutes (default is 0)
4.2.5. Control Screen
The Control screen oers UPS-control options�
To adjust the UPS controls:
1� At the main menu, select the Control icon, and press Enter�
2� Use the arrow buttons to move the cursor to the option, then press Enter to select the control�
Figure 4-6 Control Screen
Control Options
Turn on/o/to bypass
Opens the dialog to change operating modes, see Operation and Display Panel on page 47�
Mute/Unmute audible alarm
Silences or un-silences the audible alarm, see Silencing the Audible Alarm on page 43�
Start/Stop battery manual test
Starts the battery self test manually� If the manual self test is already running, stop the self test�
Clear faults
Clears displayed faults after the issue causing the fault is resolved, see Table 6-2 on page 88 , for a
description of the faults�
Reset power statistics
Resets the values tracked to calculate the Eiciency graph, see About Screen on page 66�
Operation and Display Panel64
4.2.6. Log Screen
The Log Screen oers tabs that list the current alarms and the alarm/event history� Table 4-4 below, describes the
alarm messages you may see in the logs�
To view the logs:
1� At the main menu, select the Log icon, and press Enter�
2� Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the log for
the selected tab�
Figure 4-7 Current and History Log Tabs
Table 4-4 Alarm Messages
MESSAGE DESCRIPTION
Aux� power fault UPS internal auxiliary power voltage fault� Contact Vertiv Technical Support�
Battery cabinet
connect abnormal More than 10 external battery cabinets are connected to the UPS� Disconnect excess battery cabinets�
Battery EOD The battery has reached the end of discharge and mains/utility power is unavailable� Restore the mains power� The UPS will
power o if it is not restored�
Battery low pre-
warning
This alarm occurs when the battery approaches the EOD� After the pre-warning, the battery capacity allows two minutes
discharge at full load� The user can set the time with the Low Battery Time setting in Battery settings from 2 min - 30 min, (2 min
by default)� This allows for any loads to be shut down before the system powers o if utility power cannot be restored�
Battery mode The UPS operating in battery mode� The alarm will clear when utility power is restored�
Battery overtemp Battery ambient temperature too high� Ensure that the battery ambient temperature is not higher than setting value 40 ~ 60 °C
(default: 50 °C)�
Battery replacement
timeout
The system time is past the time set for the batteries to be replaced� If you have disabled the “Batt� note duration” or have no
batteries installed, the alarm will not occur�
Battery reversed The battery positive and negative are reversed� Reconnect the battery and check the battery cable connections�
Battery test fail The voltage of the battery was low when the periodic or manual self-test was run� Battery replacement is Recommended�
Battery test started The battery periodic self-test or manual self-test was started� This will display in the log whenever the event occurs�
Battery test stopped The battery periodic self-test or manual self-test has finished� This will display in the log whenever the event occurs�
Battery to utility
transition The UPS has transferred the load to the mains power from the battery� This will display in the log whenever the event occurs�
Battery voltage
abnormal The battery voltage exceeds the normal range� Check if the battery terminal voltage exceeds the normal range�
Vertiv | Liebert® GXT5™ | Installer/User Guide 65
Table 4-4 Alarm Message (continued)
MESSAGE DESCRIPTION
Bypass abnormal
May be caused by bypass voltage and frequency outside of range, bypass power-o and incorrect bypass cables connection�
Check that the bypass voltage and frequency are within the setting range�
Check the bypass cables connection�
Bypass abnormal in
ECO mode
May be caused by ECO bypass voltage and frequency outside of range, ECO bypass power-o, and incorrect ECO bypass cables
connection� Check that the ECO bypass voltage and frequency are within the setting range� Check the bypass cable connection�
Bypass mode The UPS is on bypass� This will clear when the UPS returns to Normal mode�
Bypass over-current The load is drawing more current than the UPS is rated to supply in bypass mode� Reduce the load�
Charger fault The charger output voltage is abnormal, and the charger is o� Contact Vertiv Technical Support�
Communication fail Internal communication is abnormal� Check that the communication cables are connected correctly�
DC bus abnormal The inverter is o due to DC bus voltage out of acceptable range� The load will transfer to bypass if the bypass is available
because the bus voltage is outside of the acceptable range�
DC/DC fault The discharger is faulty, because the bus voltage exceeds the range when the discharger starts� Contact Vertiv Technical
Support�
EOD turn o The inverter is o due to EOD� Check the mains power-o state and recover the mains in time�
Fan fault At least one fan is faulty� Check if the fan is blocked or the cable connection is loose�
Faults cleared The faults have been cleared using Settings > Controls > Clear faults� This will display in the log whenever the event occurs�
Guaranteed shutdown The battery has finished discharging, then system shuts down because Guaranteed Shutdown is enabled (see Guaranteed
shutdown on page 37)� This alarm will clear when the UPS is turned on again�
Input abnormal The rectifier and charger are o due to the mains voltage and frequency exceeding normal range� Check that the rectifier input
phase voltage and frequency exceed the normal range or that the mains has power-o�
Input ground lost Check that the PE line is well connected and that the alarm can be cleared at the display�
Input neutral lost The mains input neutral is not detected� The alarm will clear when the neutral connection has been restored�
Input phase reversed The mains input line and neutral are reversed� Shut o external input breaker and connect the lines correctly�
Insuicient capacity
to start
The UPS is on bypass and is started with a load greater than 105% of the rated capacity� Reduce the load to the rated capacity or
below to start the unit�
Inverter fault The inverter is turned o when the inverter output voltage or current exceed the ranges set� If bypass is available, the UPS will
transfer to bypass mode, otherwise the system will power o� Contact Vertiv Technical Support�
Inverter overload
Inverter load capacity is larger than the rated value, overload delay time is up, inverter shuts down� If bypass is available, the
system will transfer to the bypass mode, otherwise the system will power o� Check the output load� If overloaded, reduce the
load, and the system will transfer to the inverter mode after five seconds with no alarm�
Inverter relay welded The inverter relay is shorted� Contact Vertiv Technical Support�
Load o due to output
short A short has occurred on the output� Check the output cables and for any equipment that may have shorted�
Load o due to
shutdown on battery The system was shut down in battery mode� This will clear when the system is turned back on�
Manual power- on The system was turned on via the display panel� This will display in the log whenever the event occurs�
Manual shutdown The system was shut down via the display panel� This will display in the log whenever the event occurs�
No battery No battery detected� Check the battery and battery cable connection(s)�
On maintenance
bypass The UPS is operating in maintenance bypass mode� This will display in the log whenever the event occurs�
Operating on inverter The UPS output is being powered by the inverter� This will display in the log whenever the event occurs�
Output disabled The system is in standby state, and the dry contact shutdown is enabled� Check if the shutdown dry contact is enabled�
Output o due to
bypass abnormal
The bypass voltage or frequency is outside the acceptable range, and the bypass is in stand-by mode� Check that the input is
normal�
Output o due to
overload & bypass
abnormal
The output is o due to an overload of the UPS output, and the bypass voltage or frequency is outside the acceptable range�
Check that the input is normal�
Operation and Display Panel66
Table 4-4 Alarm Message (continued)
MESSAGE DESCRIPTION
Output o, voltage is
not zero
This occurs when the output is o and the system detects that there is still voltage on the output� Check output equipment for
backfeeds or contact Vertiv Technical Support�
Output pending Remote shutdown has been initiated, and the system will turn o shortly�
Output short A short has occurred on the output� Check the output cables and for any equipment that may have shorted�
Rectifier fault The rectifier is o because the bus voltage is out of the acceptable range when the rectifier starts� Contact Vertiv Technical
Support�
Rectifier overload The output power is larger than the rectifier overload point� Check that the input voltage meets the output load, mains input 176 V
~ 100 V, the load 100% ~ 50% linear derating�
Remote power- on The UPS was powered on remotely� This will display in the log whenever the event occurs�
Remote shut- o The UPS was powered o remotely� This will display in the log whenever the event occurs�
Remote shutdown Any mode shutdown was initiated by the dry contact input� This will display in the log whenever the event occurs�
REPO Shutdown caused by the REPO terminal Normally-Closed contact input opening� This will display in the log whenever the event
occurs�
Restore factory
defaults
On the Maintenance page, “Restore Factory Defaults” has been set while the UPS is in the stand-by state� This will return settings
to their factory settings�
Shutdown due to
over temp
During the UPS operation, the system checks if the heat sink temperature exceeds the setting range�
If an overtemperature occurs, check if:
1� The ambient temperature is too high�
2� Dust is blocking any of the UPS vents�
3� A fan fault has occurred�
System over temp
The internal heat-sink temperature is too high, and the inverter is o� The alarm can only be silenced if the heat-sink temperature
is lower than the alarm setting� The system can automatically start after overtemperature fault is corrected�
If an overtemperature occurs, check if :
1� The ambient temperature is too high�
2� Dust is blocking any of the UPS vents�
3� A fan fault has occurred�
Turn on fail The UPS does not start because there is no mains/utility power or it is outside of the range of the voltage required to supply the
full load� Check the AC input power�
UPS has no output Both Inverter and Bypass are not supplying power due to the UPS output being turned o remotely or via the LCD, or are
unavailable due to no input power or input power out of range� Check that UPS is on and input power is available�
4.2.7. About Screen
The About screen oers tabs that list information about the product�
• Product tab - shows UPS identification information, firmware versions, and information about the
communication card (when the card is installed)�
• Eiciency tab - shows a curve of the eiciency of your UPS model vs the load capacity used�
• Battery age tab - shows the curve of the percent state-of-health (SOH) of the installed battery versus time� The
UPS calculates one value per week and plots it on the graph� The values are based on the battery temperature,
age, and the actual amount of energy discharged from the battery if the battery has been discharged fully�
To view the product, eiciency, and battery-age information:
1� At the main menu, select the About icon, and press Enter�
2� Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the information
for the selected tab�
Vertiv | Liebert® GXT5™ | Installer/User Guide 67
Figure 4-8 About Screen Tabs
ITEM DESCRIPTION
1 About screen tabs with Eiciency tab selected�
Note: The tab shown in the figure is an example of the graph and does not represent the actual capacity values for your UPS model�
Product Information
Product Type
UPS model number�
Serial number
UPS serial number�
Time since startup
Elapsed time since start-up of the UPS�
Boot FW version
Version of MCU boot firmware on the monitor board�
Monitor FW version
Version of MCU application firmware on the monitor board�
DSP FW version
Version of DSP firmware on the UPS power-module�
MAC address
Shows the MAC address of the RDU101 card� This is only shown when the RDU101 card is installed�
IPv4 address
Shows the IPv4 address of the RDU101 card� This is only shown when the RDU101 card is installed�
Subnet mask
Shows the subnet mask of the RDU101 card� This is only shown when the RDU101 card is installed�
Operation and Display Panel68
Gateway address
Shows the gateway address of the RDU101 card� This is only shown when the RDU101 card is installed�
Eiciency Tab
Capacity
This shows the maximum capacity of your UPS model�
Cap. (%)
This shows the percentage of the maximum capacity your UPS is currently using�
E. (%)
This shows the eiciency the UPS is currently operating at based on the Cap� (%) value�
Battery Age
This page also displays the following values:
Battery recommended replacement date
This shows the date that it is recommend to replace the battery� It is 5 years from the time the battery was
installed�
SOH (%)
This shows the current SOH percentage�
Vertiv | Liebert® GXT5™ | Installer/User Guide 69
4.3. Editing Display and Operation Settings
You may adjust the display settings and UPS configuration via the LCD� The display and operation settings are
password protected� The default password is 111111 (six ones)�
NOTE: We recommend that you change the password to protect your system and equipment and record the
new password and store it in an accessible location for later retrieval. See Changing the Password on the next
page.
To enter the password:
1� Press the up-arrow button to change the digit shown, then press the down-arrow button to move to the next
digit�
2� Repeat to select each digit, and press Enter to submit the password�
Figure 4-9 Password Prompt
4.3.1. Settings Prompts
While using the operation and display panel, prompts display to alert you to specific conditions or require
confirmation of commands or settings� Table 4-5 lists the prompts and their meaning�
Table 4-5 Display Prompts and Meanings
PROMPT MEANING
Cannot set this online, please
shut down output Appears when changing important output settings (output voltage, output frequency, output phase No�)�
Incorrect password, please input
again Appears when the Settings password is input incorrectly�
Operation failed, condition is
not met Appears when attempting to execute a operation for which the required conditions are not met�
Password changed OK Appears upon successful change of the Settings password�
Fail to change password, please
try again Appears when attempting to change the Settings password but the new and confirmation passwords do not match�
The time cannot be earlier than
system time Appears when attempting to set the time of ‘Turn on delay’ or ‘Turn o delay‘ earlier than the current system time�
Turn on failed, condition is not
met
Appears when proper conditions are not met for UPS power-on� Applies when using the power button or when
execute the command of ‘Turn on/Turn o/to Bypass’ on the LCD panel ‘Control’ page)�
Cannot set this on line, please
unplug REPO Appears when attempting to change the output phase number while the output is connected�
Operation and Display Panel70
4.3.2. Changing the Password
The default password is 111111 (six ones)� You must use the current password to change the password�
NOTE: We recommend that you change the password from the default to protect your system and equipment.
Record the new password and store it in an accessible location for later retrieval.
1� At the main menu, select the Settings icon, and press Enter�
2� At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next
digit, repeat for each digit, then press Enter to access the settings�
3� Use the arrow buttons to select the Monitor tab, then press Enter�
4� Use the down arrow to highlight Change Settings Password, press Enter, and re-enter the current password�
The Input new password dialog opens, see Figure 4-10 below�
5� Enter the new password, then confirm the new password�
A confirmation dialog opens to indicate a successful password change�
6� Press ESC to return to the settings or main menu�
Figure 4-10 New and Confirm Password dialogs
4.3.3. Selecting the Display Language
The LCD is multilingual� The available languages are English, French, Portuguese, Spanish, Chinese, German,
Japanese, and Russian�
To change the language:
1� At the main menu, select the Settings icon, and press Enter�
2� At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next
digit, repeat for each digit, then press Enter to access the settings�
3� Use the arrow buttons to select the Monitor tab, then press Enter�
4� Use the down arrow to highlight Language, then press Enter�
5� Use the up/down arrows to select the language, then press Enter�
All the LCD elements will now display in the selected language�
Vertiv | Liebert® GXT5™ | Installer/User Guide 71
4.3.4. Setting the Date and Time
To adjust the date and time:
1� At the main menu, select the Settings icon, and press Enter�
2� At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next
digit, repeat for each digit, then press Enter to access the settings�
3� Use the arrow buttons to select the Monitor tab, then press Enter�
4� Use the down arrow to highlight Date or Time, then press Enter�
5� Use the up/down arrows to select the date/time, then press Enter to confirm�
6� Use the down arrow to select the digit to change and the up arrow to select the correct digit� Repeat as
needed to set each digit�
72
This page is intentionally left blank�
Vertiv | Liebert® GXT5™ | Installer/User Guide 73
Chapter 5: Maintenance
WARNING! Risk of electric shock
Can cause equipment damage, injury and death. A battery can present a risk of electrical shock and high short-
circuit current.
Observe the following precautions when working on batteries:
• Remove watches, rings and other metal objects�
• Use tools with insulated handles�
• Wear rubber gloves and boots�
• Do not lay tools or metal parts on top of batteries�
• Disconnect input power prior to connecting or disconnecting battery terminals�
• If the battery kit is damaged in any way or shows signs of leakage, contact your Vertiv representative
immediately�
• Handle, transport, and recycle batteries in accordance with local regulations�
• Determine if the battery is inadvertently grounded� If it is, remove the source of the ground� Contact with
any part of a grounded battery can result in electrical shock� The likelihood of such shock will be reduced
if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery
supply not having a grounded supply circuit)�
5.1. Replacing Batteries
WARNING! Risk of electric shock
Can cause injury or death. Disconnect all local and remote electric power supplies before working with the UPS.
Ensure that the unit is shut down and power has been disconnected before beginning any maintenance.
WARNING! Risk of electric shock and explosion
Can cause equipment damage, injury and death. Do not dispose of the battery in a fire. The battery may explode.
Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte
comes into contact with the skin, wash the aected area immediately with plenty of clean water and get medical
attention.
WARNING! Risk of electric shock
Can cause equipment damage, injury and death. A battery can present a risk of electrical shock and high short-
circuit current.
Maintenance74
WARNING! Risk of explosion
Can cause equipment damage, injury and death. A battery can explode if the battery is replaced by an incorrect
type. Dispose of used batteries according to the instructions included with the battery-pack.
Read all safety cautions before proceeding� A trained user can replace the internal battery pack when the UPS
is in a restricted access location (such as a rack or server closet)� To obtain the appropriate replacement battery
pack(s), refer to Table 5-1 below and contact your local dealer or Vertiv representative�
Table 5-1 Replacement Battery-pack Model Numbers
UPS MODEL NUMBER BATTERY PACK MODEL NUMBER QUANTITY REQUIRED
GXT5-750IRT2UXL
GXT5-36VBATKIT
1
GXT5-750IRT2UXLE
GXT5-1000IRT2UXL
GXT5-1000IRT2UXLE
GXT5-1500IRT2UXL
GXT5-48VBATKIT
GXT5-1500IRT2UXLE
GXT5-2000IRT2UXL
GXT5-2000IRT2UXLE
GXT5-3000IRT2UXL
GXT5-72VBATKIT
GXT5-3000IRT2UXLE
GXT5-5000IRT5UXLN
GXT5-192VBATKIT
GXT5-5000IRT5UXLE
GXT5-6000IRT5UXLN
GXT5-6000IRT5UXLE
GXT5-8000IRT5UXLN
GXT5-8000IRT5UXLE
GXT5-10KIRT5UXLN
GXT5-10KIRT5UXLE
GXT5-16KIRT9UXLN
GXT5-384VBATKIT
GXT5-16KIRT9UXLE
GXT5-20KIRT9UXLN
GXT5-20KIRT9UXLE
To replace a battery pack:
NOTE: The internal battery pack is hot-swappable. However, you must exercise caution because; during this
procedure, the load is unprotected from disturbances and power outages. Do not replace the battery while
the UPS is operating in Battery Mode. This will result in a loss of output power and will drop the connected
load.
1� Press the button on the left-front of the UPS front panel, and pull the panel open, then, loosen and remove
the screw from the battery door, see Figure 5-1 on the next page�
2� Lay the cover, battery door, and screw aside for reassembly�
Vertiv | Liebert® GXT5™ | Installer/User Guide 75
3� Grasp the battery handle, and pull out the battery pack, see Figure 5-1�
4� Unpack the replacement battery pack, taking care not to damage the packaging to re-use when disposing of
the old battery�
5� Compare the new and old battery pack to make sure they are the same type and model� If so, proceed with step
6� If they are dierent, stop and contact your Vertiv representative, or Technical Support, http://www�Vertiv�com/
en-us/support/�
6� Line-up and slowly push-in each replacement battery pack� until 2/3 of the length is in the bay, then lift up
and continue to push smoothly until the battery pack is fully inserted in the bay� The battery is fully-inserted
if the battery door fits flush against the UPS�
7� Re-attach the battery door with the screw, and replace the front cover�
8� Activate the new battery pack(s) using the operating/display panel:
NOTE: The display menus and functions are described in Operation and Display Panel on page 47.
• From the main menu, select Settings, then the Monitoring tab and verify that the date and time are
correct� If the date or time need correction, see Setting the Date and Time on page 71�
• Select the Battery tab, use the arrows to select Replace Battery, and press Enter� The replaced battery
packs are activated�
• Use ESC to return to the main display�
Figure 5-1 Replacing the Battery Pack
ITEM DESCRIPTION
1 Front cover
2 Battery door
3 Battery handle
4 Grasp handle and pull battery out�
Maintenance76
5.2. Charging Batteries
The batteries are valve-regulated, non-spillable, lead acid batteries and should be kept charged to attain their
design life� The UPS charges the batteries continuously when it is connected to the utility input power�
If the UPS will be stored for a long time, We recommend connecting the UPS to input power for at least 24 hours
every 4 to 6 months to ensure full recharge of the batteries�
5.3. Checking UPS Operation
NOTE: Operation-check procedures may interrupt output power supplied to the connected load.
We recommend checking the UPS operation once every 6 months� Ensure that output power loss to the connected
load will not cause data loss or other errors before conducting the check�
1� Press the Enter button to check the indicators and display function, see Operation and Display Panel on
page 47�
2� Check for any alarm or fault indicators on the operation/display panel�
3� Make sure that there are no audible or silenced alarms� Select the Log, and look at the Current tab for alarm
and fault history, see Log Screen on page 71�
4� Check the flow screen to ensure the UPS is operating in Normal mode� If the UPS is operating in Bypass mode,
contact Vertiv Technical Support�
5� Check the flow screen to see if batteries are discharging (operating in Battery mode) while utility power is
normal� If so, contact Vertiv Technical Support�
5.4. Cleaning the UPS
WARNING! Risk of electric shock
Can cause injury or death. Disconnect all local and remote electric power supplies before working with the UPS.
Ensure that the unit is shut down and power has been disconnected before beginning any maintenance.
The UPS requires no internal cleaning� If the outside of the UPS becomes dusty, wipe with a dry cloth� Do not use
liquid or aerosol cleaners� Do not insert any objects into the ventilation holes or other openings in the UPS�
Vertiv | Liebert® GXT5™ | Installer/User Guide 77
5.5. Replacing the Power-distribution Box
Use the following procedures to remove/install a power-output distribution box on the UPS�
WARNING! Risk of electric shock
Can cause injury or death. Disconnect all local and remote electric power supplies before working with the UPS.
Ensure that the unit is shut down and power has been disconnected before beginning any maintenance.
1� Transfer the connected equipment to bypass mode�
NOTE: The programmable-output receptacles are powered-o when transferred to Bypass mode.
a� Loosen the upper captive screw over the maintenance bypass breaker, see Figure 5-2 on the next page�
b� Lift the maintenance-bypass breaker cover up, and tighten the lower captive screw� The programmable-
output receptacles are now powered-o�
2� Confirm that the UPS is operating in bypass mode� If not, then manually transfer the connected equipment to
bypass as follows:
a� From the main menu select CONTROL, then press Enter�
b� Select Turn on/o/to bypass and press Enter�
c� Select Turn to bypass and press Enter�
NOTE: The load is unprotected from disturbances in the power supply while the UPS is on bypass.
3� Turn the maintenance-bypass breaker On�
4� Wait 1 minute if the UPS is working on battery mode, then confirm that the UPS is turned-o�
5� Turn the output and input breakers O� On 8-kVA and 10-kVA models, also turn o the bypass breaker�
6� Loosen the remaining captive screws until the power-distribution boxes releases�
7� Remove the power-distribution boxes and set it aside�
8� On the rear of the panel, loosen the screws of the protective cover for the connectors, slide it over the connectors,
and tighten the screws�
NOTE: The captive screws and maintenance-bypass breaker cover is similar for all 5- to 10-kVA models.
Figure 5-2 on next page shows an example on the 5-kVA model.
Maintenance78
Figure 5-2 Maintenance-bypass Breaker Cover and Captive Screws
ITEM DESCRIPTION
1 Captive screws for POD
2 Maintenance-bypass breaker
3 Connector-cover screws
Vertiv | Liebert® GXT5™ | Installer/User Guide 79
5.6. Firmware Updates
The UPS has two firmware components:
• DSP is the firmware for the power module�
• MCU is the firmware for the display panel�
Both may be updated through a connection the UPS, using CLI and the R232 port or, if the UPS includes the
IntelliSlot RDU101 card, using the RJ-45 port on the card�
The latest firmware is available for download from the GXT5 product page at www�vertiv�com� Refer to Table 5-2
below, and make sure you have the correct files for the update�
Table 5-2 Upgrade File Names by UPS Model
UPS MODEL NUMBER DSP FIRMWARE FILENAME MCU FIRMWARE FILENAME
GXT5-500LVRT2UXL
GXT5_Micro_0�5k-3k_P***�bin
GXT5_M***�bin
GXT5-750LVRT2UXL
GXT5-1000LVRT2UXL
GXT5-1500LVRT2UXL
GXT5-2000LVRT2UXL
GXT5-3000LVRT2UXL
GXT5-3KL620RT2UXL
GXT5-3KL630RT2UXL
GXT5-6KL630RT2UXL GXT5_Small_5k-10k_208_P***�bin
GXT5-5000HVRT5UXLN
GXT5_Small_5k-10k_230_P***�bin
GXT5-8000HVRT5UXLN
GXT5-10KHVRT5UXLN
For DSP update files:
• “P”” represents the power module� The number following “P” is the version of the power module�
• “D” represents the rectifier and inverter module� The number following “D” is the version of the rectifier and inverter module�
• “K” is included after the version for the DSP kernel upgrade file, for example: GXT5_Micro_0�5k-3k_P***K�bin)
For MCU update files:
”M” represents the MCU module� The number following “M” represents the MCU software version�
5.6.1. Updating Firmware with RDU101 Card Connection
If your UPS has an IntelliSlot RDU101 communication card installed (optional on some models), you can update
firmware with a computer connected to the same network as the card�
NOTE: The RDU101 card is password protected. Be sure to obtain the user name and password from an
administrator. The name and password may have been changed from the default.
NOTE: For detailed operating instructions for the card, refer to the Liebert® IntelliSlot™ RDU101
Communications Card Installer/User Guide, available at www.Vertiv.com.
Maintenance80
Updating MCU Firmware via RDU101
NOTE: Do not update firmware while the UPS is on Battery mode.
1� Connect a network cable to the RJ-45 Ethernet port of the RDU101 card� For the card/connection location, refer
to the appropriate rear-panel description for your UPS model in Rear Panels on page 5�
2� On a computer connected to the same network as the UPS, open a browser window and enter the IP address of
the RDU101 card in the address bar�
You can get the card’s IP address from the display panel� Select the About menu then the Product tab, and locate
IPv4 address�
NOTE: We recommend using the Google Chrome browser.
3� Upload the update file using the card’s user interface, see Figure 5-3 on the next page�
a� Select the “GXT5” tab, then the File Transfer folder in the tab-menu pane on the left-hand side of the page�
b� On the file-transfer page, click Choose File, and select the MCU upgrade file, then click Transfer file�
c� Enter the Username and Password, then click Login�
The factory-defaults:
Username : Liebert (case-sensitive)
Password: Liebert (case-sensitive)
NOTE: The name and password may have been changed from the default. Be sure to obtain the username and
password from an administrator.
The status of the transfer displays in the File Transfer Status section� After about 2 minutes, the UPS restarts and
the web page refreshes�
NOTE: The transfer process takes about 2 minutes. Do not leave or close the page until the status is “Update
Complete.”
d� You can check the firmware version, select the System folder in the tab-menu pane on the left-hand side of the
page, and check the Firmware Version field, see Figure 5-4 on the next page�
Vertiv | Liebert® GXT5™ | Installer/User Guide 81
Figure 5-3 File Transfer on the RDU101 User Interface
ITEM DESCRIPTION
1 "UPS" tab, typically the UPS model number
2 File Transfer folder
3 Choose File button
4 Transfer File button
5 Status of file transfer
Figure 5-4 Firmware Version on the RDU101 User Interface
Maintenance82
5.7. Updating DSP Firmware via RDU101
NOTE: Only update the DSP firmware while the UPS is in Stand-by mode. The REPO terminal of the UPS must
be un-plugged. When the REPO terminal is unplugged the load will lose power. Do not update firmware while
the UPS is on Battery mode.
1� Disconnect the REPO terminal from the rear panel of the UPS, see Figure 5-5 below�
Figure 5-5 REPO Terminal
2� Connect a network cable to the RJ-45 Ethernet port of the RDU101 card� For the card/connection location, refer
to the appropriate rear-panel description for your UPS model in Rear Panels on page 5�
3� On a computer connected to the same network as the RDU101 open a browser window and enter the IP
address of the RDU101 card in the address bar�
You can get the card’s IP address from the display panel� Select the About menu then the Product tab, and
locate IPv4 address�
NOTE: We recommend using the Google Chrome browser.
4� Upload the update file using the card’s user interface, see Figure 5-6 on the next page�
a� Select the “GXT5” tab, then the File Transfer folder in the tab-menu pane on the left-hand side of the page�
b� On the file-transfer page, click Choose File, and select the DSP upgrade file, then click Transfer file�
c� Enter the Username and Password, then click Login�
The factory-defaults:
Username : Liebert (case-sensitive)
Password: Liebert (case-sensitive)
NOTE: The name and password may have been changed from the default. Be sure to obtain the user name
and password from an administrator.
The status of the transfer displays in the File Transfer Status section� After about 2 minutes, the UPS restarts and
the web page refreshes�
Vertiv | Liebert® GXT5™ | Installer/User Guide 83
NOTE: The transfer process takes about 2 minutes. Do not leave or close the page until the status is “Update
Complete.”
d� You can check the firmware version, select the System folder in the tab-menu pane on the left-hand side of the
page, and check the Firmware Version field, see Figure 5-7�
Figure 5-6 File Transfer on the RDU101 User Interface
Figure 5-7 Firmware Version on the RDU101 User Interface
Maintenance84
5.8. Updating Firmware with a CLI Connection
You can use the Vertiv command-line interface to update firmware with a computer connected to the R232 (RJ-
45) port on the rear of the UPS�
To perform the update via CLI, you need the following:
• Serial-terminal emulator with Ymodem transfer ability (for example: ExtraPuTTY)
• Cable with RJ-45 connector on one end and DB9 connector on the other or an RJ45/FTDI USB serial-port
adapter
Updating MCU Firmware via CLI
NOTE: Do not update firmware while the UPS is on Battery mode.
1� Connect the RJ-45 connector to the R232 port on UPS� For the connection location, refer to the appropriate
rear-panel description for your UPS model in Rear Panels on page 5�
2� Connect the DB9/USB connector to the computer with the serial-terminal emulator installed�
3� Open the serial-terminal emulator, and adjust the settings to communicate with the UPS:
• Select “Serial” connection for the session�
• Check the computer “device management” settings for the communication port (for example COM6),and
select it in the emulator�
• Select 115200 for the connection speed�
• Open the emulator session�
4� On the CLI, enter the username and password:
• Default username = user
• Default password = 123456
5� On the command line, enter update, then press d on the keyboard, see Figure 5-8 on the next page
6� In the menu bar, select Files Transfer > Ymodem, select the MCU upgrade file, then click Send�
The status of the transfer displays in a status dialog� After about 3 minutes, the UPS restarts and the CLI exits
update mode�
NOTE: The transfer process takes about 3 minutes. Do not close the status dialog.
a� You can check the firmware version by entering status system in the command line�
Vertiv | Liebert® GXT5™ | Installer/User Guide 85
Figure 5-8 File Transfer with the CLI
Updating DSP Firmware via CLI
NOTE: Only update the DSP firmware while the UPS is in Stand-by mode. The REPO terminal of the UPS must
be un-plugged. Do not update firmware while the UPS is on Battery mode.
1� Disconnect the REPO terminal from the rear panel of the UPS, see Figure 5-9 below�
Figure 5-9 REPO Terminal
2� Connect the RJ-45 connector to the R232 port on UPS� For the connection location, refer to the appropriate
rear-panel description for your UPS model in Rear Panels on page 5�
3� Connect the DB9 connector to a computer with the serial-terminal emulator installed�
Maintenance86
4� Open the serial-terminal emulator, and adjust the settings to communicate with the UPS:
• Select “Serial” connection for the session�
• Check the computer “device management” settings for the communication port (for example COM6),and
select the same port in the emulator�
• Select 115200 for the connection speed�
• Open the emulator session�
5� On the CLI, enter the username and password:
• Default username = user
• Default password = 123456
6� On the command line, enter update, then press d on the keyboard, see Figure 5-10 on the next page�
7� In the menu bar, select Files Transfer > Ymodem, select the MCU upgrade file, then click Send�
The status of the transfer displays in a status dialog� After about 2 minutes, the UPS restarts and the CLI exits
update mode�
NOTE: The transfer process takes about 2 minutes. Do not close the status dialog.
a� You can check the firmware version by entering status system in the command line�
Figure 5-10 File Transfer with the CLI
Vertiv | Liebert® GXT5™ | Installer/User Guide 87
Chapter 6: Troubleshooting
This section indicates various UPS symptoms you may encounter and provides a troubleshooting guide in the
event the UPS develops a problem� Use the following information to determine whether external factors caused
the problem and how to remedy the situation�
6.1. Symptoms that Require Troubleshooting
The following symptoms indicate the UPS is malfunctioning:
• The alarm indicator illuminates, indicating the UPS has detected a problem�
• An alarm buzzer sounds, alerting the user that the UPS requires attention�
6.2. Audible Alarm (Buzzer)
An audible alarm accompanies various events during UPS operations� Table 6-1 below, describes the sounds and
their meaning� To silence an alarm, see Silencing the Audible Alarm on page 43�
Table 6-1 Audible-alarm Descriptions
SOUND INDICATES
Continuous beep Generated when a UPS fault appears, such as a fuse or hardware failure�
One beep every 0�5 seconds Generated when a UPS critical alarm appears, such as on inverter overload�
One beep every 1 second Generated when a UPS critical alarm appears, such as on battery low voltage�
One beep every 3�3 seconds Generated when a UPS general alarm appears�
NOTE: When an alarm is indicated, an alarm message is logged. Table 4-4 on page 64, describes the alarm
messages you may see. When a fault is indicated, front-panel display list the fault, which are described in Table
6-2 below.
Troubleshooting88
6.2.1. Faults
When the fault indicator is illuminated, the LCD displays the fault� The faults are described in Table 6-2 below�
Table 6-2 Description of displayed faults
DISPLAYED FAULT CAUSE CORRECTIVE STEPS
Battery test fail The battery is bad or weak� Contact technical support�
Rectifier fault A rectifier failure occurred� Contact technical support�
Inverter overload,
Bypass overcurrent The UPS is overloaded, Bypass is over current� Reduce the load and contact technical support�
Inverter fault The inverter is faulty� Contact technical support�
Battery aged The battery is bad or weak� Replace the battery�
Output short The output connection is short-circuited� Shut-down the equipment and contact technical support�
DC bus fail The DC bus is faulty� Contact technical support�
System overtemp Over-temperature condition in the UPS� The UPS
will transfer to bypass mode� Reduce the load and contact technical support�
Charger fault The charger is faulty� Contact technical support�
Fan fault At least one fan is faulty� Contact technical support�
DC/DC fault A DC-DC charger failure occurred� Contact technical support�
6.3. Troubleshooting UPS Issues
In the event of an issue with the UPS, refer to Table 6�3 below, to determine the cause and solution� If the fault
persists, contact Vertiv Technical Support� Visit the GXT5 product page at www�vertiv�com for contact information�
When reporting a UPS issue to Vertiv, include the UPS model and serial number� These are located in several
places for your ease of location:
• On the top panel (rack mount orientation)
• The left side (tower orientation)
• The rear panel
• On the front of the unit behind the front plastic bezel
• On the LCD select Main Menu > About
Table 6-3 Troubleshooting
PROBLEM CAUSE SOLUTION
UPS fails to
start
UPS is short- circuited or
overloaded
Ensure UPS is O� Disconnect all loads and ensure nothing is lodged in output receptacles� Ensure loads
are not defective or shorted internally�
Batteries are not charged
enough or not connected
Check to ensure the internal battery is connected� If it is not, fully remove and reinstall the battery, and
try to start the unit� If the battery is connected, leave the UPS connected to input power for 24 hours to
recharge batteries, then try to start the unit�
UPS has
reduced
battery
backup time
Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries�
UPS is overloaded Check load level indicator and reduce the load on the UPS�
Batteries may not be able to
hold a full charge due to age
Replace batteries� Contact your Vertiv representative or Vertiv Technical Support for replacement
battery kit�
Vertiv | Liebert® GXT5™ | Installer/User Guide 89
Chapter 7: Specifications
Table 7-1 UPS Specifications, 750 VA and 1000 VA models
MODEL GXT5- 750IRT2UXL 750IRT2UXLE 1000IRT2UXL 1000IRT2UXLE
RATING 750 VA/750 W 1000 VA/1000 W
Dimensions, D×W×H, in. (mm)
Unit 15�7 x 16�9 x 3�4 (400 x 430 x 85)
Shipping 24�3 x 22�4 x 10�3 (617 x 570 x 262)
Weight, lb.(kg)
Unit 36�3 (16�5)
Shipping 51�7 (23�5) 46�2 (21) 51�7 (23�5) 46�2 (21)
Input AC
Voltage Range (typical) 230 VAC nominal; variable based on output load
90% ~ 100% loading 168 ~ 288 VAC
70% ~ 90% loading 150 ~ 288 VAC
28% ~ 70% loading 115 ~ 288 VAC
0 ~ 28% loading 115 ~ 288 VAC
Frequency 40 Hz ~ 70 Hz; Auto Sensing
Input Power Cord C14
Output AC
Output Receptacles C13×8
Voltage 200/208/220/230/240 VAC (user-configurable); ±3%
Waveform Sine wave
Utility (AC) Model
Overload
>200% for 250 ms
150-200% for 2 seconds
125-150% for 50 seconds
105-125% 60 seconds
Internal Charger
Charging current Nominal 2�2 A; Maximum 8 A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 3 × 12V × 9�0 Ah
Battery Mfr�/Part# LEOCH DJW12-9�0
Backup time See Battery Run Times on page 100�
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
Environmental Requirements
Operating Temperature,
°F (°C) +32 to +122 (0 to 50); Operating temperature may be increased to 122 °F (50 °C with a 10% derating of the output power
Storage Temperature, °F
(°C) -4to +140 (-20 to 60) ( contain batteries will be from -15 to 40 °C�)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft� (3000 m) at 77 ºF (25 ºC) without derating
Audible Noise <46 dBA max @ 3 ft� (1 m) front and sides <43 dBA max @ 3 ft� (1 m) rear
Specifications90
Table 7-1 UPS Specifications, 750 VA and 1000 VA models (continued)
MODEL GXT5- 750IRT2UXL 750IRT2UXLE 1000IRT2UXL 1000IRT2UXLE
RATING 750 VA/750 W 1000 VA/1000 W
Agency
Safety
EN 62040-1:2008+A1:2013;
GS mark;
UL 1778 5th Edition and CSA 22�2 No� 107�1
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62�41 Category B IEC 61000-4-5 Surges/Lightning
RFI/EMI CISPR22 Class A
Table 7-2 UPS Specifications, 1500 VA and 2000 VA Models
MODEL GXT5- 1500IRT2UXL 1500IRT2UXLE 2000IRT2UXL 2000IRT2UXLE
RATING 1500 VA/1500 W 2000 VA/2000 W
Dimensions, D×W×H, in. (mm)
Unit 18�5×16�9×3�4 (470×430×85)
Shipping 24�3 ×22�4 x 10�3 (617 x 570 x 262)
Weight, lb.(kg)
Unit 46�2 (21)
Shipping 61�6 (28) 56�1 (25�5) 61�6 (28) 56�1 (25�5)
Input AC
Voltage Range(typical) 230 VAC nominal; variable based on output load
90% ~ 100% loading 168 ~ 288 VAC
70% ~ 90% loading 150 ~ 288 VAC
28% ~ 70% loading 115 ~ 288 VAC
0 ~ 28% loading 115 ~ 288 VAC
Frequency 40 Hz ~ 70 Hz; Auto Sensing
Input Power Cord C14 C20
Output AC
Output Receptacles C13×8
Voltage 200/208/220/230/240 VAC (user-configurable); ±3%
Waveform Sine wave
Utility (AC) Model Overload
>200% for 250 ms
150-200% for 2 seconds
125-150% for 50 seconds
105-125% 60 seconds
Internal Charger
Charging current Nominal 2�2 A; Maximum 8 A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 4 × 12V × 9�0 Ah
Vertiv | Liebert® GXT5™ | Installer/User Guide 91
Table 7-2 UPS Specifications, 1500 VA and 2000 VA Models (continued)
MODEL GXT5- 1500IRT2UXL 1500IRT2UXLE 2000IRT2UXL 2000IRT2UXLE
RATING 1500 VA/1500 W 2000 VA/2000 W
Backup time See Battery Run Times on page 100�
Recharge Time 4 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
Environmental Requirements
Operating
Temperature, °F (°C) +32 to +122 (0 to 50); Operating temperature may be increased to 122 °F (50 °C with a 10% derating of the output power
Storage
Temperature, °F (°C) -4to +140 (-20 to 60) ( contain batteries will be from -15 to 40 °C�)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft� (3000 m) at 77ºF (25ºC) without derating
Audible Noise <46 dBA max @ 3ft� (1 m) front and sides <45dBA max @ 3 ft�
(1 m) rear
<48 dBA max @ 3ft� (1m) front and sides <48 dBA max @ 3 ft�
(1 m) rear
Agency
Safety
EN 62040-1:2008+A1:2013;
GS mark;
UL 1778 5th Edition and CSA 22�2 No� 107�1
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62�41 Category B IEC 61000-4-5 Surges/Lightning
RFI/EMI CISPR22 Class A
Table 7-3 UPS Specifications, 3000 VA Models
MODEL GXT5- 3000IRT2UXL 3000IRT2UXLE
RATING 3000 VA/3000 W
Dimensions, D×W×H, in.(mm)
Unit 21�3 x 16�9 x 3�4 (540 × 430 × 85)
Shipping 28�2 x 22�4 x 10�3 (717 x 570 x 262)
Weight, lb.(Kg)
Unit 62 (28�2)
Shipping 79�2 (36) 72�6 (33)
Input AC
Voltage Range (typical) 230 VAC nominal; variable based on output load
90% ~ 100% loading 184 ~ 288 VAC
70% ~ 90% loading 161 ~ 288 VAC
28% ~ 70% loading 115 ~ 288 VAC
0 ~ 28% loading 115 ~ 288 VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Cord C20
Output AC
Output Receptacles C13×6&C19
Specifications92
Table 7-3 UPS Specifications, 3000 VA Models (continued)
MODEL GXT5- 3000IRT2UXL 3000IRT2UXLE
RATING 3000 VA/3000 W
Voltage 200/208/220/230/240 VAC (user-configurable); ±3%
Waveform Sine wave
Utility(AC) Model
Overload
>200% for 250 ms
150- 200% for 2 seconds
125- 150% for 50 seconds
105-125% 60 seconds
Internal Charger
Charging current Nominal 2�2 A; Maximum 8 A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 6 × 12V × 9�0 Ah
Battery Mfr�/Part# LEOCH DJW12-9�0
Backup time See Battery Run Times on page 100�
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
Environmental Requirements
Operating Temperature,
°F (°C) +32 to +122 (0 to 50); Operating temperature may be increased to 122 °F (50 °C with a 10% derating of the output power
Storage Temperature, °F
(°C) -4to +140 (-20 to 60)( contain batteries will be from -15 to 40 °C�)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft� (3000 m) at 77 ºF (25 ºC) without derating
Audible Noise <48 dBA max @ 3 ft� (1 m) front and sides <48 dBA max @ 3 ft� (1 m) rear
Agency
Safety
EN 62040-1:2008+A1:2013;
GS mark;
UL 1778 5th Edition and CSA 22�2 No� 107�1
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62�41 Category B IEC 61000-4-5 Surges/Lightning
RFI/EMI CISPR22 Class A
Vertiv | Liebert® GXT5™ | Installer/User Guide 93
Table 7-4 UPS Specifications, 5-kVA and 6-kVA models
MODEL: GXT5- 5000IRT5UXLN 5000IRT5UXLE 6000IRT5UXLN 6000IRT5UXLE
RATING 5000 VA/5000 W 6000 VA/6000 W
Dimensions, mm (in.)
Unit, WxDxH 430×630×217 (16�9×24�8×8�5)
Shipping, WxDxH 646×816×520 (25�4×32�1×20�5)
Weight, kg (lb)
Unit 70�8 (156)
Shipping 92 (202�8) 89 (196�2) 92 (202�8) 89 (196�2)
Input AC Parameters
Operating Frequency, Nom� 50 or 60 Hz (factory-default is 50 Hz)
Factory-default VAC 230 VAC
User-configurable VAC 200/208/220/230/240 VAC
(Adjustable using operation/display configuration options)
Operating voltage range without
battery operation 176 – 288 VAC (100 – 176 VAC with power derating)
Maximum Allowable VAC 288 VAC
Input frequency without battery
operation 40 – 70 Hz
Input Power Connection PD5-CE6HDWRMBS PD5-CE6HDWRMBS
Output AC Parameters
AC-AC Eiciency 94%
Factory-default VAC Frequency 230 VAC, 50 Hz
Output Power Connection PD5-CE6HDWRMBS PD5-CE6HDWRMBS
Waveform Sinewave
Normal Mode Overload
> 150% minimum 200 ms
125 – 150% for 60 seconds
105 – 125% for 5 minutes
≤ 105% continuous
Internal Battery Charger
Charger Current, A 2�25 A default, maximum 5 A
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage x Rating 16 x 12V x 9�0AH
Battery Mfr�/Part # LEOCH DJW12-9�0
Back-up time See Table 7-15 on page 102� See Table 7-16 on page 103�
Upper-limit selections +10%, +15%, +20%; default +10%�
Lower-limit selections -10%, -15%, -20%; default -15%
Disable-bypass operation When the input frequency prevents synchronous operation�
Environmental Parameters
Operating Temperature, °C (°F) 0 to 40 (32 to 104) (no derating)
Storage Temperature, °C (°F) -15 to 40 (5 to 104)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842�5 ft) at 25°C (77°F) without derating
Audible Noise <55 dBA, at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Specifications94
Table 7-4 UPS Specifications, 5-kVA and 6-kVA models (Continued)
MODEL: GXT5- 5000IRT5UXLN 5000IRT5UXLE 6000IRT5UXLN 6000IRT5UXLE
RATING 5000 VA/5000 W 6000 VA/6000 W
Agency Parameters
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A
Transportation ISTA Procedure 1E
Table 7-5 UPS Specifications, 8-kVA and 10-kVA models
MODEL: GXT5- 8000IRT5UXLN 8000IRT5UXLE 10KIRT5UXLN 10KIRT5UXLE
RATING 8000 VA/8000 W 10000 VA/10000 W
Dimensions, mm (in.)
Unit, WxDxH 430×630×217 (16�9×24�8×8�5)
Shipping, WxDxH 646×816×520 (25�4×32�1×20�5)
Weight, kg (lb)
Unit 74�5 (164�2)
Shipping 95 (209�4) 93 (205) 95 (209�4) 93 (205)
Input AC Parameters
Operating Frequency, Nom� 50 or 60 Hz (factory-default is 50 Hz)
Factory-default VAC 230 VAC
User- configurable VAC 200/208/220/230/240 VAC
(Adjustable using operation/display configuration options)
Operating voltage range
without battery operation 176 – 288 VAC (100 – 176 VAC with power derating)
Maximum Allowable VAC 288 VAC
Input frequency without
battery operation 40 – 70 Hz
Input Power Connection PD5-CE10HDWRMBS PD5-CE10HDWRMBS
Output AC Parameters
AC-AC Eiciency 94�5% 95%
Factory-default VAC
Frequency 230 VAC, 50 Hz
Output Power Connection PD5-CE10HDWRMBS PD5-CE10HDWRMBS
Waveform Sinewave
Main Mode Overload
> 150% minimum 200 ms
125 – 150% for 60 seconds
105 – 125% for 5 minutes
≤ 105% continuous
Internal Battery Charger
Charger Current, A 2�25 A default, maximum 8 A
Vertiv | Liebert® GXT5™ | Installer/User Guide 95
Table 7-5 UPS Specifications, 8-kVA and 10-kVA models (Continued)
MODEL: GXT5 8000IRT5UXLN 8000IRT5UXLE 10KIRT5UXLN 10KIRT5UXLE
RATING 8000 VA/8000 W 10000 VA/10000 W
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage x Rating 16 x 12V x 9�0AH
Battery Mfr�/Part # LEOCH DJW12-9�0
Back-up time See Table 7-17 on page 103� See Table 7-18 on page 104�
Upper-limit selections +10%, +15%, +20%; default +10%�
Lower-limit selections -10%, -15%, -20%; default -15%
Disable-bypass operation When the input frequency prevents synchronous operation�
Environmental Parameters
Operating Temperature, °C (°F) 0 to 40 (32 to 104) (no derating)
Storage Temperature, °C (°F) -15 to 40 (5 to 104)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842�5 ft) at 25°C (77°F) without derating
Audible Noise <55 dBA, at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Agency Parameters
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast
Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A
Transportation ISTA Procedure 1E
Specifications96
Table 7-6 UPS Specifications, 16-kVA and 20-kVA models
MODEL: GXT5- 16KIRT9UXLN 16KIRT9UXLE 20KIRT9UXLN 20KIRT9UXLE
RATING 16000 VA/16000 W 20000 VA/20000 W
Dimensions, mm (in.)
Unit, WxDxH 430×630×394 (16�9×24�8×15�5)
Shipping, WxDxH 900×1200×700 (35�4×47�2×27�6)
Weight, kg (lb)
Unit 135�2 (298)
Shipping 190 (418�9) 186�7 (411�6) 190 (418�9) 186�7 (411�6)
Input AC Parameters
Operating Frequency, Nom� 50 or 60 Hz (factory-default is 50 Hz)
Factory-default VAC 230 VAC
User-configurable VAC 200/208/220/230/240 VAC
(Adjustable using operation/display configuration options)
Operating voltage range without
battery operation 176 – 288 VAC (100 – 176 VAC with power derating)
Maximum Allowable VAC 288 VAC
Input frequency without battery
operation 40 – 70 Hz
Input Power Connection Input terminal block
Output AC Parameters
AC-AC Eiciency 95%
Factory-default VAC Frequency 230 VAC, 50 Hz
Output Power Connection Output terminal block
Waveform Sinewave
Main Mode Overload
> 150% minimum 200 ms
125 – 150% for 60 seconds
105 – 125% for 5 minutes
≤ 105% continuous
Internal Battery Charger
Charger Current, A 2�25 A default, maximum 13 A
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage x Rating 32 x 12V x 9�0AH
Battery Mfr�/Part # LEOCH DJW12-9�0
Back-up time See Table 7-19 on page 104� See Table 7-20 on page 105�
Upper-limit selections +10%, +15%, +20%; default +10%�
Lower-limit selections -10%, -15%, -20%; default -15%
Disable-bypass operation When the input frequency prevents synchronous operation�
Environmental Parameters
Operating Temperature, °C (°F) 0 to 40 (32 to 104) (no derating)
Storage Temperature, °C (°F) -15 to 40 (5 to 104)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842�5 ft) at 25°C (77°F) without derating
Vertiv | Liebert® GXT5™ | Installer/User Guide 97
Table 7-6 UPS Specifications, 16-kVA and 20-kVA models (Continued)
MODEL: GXT5- 16KIRT9UXLN 16KIRT9UXLE 20KIRT9UXLN 20KIRT9UXLE
RATING 16000 VA/16000 W 20000 VA/20000 W
Audible Noise <58 dBA, at 1 meter from the front,
<51 dBA, at 1 meter from rear or sides
Agency Parameters
Safety IEC62040-1:2008 version, GS mark; UL1778, c-UL listed
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A)
CISPR22 Class A (RFI)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62�41 Category B
Transportation ISTA Procedure 1E
Table 7-7 Power distribution specification
MODEL NUMBER PD5-CE6HDWRMBS
PD5-CE6HDWRMBSU
PD5-CE10HDWRMBS
PD5-CE10HDWRMBSU
Amp Rating 50 A 63 A
Input Power Connection Single-phase (L-N-G) hard-wired
Output Power Connection Single-phase (L-N-G) hard-wired
Includes Two IEC320 C19 16 A/250 V Sockets
Six C13 10 A/250 V Sockets
Four IEC320 C19 16 A/250 V Sockets
Four C13 10 A/250 V Sockets
Input Branch Circuit
Breaker, Supplied by User 50 A 63 A
Specifications98
Table 7-8 External Battery Cabinet Specifications, 750 VA to 3000 VA models
MODEL NUMBER GXT5-EBC36VRT2U GXT5-EBC48VRT2U GXT5-EBC72VRT2U
USED W/UPS MODEL 750 – 1,000 VA MODELS 1,500 – 2,000 VA MODELS 3,000 VA MODELS
Dimensions, D×W×H, in. (mm)
Unit 14�6 x 16�9 x 3�3
(370 × 430 × 85)
19�7 x 16�9 x 3�3
(497 × 430 × 85)
23�7 x 16�9 x 3�3
(602 × 430 × 85)
Shipping 24�3 x 22�4 x 10�3 (617 x 570 x 262)
Weight, lb.(Kg)
Unit 48�4 (22) 57�3 (28�5) 85�8 (39)
Shipping 91�3 (41�5) 86 (41�5) 110 (50)
Battery
Type Valve-regulated, non-spillable, lead acid
Qty × V 3 × 12V 4 × 12V 6 × 12V
Battery Mfr�/Part# LEOCH DJW12-9�0
Backup time See appropriate table for model size in Battery Run Times on page 100�
Environmental Requirements
Operating Temperature, °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C) 5 to 104 (-15 to 40) High ambient temperatures will reduce battery life
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft� (3000 m) at 77 ºF (25 ºC) without derating
Agency
Safety
EN 62040-1:2008+A1:2013;
GS mark;
UL 1778 5th Edition and CSA 22�2 No� 107�1
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Safety UL 1778 5th Edition and CSA 22�2 No� 107�1
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62�41 Category B
RFI/EMI FCC Part 15 (Class A)
Vertiv | Liebert® GXT5™ | Installer/User Guide 99
Table 7-9 External Battery Cabinet Specifications, 5-kVA to 20-kVA models
MODEL NUMBER GXT5-EBC192VRT3U GXT5-EBC384VRT6U
USED WITH UPS MODEL 5 – 10 KVA MODELS 16 – 20 KVA MODELS
Dimensions, WxDxH, mm (in.)
Unit (with bezel) 430 x 630 x 130 (16�9 x 24�8 x 5�1) 430 x 630 x 261 (16�9 x 24�8 x 10�3)
Shipping 840 x 670 x 465 (33 x 26�4 x 18�3) 840 x 670 x 595 (33 x 26�4 x 23�4)
Weight, kg (lb)
Unit 57�6 (127) 112 (246�9)
Shipping 80 (176�4) 136 (299�8)
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage 16 x 12V 32 x 12V
Battery Mfr�/Part# LEOCH DJW12-9�0
Back-up Time See appropriate table for model size in Battery Run Times on page 100�
Environmental Parameters
Operating Temp, °C (°F) 0 to 40 (32 to 104)
Storage Temp, °C (°F) -15 to 40 (5 to 104)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842�5 ft�) at 25°C (77°F)
Agency Parameters
Safety IEC62040-1:2008 version, GS mark; UL1778, c-UL listed
Transportation ISTA Procedure 1E
Specifications100
7.1. Battery Run Times
NOTE: Run times in this table are approximate. Times are based on new, fully-charged, standard battery
modules at a temperature of 77 °F (25 °C) with 100% resistive UPS loading. Run times listed above can vary
by ±5% due to manufacturing variances of the individual batteries.
Table 7-10 Battery Run Time, 750 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 75 75 135�4 444�1 770�8 1123�4 1452�2 1695�4 1863�8 1987�3 2081�7 2156�3 2216�6
20 150 150 68�0 229�0 401�4 581�6 760�5 952�0 1147�8 1330�7 1499�7 1635�5 1745�4
30 225 225 44�1 163�7 281�7 407�9 537�8 663�9 800�6 939�7 1080�9 1221�8 1350�2
40 300 300 33�7 127�1 218�3 316�1 416�5 519�9 620�3 724�8 833�9 944�6 1056�5
50 375 375 25�7 103�2 178�9 255�9 337�1 420�2 505�5 592�1 672�6 761�7 852�0
60 450 450 20�4 84�8 149�0 212�4 280�7 350�0 420�3 492�6 565�3 631�7 706�8
70 525 525 16�7 72�0 128�2 183�8 238�8 298�1 358�3 419�6 481�8 544�9 607�0
80 600 600 14�1 59�7 112�1 161�6 208�6 260�6 313�2 366�4 420�4 475�8 531�1
90 675 675 12�1 53�0 99�5 143�9 188�3 232�1 278�8 326�1 374�6 423�3 473�1
100 750 750 10�5 46�3 88�3 130�2 170�8 208�8 251�5 294�1 337�6 381�7 426�5
Table 7-11 Battery Run Time, 1000 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 100 100 101�8 332�7 584�9 841�2 1114�7 1373�2 1590�9 1750�8 1873�0 1969�6 2047�7
20 200 200 50�1 179�8 311�9 453�2 595�8 736�7 888�2 1042�4 1199�1 1340�5 1476�5
30 300 300 33�7 127�1 218�3 316�1 416�5 519�9 620�3 724�8 833�9 944�6 1056�5
40 400 400 23�8 95�8 168�9 239�3 316�4 394�3 474�5 555�3 629�9 713�6 798�3
50 500 500 17�8 76�3 135�1 193�0 251�8 314�0 377�3 443�1 506�8 573�0 632�6
60 600 600 14�1 59�7 112�1 161�6 208�6 260�6 313�2 366�4 420�4 475�8 531�1
70 700 700 11�5 50�7 95�3 139�4 181�7 224�1 268�6 315�0 361�0 408�6 457�6
80 800 800 9�6 43�3 83�4 120�8 160�1 197�6 235�3 275�3 316�3 357�1 399�0
90 900 900 8�1 38�2 73�0 107�4 141�0 174�8 206�9 241�5 277�6 314�0 350�4
100 1000 1000 6�8 33�3 62�8 94�6 125�7 156�3 187�0 216�1 248�0 280�4 313�1
Vertiv | Liebert® GXT5™ | Installer/User Guide 101
Table 7-12 Battery Run Time, 1500 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 150 150 107�3 350�3 612�3 885�6 1173�2 1436�2 1644�5 1797�2 1914�0 2006�2 2080�9
20 300 300 52�8 187�9 325�3 472�1 618�0 769�6 927�7 1089�0 1247�1 1393�8 1526�8
30 450 450 32�7 123�9 213�1 309�0 407�6 508�2 609�2 708�8 815�3 923�4 1033�0
40 600 600 22�2 89�2 159�1 226�4 297�8 371�9 448�5 523�5 600�5 672�1 751�6
50 750 750 16�3 70�2 125�3 179�9 234�5 292�4 351�5 411�5 472�8 533�9 596�2
60 900 900 12�7 55�1 103�5 148�3 194�8 239�7 289�0 338�1 387�8 439�9 489�9
70 1050 1050 10�1 44�5 85�9 125�6 165�6 203�4 243�0 285�0 326�6 369�5 412�5
80 1200 1200 8�2 38�6 73�8 108�4 142�3 176�3 208�4 244�0 280�4 316�9 353�6
90 1350 1350 6�7 32�7 61�7 93�2 124�1 154�3 184�8 213�4 245�0 277�0 309�4
100 1500 1500 5�6 28�2 54�3 83�4 111�2 138�5 165�8 192�5 218�4 246�7 275�3
Table 7-13 Battery Run Time, 2000 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 200 200 78�5 258�8 455�3 650�5 861�7 1078�7 1289�4 1482�1 1636�0 1757�5 1855�8
20 400 400 36�2 134�8 231�0 334�0 442�2 550�0 653�9 767�6 883�1 1000�1 1118�7
30 600 600 21�8 88�2 156�6 223�1 293�8 366�4 441�9 515�7 592�1 662�0 740�7
40 800 800 14�8 63�1 115�9 167�7 216�8 269�8 324�8 380�4 437�8 493�7 551�2
50 1000 1000 10�7 47�1 89�2 131�9 172�7 211�1 254�6 297�4 341�8 386�1 432�1
60 1200 1200 8�2 38�5 73�5 108�1 141�9 175�8 208�0 243�2 279�6 316�0 352�7
70 1400 1400 6�3 31�0 58�9 89�2 119�1 148�5 178�3 206�2 236�1 266�8 297�8
80 1600 1600 5�0 25�9 50�1 78�1 103�9 129�3 154�3 179�9 204�6 230�7 257�6
90 1800 1800 4�0 22�0 42�9 66�5 88�9 113�0 136�0 158�2 180�4 202�5 225�2
100 2000 2000 3�2 18�8 38�1 57�1 79�8 99�9 119�3 140�7 161�0 180�6 200�6
Specifications102
Table 7-14 Battery Run Time, 3000 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 300 300 78�9 260�2 457�8 654�1 866�5 1084�9 1296�1 1488�8 1641�8 1762�7 1860�5
20 600 600 36�7 136�3 233�3 337�8 447�1 556�0 660�9 775�9 892�7 1011�1 1131�0
30 900 900 21�9 88�4 157�2 223�8 294�7 367�6 443�3 517�4 594�0 664�2 743�1
40 1200 1200 14�9 63�3 116�1 168�0 217�3 270�3 325�4 381�2 438�7 494�7 552�4
50 1500 1500 10�8 47�5 89�6 132�6 173�6 212�5 256�0 299�0 343�8 388�2 434�7
60 1800 1800 8�3 38�8 74�2 109�0 143�0 177�1 209�4 245�5 282�0 318�7 355�6
70 2100 2100 6�4 31�4 59�4 89�8 119�9 149�5 179�5 207�6 237�8 268�8 300�0
80 2400 2400 5�1 26�2 50�6 78�7 104�8 130�4 155�7 181�3 206�0 232�5 259�6
90 2700 2700 4�1 22�4 43�3 67�6 89�7 114�2 137�5 160�2 182�6 204�5 227�9
100 3000 3000 3�3 19�1 38�7 57�9 80�9 101�6 121�1 142�6 163�5 183�4 203�2
Table 7-15 Battery Run Time, 5-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 500 500 120�0 272�5 427�5 582�5 737�5 892�5 1047�5 1202�5 1357�5 1512�5 1667�5
20 1000 1000 59�0 129�0 211�0 294�0 377�0 460�0 543�0 625�5 708�5 791�5 874�5
30 1500 1500 36�5 85�0 133�0 189�5 246�0 303�0 359�5 416�5 473�0 530�0 586�5
40 2000 2000 25�0 62�5 99�0 136�0 179�5 222�5 266�0 309�5 353�0 396�5 439�5
50 2500 2500 18�5 48�0 78�0 107�5 138�0 173�0 208�0 243�0 278�0 313�5 348�5
60 3000 3000 14�5 38�5 63�5 88�0 113�0 138�5 168�0 197�0 226�5 256�0 285�5
70 3500 3500 11�5 31�0 53�0 74�0 95�5 117�0 139�0 164�5 189�5 214�5 240�0
80 4000 4000 9�5 26�0 45�0 64�0 82�5 101�0 120�0 139�5 161�5 183�5 206�0
90 4500 4500 8�0 22�0 38�5 55�5 72�0 89�0 105�5 122�0 140�0 159�5 179�0
100 5000 5000 7�0 19�0 33�5 49�0 64�0 79�0 94�0 109�0 124�0 140�0 158�0
Vertiv | Liebert® GXT5™ | Installer/User Guide 103
Table 7-16 Battery Run Time, 6-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 600 600 100�0 226�0 357�5 489�0 621�0 752�5 884�5 1016�0 1148�0 1279�5 1411�5
20 1200 1200 48�0 107�0 172�0 242�0 312�0 382�0 452�0 522�0 592�0 661�5 731�5
30 1800 1800 29�0 70�0 110�0 154�0 201�5 249�5 297�5 345�5 393�0 441�0 489�0
40 2400 2400 19�5 50�5 81�5 112�5 145�0 181�5 218�0 254�5 291�0 327�5 364�0
50 3000 3000 14�5 38�5 63�5 88�0 113�0 138�5 168�0 197�0 226�5 256�0 285�5
60 3600 3600 11�0 30�0 51�0 72�0 92�5 113�5 134�0 158�5 183�5 208�0 232�5
70 4200 4200 9�0 24�0 42�0 60�5 78�0 96�0 113�5 131�5 152�5 173�5 194�5
80 4800 4800 7�5 20�0 35�5 51�5 67�0 82�5 98�5 114�0 129�5 147�5 166�0
90 5400 5400 6�0 17�0 30�5 44�5 58�5 72�5 86�5 100�5 114�0 128�0 143�5
100 6000 6000 5�5 14�5 26�0 39�0 51�5 64�5 77�0 89�5 102�0 114�5 127�0
Table 7-17 Battery Run Time, 8-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 800 800 75�0 166�0 267�5 369�0 471�0 572�5 674�5 776�0 878�0 979�5 1081�0
20 1600 1600 33�5 79�0 124�5 176�0 229�5 283�0 336�5 390�0 443�5 496�5 550�0
30 2400 2400 19�5 50�5 81�5 112�5 145�0 181�5 218�0 254�5 291�0 327�5 364�0
40 3200 3200 13�0 35�0 59�0 82�0 105�5 128�5 155�0 183�0 210�5 238�0 265�5
50 4000 4000 9�5 26�0 45�0 64�0 82�5 101�0 120�0 139�5 161�5 183�5 206�0
60 4800 4800 7�5 20�0 35�5 51�5 67�0 82�5 98�5 114�0 129�5 147�5 166�0
70 5600 5600 6�0 16�0 29�0 42�5 56�0 69�5 83�0 96�5 110�0 123�5 137�5
80 6400 6400 4�5 13�5 24�0 35�5 48�0 59�5 71�5 83�0 95�0 106�5 118�5
90 7200 7200 4�0 11�5 20�5 30�5 41�0 52�0 62�5 73�0 83�5 94�0 104�5
100 8000 8000 3�5 9�5 17�5 26�5 36�0 45�5 55�5 64�5 74�0 83�5 93�0
Specifications104
Table 7-18 Battery Run Time, 10-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 1000 1000 59�0 129�0 211�0 294�0 377�0 460�0 543�0 625�5 708�5 791�5 874�5
20 2000 2000 25�0 62�5 99�0 136�0 179�5 222�5 266�0 309�5 353�0 396�5 439�5
30 3000 3000 14�5 38�5 63�5 88�0 113�0 138�5 168�0 197�0 226�5 256�0 285�5
40 4000 4000 9�5 26�0 45�0 64�0 82�5 101�0 120�0 139�5 161�5 183�5 206�0
50 5000 5000 7�0 19�0 33�5 49�0 64�0 79�0 94�0 109�0 124�0 140�0 158�0
60 6000 6000 5�5 14�5 26�0 39�0 51�5 64�5 77�0 89�5 102�0 114�5 127�0
70 7000 7000 4�0 12�0 21�0 31�5 42�5 54�0 64�5 75�0 86�0 97�0 107�5
80 8000 8000 3�5 9�5 17�5 26�5 36�0 45�5 55�5 64�5 74�0 83�5 93�0
90 9000 9000 2�5 8�0 15�0 22�5 30�5 39�5 48�0 56�5 65�0 73�0 81�5
100 10000 10000 2�0 7�0 13�0 19�5 26�5 34�5 42�0 50�0 57�5 65�0 72�5
Table 7-19 Battery Run Time, 16-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 1600 1600 79�0 176�0 283�0 390�0 496�5 603�5 710�5 817�5 924�0 1031�0 1138�0
20 3200 3200 35�0 82�0 128�5 183�0 238�0 293�0 348�0 403�5 458�5 513�5 568�5
30 4800 4800 20�0 51�5 82�5 114�0 147�5 184�5 221�5 258�5 295�5 332�5 369�5
40 6400 6400 13�5 35�5 59�5 83�0 106�5 130�5 157�5 185�5 213�5 241�5 269�0
50 8000 8000 9�5 26�5 45�5 64�5 83�5 102�5 121�5 141�5 164�0 186�5 209�0
60 9600 9600 7�5 20�5 36�0 52�5 68�0 84�0 100�0 115�5 131�5 150�0 168�5
70 11200 11200 6�0 16�5 29�5 43�5 57�5 71�0 84�5 98�0 112�0 125�5 140�5
80 12800 12800 5�0 14�0 24�5 36�5 49�0 61�0 73�0 85�0 97�0 109�0 121�0
90 14400 14400 4�0 11�5 21�0 31�0 42�0 53�0 63�5 74�5 85�0 95�5 106�5
100 16000 16000 3�5 10�0 18�0 27�0 36�5 46�5 56�5 66�0 75�5 85�0 94�5
Vertiv | Liebert® GXT5™ | Installer/User Guide 105
Table 7-20 Battery Run Time, 20-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6 7 8 9 10
%VA W Minutes
10 2000 2000 62�5 136�0 222�5 309�5 396�5 483�0 570�0 656�5 743�5 830�5 917�0
20 4000 4000 26�0 64�0 101�0 139�5 183�5 228�0 272�5 316�5 361�0 405�0 449�5
30 6000 6000 14�5 39�0 64�5 89�5 114�5 140�5 170�5 200�0 230�0 259�5 289�5
40 8000 8000 9�5 26�5 45�5 64�5 83�5 102�5 121�5 141�5 164�0 186�5 209�0
50 10000 10000 7�0 19�5 34�5 50�0 65�0 80�5 95�5 111�0 126�0 142�5 161�0
60 12000 12000 5�5 15�0 27�0 40�0 53�0 65�5 78�5 91�5 104�0 117�0 129�5
70 14000 14000 4�0 12�0 21�5 32�5 43�5 55�0 66�0 76�5 87�5 98�5 109�5
80 16000 16000 3�5 10�0 18�0 27�0 36�5 46�5 56�5 66�0 75�5 85�0 94�5
90 18000 18000 3�0 8�5 15�0 23�0 31�0 40�0 48�5 57�5 66�0 74�5 83�0
100 20000 20000 2�5 7�0 13�0 19�5 27�0 34�5 42�5 50�5 58�0 66�0 73�5
Specifications106
This page is intentionally left blank�
Vertiv | Liebert® GXT5™ | Installer/User Guide 107
Appendix I: Open Source Software Legal Notices
The GXT5 product links the FreeRTOS software with Vertiv Group Corporation’s proprietary modules that
communicate with the FreeRTOS software solely through the FreeRTOS API interface� This use is an exception to
the FOSS GPLv2 license� The user is free to redistribute the FreeRTOS software and/or modify it under the terms of
the GNU General Public License as published by the Free Software Foundation� A copy of the GNU General Public
License is located at www�gnu�org/licenses/old-licenses/gpl-2�0�html A copy of the exception is located at https://
spdx�org/licenses/freertos-exception-2�0�html� For a period of three (3) years after purchasing the GXT5 product,
the purchaser has the right to obtain a copy of the FreeRTOS software that is incorporated in the GXT5 product�
The purchaser can contact Vertiv Technical Support and request the software�
Open Source Software Legal Notices108
This page is intentionally left blank�
Vertiv | Liebert® GXT5™ | Installer/User Guide 109
Appendix II:Technical Support
Our Technical Support sta is ready to assist you with any installation or operating issues you may encounter with
your Liebert® product� Please call or e-mail us:
In Europe, Middle East, and Asia
EMEA Multi-Language Technical support
e: eoc@vertiv�com
p: Toll free 0080011554499
p: Toll +39 02 98250222
In the United States
Technical support
e: liebert�upstech@vertiv�com
p: 1-800-222-5877 menu option 1
Monitoring support
e: liebert�monitoring@vertiv�com
p: 1-800-222-5877 menu option 2
Warranty support
e: microups�warranty@vertiv�com
p: 1-800-222-5877 menu option 3
Technical Support110
This page is intentionally left blank�
© 2019 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered marks of Vertiv Group Corp. All other names and
logos referred to are trade names, trademarks, or registered trademarks of their respective owners. While every precaution has been taken to ensure
accuracy and completeness herein. Vertiv Co. assumes no responsibility and disclaims all liability, for damages resulting from use of this information or for any
errors or omissions. Specifications are subject to change without notice.
SL-70547_REV0_11-19