Vertiv GXTRT-3000IRT2UXL User Manual
Displayed below is the user manual for GXTRT-3000IRT2UXL by Vertiv which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals
Liebert® GXT RT+ UPS
230 V Input, 230 V Output
I
Installer/User Guide
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-emea/support/ for additional assistance.
The information contained in this document is subject to change
without notice and may not be suitable for all applications.
While every precaution has been taken to ensure the accuracy
and completeness of this document, Vertiv assumes no
responsibility and disclaims all liability for damages resulting
from use of this information or for any errors or omissions. Refer
to other local practices or building codes as applicable for the
correct methods, tools, and materials to be used in performing
procedures not specifically described in this document.
The products covered by this instruction manual are
manufactured and/or sold by Vertiv. This document is the
property of Vertiv and contains confidential and proprietary
information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions
regarding usage of trademark names should be directed to the
original manufacturer.
Vertiv | Liebert® GXT RT+ | Installer/User Guide i
Table of Contents
Important Safety Information................................................................................................................................................................................................1
Chapter 1: GXT RT+ Description..................................................................................................................................................................................................3
1.1. UPS Features and Available Models.......................................................................................................................................................................3
1.2. External Battery Cabinet.................................................................................................................................................................................................3
Chapter 2: Installation and Setup.....................................................................................................................................................................................5
2.1. Rear Panel Views...................................................................................................................................................................................................................5
2.2. Installing the UPS..................................................................................................................................................................................................................6
2.2.1.Rack Installation..........................................................................................................................................................................................................6
2.2.2.Tower Installation......................................................................................................................................................................................................6
2.3. Setup the UPS...........................................................................................................................................................................................................................6
Chapter 3: Operations.................................................................................................................................................................................................................9
3.1. Button Operation.....................................................................................................................................................................................................................9
3.2. LCD Panel......................................................................................................................................................................................................................................9
3.3. Audible Alarm...........................................................................................................................................................................................................................12
3.4. LCD Display Wordings Index.....................................................................................................................................................................................12
3.5. UPS Setting.................................................................................................................................................................................................................................13
3.6. Operating Mode Description.....................................................................................................................................................................................16
3.7. Faults Reference Code.....................................................................................................................................................................................................17
3.8. Warning Indicators..............................................................................................................................................................................................................18
Chapter 4: Troubleshooting................................................................................................................................................................................................20
Vertiv | Liebert® GXT RT+ | Installer/User Guideii
Chapter 5: Storage and Maintenance.......................................................................................................................................................................22
5.1. Operation.....................................................................................................................................................................................................................................22
5.2. Storage.........................................................................................................................................................................................................................................22
5.3. Battery Replacement for Rack UPS.................................................................................................................................................................23
Chapter 6: Specifications.....................................................................................................................................................................................................24
Appendix I: Technical Support.......................................................................................................................................................................................28
Vertiv | Liebert® GXT RT+ | Installer/User Guide 1
Important Safety Information
Comply with all warnings and operating instructions in this manual strictly. Save this manual and carefully read
the following instructions before installing the unit. Do not operate this unit before reading all safety information
and operating instructions carefully.
Transportation
Only transport the UPS system in the original packaging to protect against shock and impact.
Preparation
• Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to
acclimate the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct sunlight or near a heater.
• Do not block ventilation holes in the UPS housing.
Installation
• Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS
output sockets.
• Place cables in such a way that no one can step on or trip over them.
• Do not connect domestic appliances such as hair dryers to UPS output sockets.
• Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to
the UPS system.
• Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the
UPS system to the building wiring shockproof outlet.
• Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
• When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected
devices does not exceed 3.5 mA.
Important Safety Information2
Operation
• Do not disconnect the mains cable on the UPS system or the building wiring shockproof outlet during
operations since this would cancel the protective earthing of the UPS system and of all connected loads.
• The UPS system features its own, internal power source (batteries). The UPS output sockets or output
terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
• In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
• Prevent fluids and foreign objects from entering the inside of the UPS system.
Maintenance, Service, and Faults
• The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance
personnel.
• Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet),
components inside the UPS system are still connected to the battery and electrically live and dangerous.
• Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no
current is present and no hazardous voltage exists in the terminals of high energy capacitors such as BUS-
capacitors.
• Only persons that are adequately familiar with batteries and with the required precautionary measures may
replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
• Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages
may occur between the battery terminals and the ground. Before touching, please verify that no voltage is
present!
• Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary
measures specified below and any other measures necessary when working with batteries:
»Remove wristwatches, rings and other metal objects
»Use only tools with insulated grips and handles.
• When changing batteries, install the same number and same type of batteries.
• Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
• Recycle or dispose of batteries properly according to local regulations.
• Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
• Please replace fuses only with the same type and amperage in order to avoid fire hazards.
• Do not dismantle the UPS system.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 3
Chapter 1: GXT RT+ Description
1.1. UPS Features and Available Models
The GXT RT+ includes the following features. Table 1-1 below, lists the available models and power ratings.
• Input power factor of 0.9.
• Automatic bypass, allowing the load to transfer to the mains in case of an overload or internal fault.
• Optional tower or rack installation to meet varying installation requirements.
• Adapts to areas with unstable power-mains supply via high-frequency double-conversion topology structure,
with high input-power factor, wide input-voltage range, and output immune to grid interference.
• ECO power-supply mode helps you save the maximum amount of energy.
Table 1-1 UPS Models and Power Ratings
MODEL NUMBER NOMINAL POWER RATING
GXTRT-1000IRT2UXL 1000 VA/900 W
GXTRT-1500IRT2UXL 1500 VA/1350 W
GXTRT-2000IRT2UXL 2000 VA/1800 W
GXTRT-3000IRT2UXL 3000 VA/2700 W
1.2. External Battery Cabinet
Optional external battery cabinets are available for the UPS. Table 1-2 below to determine which EBC works with
your system. Only connect an external battery of the same voltage and chemistry to the UPS.
Table 1-2 External Battery Cabinet
EBC MODEL NUMBER COMPATIBLE UPS MODELS
GXTRT-EBC24VRT2U GXTRT-1000IRT2UXL
GXTRT-EBC36VRT2U GXTRT-1500IRT2UXL
GXTRT-EBC48VRT2U GXTRT-2000IRT2UXL
GXTRT-EBC72VRT2U GXTRT-3000IRT2UXL
4
This page is intentionally left blank.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 5
Chapter 2: Installation and Setup
Before installation, please inspect the unit for shipping damage. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
The UPS should be installed in an area away from vibration, dust, humidity, high temperature, flammable liquids,
gases, corrosive and conductive contaminants. Install the UPS indoors in a clean environment, where it is away
from windows and doors. Maintain minimum of 300 mm clearance on the front and rear panels of the UPS.
2.1. Rear Panel Views
Figure 2-1 Rear Panels
ITEM DESCRIPTION
1 AC input
2 Input circuit breaker
3 USB communication port
4 RS 232 communication port
5 SNMP intelligent slot (option)
6 External battery connection
7 Output receptacles
GXTRT-1000IRT2UXL GXTRT-1500IRT2UXL
GXTRT-2000IRT2UXL
GXTRT-3000IRT2UXL
Installation and Setup6
2.2. Installing the UPS
2.2.1. Rack Installation
This UPS can be mounted in a 19” rack chassis as shown in below.
Step 1 Step 2
2.2.2. Tower Installation
To install the UPS as a tower:
1. Take the support bases out of the accessories box.
2. If optional, external battery cabinets will be connected, take out the spacers shipped with each battery
cabinet.
3. Connect the spacers and the support bases. Each GXT RT+ requires 2 support bases, one in the front and one
in the rear.
4. Place the GXT5 and any battery cabinets on the 2 support bases.
2.3. Setup the UPS
Step 1: Connect battery wires
If using External Battery Cabinets (EBCs), verify that the EBC breaker is in the “O” position. Then, connect
one end of the supplied EBC cable to the UPS and one end to the battery cabinet. If connecting more than one
external battery, connect one end of the external battery cable to the second connector on the battery cabinet,
then connect the other end to the next battery cabinet.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 7
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. The power cord
is supplied in the UPS package. Use an upstream circuit breaker rated for your model based on the below table.
MODEL NUMBER RECOMMENDED CIRCUIT BREAKER RECOMMENDED POWER CABLE WIRE SIZE
GXTRT-1000IRT2UXL
10 A 18 AWG
GXTRT-1500IRT2UXL
GXTRT-2000IRT2UXL
GXTRT-3000IRT2UXL 20 A 14 AWG
Step 3: UPS output connection
Connect devices to be protected to the outlets.
Step 4: Communication connection
Communication Port
USB port RS-232 port Intelligent slot
Installation and Setup8
To allow for unattended UPS shutdown/start up and status monitoring, connect the communication cable one
end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software
installed, you can schedule UPS shutdown/start up and monitor UPS status through your PC.
The UPS is equipped with an intelligent slot for either an SNMP or AS400 card. When either an SNMP or AS400
card is installed, it will provide advanced communication and monitoring options.
Note: The USB port and RS-232 port cannot operate at the same time.
Step 5: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery
run capability during this initial charge period.
Step 6: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown of the
attached computer. Follow the steps below to download and install monitoring software from the Internet:
1. Go to the website http://vertiv.com/Liebert-GXT-RT-Plus.
2. Select the appropriate ViewPower download link for the OS of the attached computer.
3. Follow the on screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon located in the
system tray, near the clock.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 9
Chapter 3: Operations
3.1. Button Operation
BUTTON FUNCTION
ON/MUTE/UP
• Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
• Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 sec-
onds to disable or enable the current active audible alarm. The audible alarm will automatically
enable if another warning or error occurs.
• Up key: Press this button to display previous selection in UPS setting mode.
• Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPS
self-testing while in AC mode, ECO mode, or converter mode.
OFF/ENTER
• Turn o the UPS: Press and hold this button at least 2 seconds to turn o the UPS. UPS will be in
standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by
pressing this button.
• Confirm selection key: Press this button to confirm selection in UPS setting mode.
SELECT/DOWN
• Switch LCD message: Press this button to change the LCD message for input voltage, input fre-
quency, battery voltage, output voltage and output frequency.
• Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in
standby mode or bypass mode.
• Down key: Press this button to display next selection in UPS setting mode.
ON/MUTE/UP +
SELECT/DOWN
Buttons
• Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons si-
multaneously for 5 seconds. Then, UPS will enter to bypass mode if the input voltage is within the
acceptable range. This is the normal way to switch to bypass. If desired, the UPS can also be set
to switch to bypass when switched o instead of turning o all outputs. See Setting 05: Bypass
enable/disable when UPS is o, on page 14 for details.
Operations10
3.2. LCD Panel
DISPLAY FUNCTION
Remaining backup time setting and information
Illuminated when UPS is in battery backup mode.
Indicates the backup time remaining in number of hours, minutes, or seconds.
H: hours, M: minute, S: second
Setting operation
Shows the setting number currently selected when in settings menu.
Fault & warning information
A warning or fault is occurring.
Shows the active warning or fault code.
The codes are listed in detail in Section 3.5 UPS Setting.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 11
DISPLAY FUNCTION
Mute operation
The audible alarm is disabled when this is lit.
UPS information
Shows the currently selected status from the following list:
- Vac input voltage
- Vac output voltage
- Vdc battery voltage
- Hz frequency
- % load level
- °C/°F internal temperature
Load information
Displays the output load level by showing 1- 4 bars:
1 bar - 0-25%
2 bars - 26-50%
3 bars - 51-75%
4 bars - 76-100%
The output is overloaded.
The output is shorted.
Mode operation information
The UPS is in online mode.
The UPS is in battery mode.
The UPS is in bypass mode.
The UPS is in ECO mode.
Operations12
DISPLAY FUNCTION
The UPS is in frequency converter mode.
The UPS is charging the battery.
Battery information
Displays the battery capacity by showing 1- 4 bars:
1 bar - 0-25%
2 bars - 26-50%
3 bars - 51-75%
4 bars - 76-100%
The battery has faulted.
Shows that the battery level is low.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 13
3.3. Audible Alarm
Condition Audible Alarm
Bypass Mode Sounds every 10 seconds
Battery Mode Sounds every 4 seconds
Low Battery Sounds every second
Overload Sounds twice every second
Fault Continuously sounds
3.4. LCD Display Wordings Index
LCD AREA DISPLAY CONTENT ABBREVIATION MEANING
ENA Enable
DIS Disable
ESC Escape
b.L Low battery
O.L Overload
N.C Battery is not connected
O.C Overcharge
C.H Charger
b.F Battery fault
b.V Bypass voltage out of range
W.T Waiting
F.U Bypass frequency unstable
E.E EEPROM error
Operations14
3.5. UPS Setting
To adjust UPS settings, switch the UPS to standby mode and press and hold the settings button for 5 seconds
to enter the settings menu. Use the arrow keys to browse to the desired setting and then press enter to select it.
Once selected, use the arrow keys to select the desired settings value. Browse to setting 00, ESC and select ESC
to leave the menu.
There are two numbers shown when browsing the UPS
setting menu.
The top number is for the setting number. Refer to the
table below for details of each setting.
The bottom number is the setting option or value for
each setting number.
01: Output voltage setting
INTERFACE SETTING
You may choose the following output voltages:
220: output voltage is 220 Vac
230: output voltage is 230 Vac (Default)
240: output voltage is 240 Vac
02: Frequency Converter enable/disable
INTERFACE SETTING
Enable or disable frequency converter mode.
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
Vertiv | Liebert® GXT RT+ | Installer/User Guide 15
03: Output frequency setting
INTERFACE SETTING
By default, the following output frequencies can be set on battery mode.
The battery indicator will be shown as in the top image to the left.
50: output frequency is 50 Hz (Default)
60: output frequency is 60 Hz
If frequency converter mode is enabled, the following output frequencies
can be selected. Th CF symbol will be shown as in the bottom image to
the left.
50: output frequency is 50 Hz (Default)
60: output frequency is 60 Hz
04: ECO enable/disable
INTERFACE SETTING
Enable or disable ECO mode.
ENA: ECO mode enabled
DIS: ECO mode disabled (Default)
05: Bypass enable/disable when UPS is o
INTERFACE SETTING
Enable or disable Bypass when the UPS is o.
ENA: Bypass enable
DIS: Bypass disable (Default)
Operations16
06: Backup time setting
INTERFACE SETTING
Sets the amount of backup time on battery mode for general outlets
before power is removed.
0-998: setting the backup time in minutes from 0-998 in battery mode.
0: When setting as “0”, the backup time will be only 10 seconds.
999: When setting as “999”, the backup time setting will be disabled.
(default)
07: Battery total AH setting
INTERFACE SETTING
Set up the battery total AH of the UPS. (unit: AH)
7-999: sets the total battery capacity from 7-999 in AH.
Please set the correct battery capacity if EBCs are connected.
Each GXT RT+ EBC adds 18 AH.
00: Exit setting
INTERFACE SETTING
ESC: Exit the setting menu.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 17
3.6. Operating Mode Description
OPERATING MODE DESCRIPTION LCD DISPLAY
Turn on
When pressing the “ON/MUTE” button, if battery
voltage is within acceptable range, “ON” will flash
until the UPS is turned on.
Online mode
When the input voltage is within acceptable range,
UPS will provide pure and stable AC power to
output. The UPS will also charge the battery in
online mode.
ECO mode
Energy saving mode:
When the input voltage is within voltage regulation
range, UPS will bypass input voltage to the output
to save energy.
Frequency
Converter mode
When input frequency is within 40 Hz to 70Hz, the
UPS can be set at a constant output frequency,
50 Hz or 60 Hz. The UPS will still charge battery
under this mode.
Battery mode
When the input voltage is outside the acceptable
range, the UPS will provide backup power from the
battery and the alarm will sound every 4 seconds.
Operations18
OPERATING MODE DESCRIPTION LCD DISPLAY
Bypass mode
When input voltage is within the acceptable range
but the UPS is overloaded, UPS will enter bypass
mode or bypass mode can be set by front panel.
The alarm will sound every 10 seconds.
Standby mode UPS output is o, but the battery is still charged as
needed.
Fault mode
The UPS is in fault mode when no output power
can be supplied from the UPS and the fault icon
and number are displayed on the LCD display. The
alarm will sound continuously.
3.7. Faults Reference Code
FAULT EVENT FAULT CODE FAULT ICON
Bus start fail 01 X
Bus over 02 X
Bus under 03 X
Bus unbalance 04 X
Bus short 05 X
Inverter soft start fail 11 X
Inverter voltage high 12 X
Vertiv | Liebert® GXT RT+ | Installer/User Guide 19
FAULT EVENT FAULT CODE FAULT ICON
Inverter voltage Low 13 X
Inverter output short 14
Battery voltage too high 27
Battery voltage too low 28
Over temperature 41 X
Over load 43
Charger failure 45 X
3.8. Warning Indicators
WARNING INDICATOR ALARM
WORD ICON (FLASHING)
Low battery b.L Sounds every second
Over load O.L Sounds twice every second
Battery is not connected N.C Sounds every second
Overcharge O.C Sounds every second
Waiting W.T Sounds every second
Charger failure C.H Sounds every second
Bypass voltage out of range b.V Sounds every second
Operations20
WARNING INDICATOR ALARM
WORD ICON (FLASHING)
Battery fault b.F Sounds every second
Bypass frequency unstable F.U Sounds every second
EEPROM error E.E Sounds every second
Vertiv | Liebert® GXT RT+ | Installer/User Guide 21
Chapter 4: Troubleshooting
If the UPS system does not operate correctly, please use the table below to resolve the problem.
SYMPTOM POSSIBLE CAUSE REMEDY
No indication and alarm even though the mains is
normal
The AC input power is not connected
well
Check if the input power cord is firmly
connected to the mains
The AC input is not connected to the
UPS output
Plug the AC input power cord to AC
input correctly
The icon and flashing on LCD display and
alarm is sounding every second
The external or internal battery is
incorrectly connected
Check if all batteries are connected
well
Fault code is shown as 27 and the icon is
lighting on LCD display and alarm is continuously
sounding
Battery voltage is too high or the
charger has faulted Contact Vertiv
Fault code is shown as 28 and the icon is
lighting on LCD display and alarm is continuously
sounding
Battery voltage is too low or the
charger has faulted Contact Vertiv
The icon and is flashing on LCD
display and alarm is sounding twice every second
UPS is overloaded Remove excess loads from UPS output
UPS is overloaded. Devices connected
to the UPS are fed directly by the
electrical network via the Bypass.
Remove excess loads from UPS output
After repetitive overloads, the UPS is
locked in the Bypass mode. Connected
devices are fed directly by the mains
Remove excess loads from UPS output
first. Then shut down the UPS and
restart it
Fault code is shown as 43 and The icon is
lighting on LCD display and alarm is continuously
sounding
The UPS shut down automatically
because of overload at the UPS output
Remove excess loads from UPS output
and restart it
Fault code is shown as 14 and the icon is
lighting on LCD display alarm is continuously
sounding
The UPS shut down automatically
because short circuit occurs on the
UPS output
Check output wiring and if connected
devices are in short circuit status
Fault code is shown as 1, 2, 3, 4, 11, 12, 13 , 41 and 45
on LCD display and alarm is continuously sound
A UPS internal fault has occurred.
There are two possible results:
1. The load is still supplied, but directly
from AC power via bypass.
2. The load is no longer supplied by
power.
Contact Vertiv
Battery backup time is shorter than nominal value Batteries are not fully charged
Charge the batteries for at least 5
hours and then check the capacity. If
the problem still persists, consult Vertiv
Batteries defect Contact Vertiv to replace the battery
Fault code 05 is shown on LCD display. At the same
time, the alarm is continuously sounding and the
output is o
A UPS internal fault has occurred and
BUS is short circuited
Consult Vertiv. If the UPS power is on
again before repair, the DC/DC mosfet
will damage
22
This page is intentionally left blank.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 23
Chapter 5: Storage and Maintenance
5.1. Operation
The UPS system contains no user-serviceable parts. If the battery service life (3 ~ 5 years at 25 °C ambient
temperature) has been exceeded, the batteries must be replaced. In this case, please contact Vertiv.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the
replacement battery packing material.
5.2. Storage
Before storing, charge the UPS for at least 5 hours. Store the UPS covered and upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:
STORAGE TEMPERATURE RECHARGE FREQUENCY CHARGING DURATION
-25 °C - 40 °C Every 3 months 1-2 hours
40 °C - 45 °C Every 2 months 1-2 hours
Storage and Maintenance24
5.3. Battery Replacement for Rack UPS
NOTICE: This UPS is equipped with hot swappable internal batteries that the user can replace without shutting
down the UPS or connected loads. Replacement is a safe procedure, isolated from electrical hazards.
CAUTION!! Read all warnings, cautions, and notes before replacing batteries.
Note: Upon battery disconnection, equipment is not protected from power outages.
Step 1
Step 4
Step 7
Remove the front panel.
Remove the top cover of battery box
and replace the inside batteries.
Put the front panel back to the unit.
Disconnect the battery wires.
After replacing the batteries, put
the battery box back to original
location and replace the screws
tightly.
Pull out the battery box by removing
two screws on the front panel.
Re-connect the battery wires.
Step 2
Step 5
Step 3
Step 6
Vertiv | Liebert® GXT RT+ | Installer/User Guide 25
Chapter 6: Specifications
Table 6-1 UPS Specifications
CAPACITY 1000 VA/ 900 W 1500 VA/ 1350 W 2000 VA/ 1800 W 3000 VA/ 2700 W
GXTRT- 1000IRT2UXL 1500IRT2UXL 2000IRT2UXL 3000IRT2UXL
INPUT
Voltage
Range
Low Line Transfer
180 VAC / 160 VAC / 140 VAC / 120 VAC ± 5%
(Ambient Temp. < 35 °C)
(Based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)
Low Line Comeback
195 VAC / 175 VAC / 155 VAC / 135 VAC ± 5 %
(Ambient Temp. < 35 °C)
(Based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)
High Line Transfer 300 VAC ± 5 %
High Line Comeback 290 VAC ± 5 %
Frequency Range 40 Hz ~ 70 Hz
Phase Single phase with ground
Power Factor 0.95 @ nominal input voltage
OUTPUT
Output Voltage 220/230/240 VAC
Output Power Factor 0.9
AC Voltage Regulation ± 1% (Batt. Mode)
Frequency Range 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode) 50 Hz ± 0.5% or 60 Hz ± 0.5%
Overload in Online Mode
Ambient Temp. < 35 °C:
< 105%: Operate continuously
105% - 110%: Transfer to bypass after 10 minutes
110% - 130%: Transfer to bypass after 1 minute
> 130%: Transfer to bypass after 3 seconds
Ambient Temp. > 35 °C:
Derate above times 50%
Overload in Battery Mode
Ambient Temp. < 35 °C:
< 105%: Operate continuously
105% - 110%: UPS shuts down after 10 minutes
110% - 130%: UPS shuts down after 1 minute
> 130%: UPS shuts down after 3 seconds
Ambient Temp. > 35 °C:
Derate above times 50%
Overload in bypass Mode
< 110%: Operate continuously
110% - 120%: UPS shuts down after 30 minutes
120% - 130%: UPS shuts down after 10 minutes
130% - 150%: UPS shuts down after 1 minute
> 150%: UPS shuts down immediately
Transfer
Time
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform Pure Sinewave
EFFICIENCY
Online Mode 88% 88% 89% 90%
Battery Mode 83% 84% 87% 88%
Specifications26
Table 6-1 UPS Specifications (continued)
CAPACITY 1000 VA/ 900 W 1500 VA/ 1350 W 2000 VA/ 1800 W 3000 VA/ 2700 W
GXTRT- 1000IRT2UXL 1500IRT2UXL 2000IRT2UXL 3000IRT2UXL
BATTERY
Battery Type Valve-regulated, non-spillable, lead acid
Quantity x
Voltage x Rating 2 x 12V x 9Ah 3 x 12V x 9Ah 4 x 12V x 9Ah 6 x 12V x 9Ah
Recharge Time 4 hours recover to 90% capacity (Typical)
Charging
Current 1.0 A (max.)
Charging
Voltage 27. 2 VDC ± 1% 40.9 VDC ± 1% 54.4 VDC ± 1% 81.7 VDC ± 1%
PHYSICAL
Unit Dimensions
D X W X H (mm) 312 x 438 x 88 462 x 438 x 88 632 x 438 x 88
Unit Weight
(kgs) 11 14.5 18.2 27.6
Shipping
Dimensions D X
W X H (mm)
600 x 500 x 240 700 x 565 x 240 760 x 600 x 240
Shipping Weight
(kgs) 13.1 16.8 20.7 31.2
MANAGEMENT
Smart RS-232 or
USB Supports Windows® 2003/XP/Vista/2008/7/8/2012/10/2016/2019, Linux, and MAC
Optional SNMP Power management from SNMP manager and web browser
AGENCY
Safety CE Mark; IEC/EN 62040-1: 2014
EMI IEC/EN 62040-2:2006+AC:2006 Class A
Surge Immunity EN 61000-4-5: 2005 Class 2 L-N, Class 3 L-G
Transportation ISTA 2A
ENVIRONMENTAL REQUIREMENTS
Operating
Temperature, °C 0 to 50*
Storage
Temperature, °C -20 to 50
Operating
Relative
Humidity
20% to 90%, non-condensing
Storage Relative
Humidity 10% to 90%, non-condensing
Operating
Elevation
2000 m without derating. Between 2000 and 3000 m, derate 1% for every 100m.
Operation above 3000 m is not supported.
Noise Level 55 dBA Max @ 1 Meter
*To extend battery life, it is recommended to use the UPS in the range of 15 - 25 °C.
The threshold of low line transfer and low line comeback is increased when Ambient Temp. is 35 - 50 °C.
70% derating of output when Ambient Temp. is 40 - 50 °C.
The overload capacity is decreased when Ambient Temp. is 40 - 50 °C.
Transfer to bypass mode and show temp. alarm when Ambient Temp. > 50 °C and transfer back to online mode when Ambient Temp. < 40 °C.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 27
Table 6-2 EBC Specifications
MODEL NUMBER GXTRT- EBC24VRT2U EBC36VRT2U EBC48VRT2U EBC72VRT2U
USED W/UPS MODEL GXTRT- 1000IRT2UXL 1500IRT2UXL 2000IRT2UXL 3000IRT2UXL
PHYSICAL
Unit Dimensions D X W X H (mm) 410 x 438 x 88 510 x 438 x 88 630 x 438 x 88
Unit Weight (kgs) 12.5 17.2 23.3 41.5
Shipping Dimensions D X W X H (mm) 600 x 500 x 240 700 x 565 x 240 760 x 600 x 240
Shipping Weight (kgs) 15 22 28.5 48.5
BATTERY
Battery Type Valve-regulated, non-spillable, lead acid
Battery Configuration
Two parallel strings of two
12V/9Ah
batteries in series.
Two parallel strings of
three 12V/9Ah
batteries in series.
Two parallel strings of
four 12V/9Ah
batteries in series.
Two parallel strings of six
12V/9Ah
batteries in series.
Charging Voltage 27.2 VDC ± 1% 40.9 VDC ± 1% 54.4 VDC ± 1% 81.7 VDC ± 1%
AGENCY
Safety CE Mark; IEC/EN 62040-1: 2014
EMI IEC/EN 62040-2: 2006+AC:2006 Class A
Surge Immunity EN 61000-4-5: 2005 Class 2 L-N, Class 3 L-G
Transportation ISTA 2A
ENVIRONMENTAL REQUIREMENTS
Operating Temperature, °C 0 to 50
Storage Temperature, °C -20 to 50
Operating Relative Humidity 20% to 90%, non-condensing
Storage Relative Humidity 10% to 90%, non-condensing
Operating Elevation 2000 m without derating. Between 2000 and 3000 m, derate 1% for every 100 m.
Operation above 3000 m is not supported.
Table 6-3 GXTRT-1000IRT2UXL Runtime Table
See Note 1
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6
%VA W Minutes
25 250 225 19 69 129 184 240 291 335
50 500 450 9 38 70 103 139 176 213
69 690 621 5.3 26 48 72 95 120 145
75 750 675 5 10 10 10 10 10 10
80 800 720 3.5 3.5 3.5 3.5 3.5 3.5 3.5
90 900 810 3.5 3.5 3.5 3.5 3.5 3.5 3.5
100 1000 900 3.1 3.5 3.5 3.5 3.5 3.5 3.5
Specifications28
Table 6-4 GXTRT-1500IRT2UXL Runtime Table
See Note 1
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6
%VA W Minutes
25 375 338 21 76 143 203 261 321 380
50 750 675 938.5 72 106 143 180 215
69 1035 932 5.5 26.2 48 72 97 123 150
75 1125 1013 5.2 10 10 10 10 10 10
80 1200 1080 3.5 3.5 3.5 3.5 3.5 3.5 3.5
90 1350 1215 3.5 3.5 3.5 3.5 3.5 3.5 3.5
100 1500 1350 3.2 3.5 3.5 3.5 3.5 3.5 3.5
Table 6-5 GXTRT-2000IRT2UXL Runtime Table
See Note 1
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6
%VA W Minutes
25 500 450 23 85 159 228 300 364 423
50 1000 900 9 39 73 111 151 188 225
69 1380 1242 5.7 27 50 77 104 132 160
75 1500 1350 6 10 10 10 10 10 10
80 1600 1440 3.5 3.5 3.5 3.5 3.5 3.5 3.5
90 1800 1620 3.5 3.5 3.5 3.5 3.5 3.5 3.5
100 2000 1800 3.2 3.5 3.5 3.5 3.5 3.5 3.5
Table 6-6 GXTRT-3000IRT2UXL Runtime Table
See Note 1
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6
%VA W Minutes
25 750 675 26 95 168 242 312 380 443
50 1500 1350 11 42 78 115 155 195 234
69 2070 1863 5.8 28 52 79 107 136 165
75 2250 2025 6 10 10 10 10 10 10
80 2400 2160 3.5 3.5 3.5 3.5 3.5 3.5 3.5
90 2700 2430 3.5 3.5 3.5 3.5 3.5 3.5 3.5
100 3000 2700 3.3 3.5 3.5 3.5 3.5 3.5 3.5
Note 1: When the output load is >80% of full load, the discharge time limit is set to 3.5 min. When the output load is >70%
and <80%, the discharge time limit is set to 10 min. When the output load is <70% load, there is no limit other than battery
capacity.
Vertiv | Liebert® GXT RT+ | Installer/User Guide 29
Appendix I: Technical Support
Our Technical Support sta is ready to assist you with any installation or operating issues you may encounter with
your Liebert® product. Please call or e-mail us:
In Europe, Middle East, and Asia
EMEA Multi-Language Technical support
e: eoc@vertiv.com
p: Toll free 0080011554499
p: Toll +39 02 98250222
In the United States
Technical support
e: liebert.upstech@vertiv.com
p: 1-800-222-5877 menu option 1
Monitoring support
e: liebert.monitoring@vertiv.com
p: 1-800-222-5877 menu option 2
Warranty support
e: microups.warranty@vertiv.com
p: 1-800-222-5877 menu option 3
© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and
logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy
and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any
errors or omissions. Specifications, rebates and other promotional oers are subject to change at Vertiv’s sole discretion upon notice.
SL-28300_REV0_11-19