Table of Contents
- Important Safety Instructions
- 1.0 Introduction
- 2.0 Installation
- 3.0 Enable Communication Protocols
- 4.0 Liebert IntelliSlot Unity Card Web Page Layout
- 5.0 Editing the Liebert IntelliSlot Unity Card Configuration
- 5.1 Communications Tab Folders
- 5.2 Communications—Active Events Folder
- 5.3 Communications—Downloads Folder
- 5.4 Communications—Configuration Folder
- 5.5 Communications—Protocols Folder
- 5.6 Communications—Status Folder
- 5.7 Communications—Support Folder
- 6.0 Firmware Updates
- Appendix A - Configuration Folder— LIFE™ Sub Folder
Vertiv IS-UNITY-DP User Manual
Displayed below is the user manual for IS-UNITY-DP by Vertiv which is a product in the Network Cards category. This manual has pages.
Related Manuals
Liebert® IntelliSlot™ Unity™ Card
User Manual—Web, SNMP, Modbus, BACnet, YDN23
Liebert® IntelliSlot™ Unity™ Card User Manual i
Table of Content
Important Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Compatibility With Other Emerson Products and Communication Protocols . . . . . . . . . . . 4
1.3 Support for Liebert SN Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Installing the Liebert IntelliSlot Unity Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.1 Assigning the Card’s IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.1.1 DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.1.2 Static IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2 Connect an Ethernet Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.3 Connect an RS-485 Serial Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Change User Names and Passwords Immediately. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3 Configure the Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4 Installing Multiple Liebert IntelliSlot Unity Cards in a System . . . . . . . . . . . . . . . . . . . . . . 12
2.5 Security Best Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.0 Enable Communication Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1 Enable Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.1 Enable Modbus Protocol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.1.1 Configure Modbus TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1.1.2 Configure Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.1.2 Enable BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1.2.1 Configure BACnet IP Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.2.2 Configure BACnet MSTP Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.1.3 Enable SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1.3.1 Configure SNMP Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.1.3.1.1 Select SNMPv3 Engine ID Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.1.3.1.2 Configure SNMPv3 User Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1.3.1.3 Configure SNMPv1 Trap Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.3.1.4 Configure SNMPv1/v2c Access Settings . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2 Download Protocol Mappings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
ii Liebert® IntelliSlot™ Unity™ Card User Manual
4.0 Liebert IntelliSlot Unity Card Web Page Layout . . . . . . . . . . . . . . . . . . . 29
4.1 Web Page Sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.2 Help Text. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3 Managed Device Tab Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.4 Communications Tab Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.5 Sensor Tab Menus—Shown Only if a Sensor is Connected. . . . . . . . . . . . . . . . . . . . . . . 35
4.5.1 Sensor Tab Summary Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.5.2 Sensor Tab Summary Page-Details Pane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.6 Changing Sensor Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.0 Editing the Liebert IntelliSlot Unity Card Configuration . . . . . . . . . . . . 39
5.1 Communications Tab Folders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.2 Communications—Active Events Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.3 Communications—Downloads Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.4 Communications—Configuration Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.4.1 Configuration—System Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.4.1.1 Time Service Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.4.2 Configuration—User Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.4.3 Configuration—Network Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.4.3.1 IPv4/IPv6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.4.3.2 Domain Name Server (DNS) Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.4.4 Configuration—Web Server Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.4.4.1 Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.4.4.1.1 Uploading SSL Certificate PEM Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.4.4.1.2 Generating a Self-signed SSL Certificate . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.4.5 Configuration—LIFE™ Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.4.6 Configuration—Emerson Protocol Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.4.7 Configuration—Messaging Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.4.7.1 Email . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.4.7.2 SMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.4.7.3 Messaging Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Liebert® IntelliSlot™ Unity™ Card User Manual iii
5.5 Communications—Protocols Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
5.5.1 Protocols—BACnet Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.5.1.1 BACnet IP Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.5.1.2 BACnet MSTP Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.5.2 Protocols—Modbus Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.5.2.1 Modbus TCP Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.5.2.2 Modbus RTU Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5.5.3 Protocols—SNMP Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5.5.3.1 SNMPv3 User Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5.5.3.2 Editing the SNMPv3 Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.5.3.3 SNMPv1 Trap Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.5.3.4 SNMPv1/v2c Access Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.5.4 Protocols—YDN23 Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.6 Communications—Status Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.7 Communications—Support Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.7.1 Support—Active Networking Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.7.2 Support—Firmware Update Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.0 Firmware Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
6.1 Updating the Liebert IntelliSlot Unity Card’s Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
6.2 Revert to Alternate Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Appendix A - Configuration Folder—LIFE™Sub Folder . . . . . . . . . . . . . . . . 79
iv Liebert® IntelliSlot™ Unity™ Card User Manual
List of Figures
Figure 1-1: Liebert IntelliSlot Unity-DP card features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 2-1: Command prompt access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 2-2: Change administrator and general user names and passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 2-3: Enabling the communication protocol—IPv4 or IPv6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 3-1: Enable protocols; enable commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 3-2: Modbus TCP-Trusted IP List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 3-3: Modbus-RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 3-4: BACnet protocol settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 3-5: BACnet IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 3-6: BACnet MSTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 3-7: SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 3-8: SNMP Engine ID generated using text-format scheme. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 3-9: SNMPv3 user settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 3-10: SNMPv1 trap settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 3-11: SNMPv1/v2c Access settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 4-1: Web page sections, UPS example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 4-2: Web page sections, Thermal Management unit example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 4-3: Managed Device Web page without sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 4-4: Help text on mouse-over . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 4-5: Managed Device tab examples, Liebert GXT4™ and Liebert CRV™. . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 4-6: Sensor tab menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 4-7: Sensor tab-Summary page layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 4-8: Sensor details—Door closure and temperature sensor examples . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 4-9: Changing sensor order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 5-1: Editing configuration settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 5-2: Configuration folder, System subfolder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 5-3: Configuration folder, System subfolder, Time Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 5-4: IPv4/IPv6 settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 5-5: Remote write access disabled indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 5-6: Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 5-7: Upload SSL Key & Certificate PEM Files dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 5-8: Generate Self-Signed SSL Certificate dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 5-9: Edit the SNMPv3 table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Figure 6-1: Ethernet port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Figure 6-2: Firmware update screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
vLiebert
® IntelliSlot™ Unity™ Card User Manual
List of Tables
Table 1-1: Compatibility with Liebert equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 1-2: Liebert IntelliSlot card communication protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2-1: Settings to review and verify
to reduce risk of unauthorized access to critical infrastructure equipment . . . . . . . . . . . . . . . . . . . . . 13
Table 2-2: Ports used by the Unity card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4-1: Help text and icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 4-2: Communications tab menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 4-3: Sensor tab folders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Liebert® IntelliSlot™ Unity™ Card User Manual vi
Page intentionally left blank.
Important Safety Instructions
1Liebert
® IntelliSlot™ Unity™ Card User Manual
Important Safety Instructions
SAVE THESE INSTRUCTIONS
NOTICE
Risk of improper installation. Can cause equipment damage.
Only a qualified service professional should install these products. Emerson recommends having
an Emerson Network Power® Liebert Services representative perform the installation in large
UPS’s. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378).
!
WARNING
Risk of arc flash and electric shock. Can cause injury or death.
Open all local and remote electric power supply disconnect switches, verify with a voltmeter that
power is off and wear personal protective equipment per NFPA 70E before working within the
electric control enclosure. Failure to comply can cause serious injury or death.
!
WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
Open all local and remote electric power supply disconnect switches and verify with a voltmeter
that power is off before working within any electric connection enclosures.
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations and manufacturers’ specifications.
Opening or removing the covers to any equipment may expose personnel to lethal voltages within
the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
Important Safety Instructions
Liebert® IntelliSlot™ Unity™ Card User Manual 2
Page intentionally left blank.
Introduction
3Liebert
® IntelliSlot™ Unity™ Card User Manual
1.0 Introduction
This Liebert IntelliSlot Unity platform delivers enhanced communication and control of AC Power, Power
Distribution and Thermal Management products. The platform communicates with Emerson Network
Power® software tools and services, including Trellis®, LIFE™ Services, Liebert SiteScan Web™ and Liebert
Nform®.
The platform includes the Liebert IntelliSlot Unity-DP™ and Liebert IntelliSlot Unity LIFE™ cards.
Each card employs the Emerson Protocol to monitor and manage a wide range of operating parameters,
alarms and notifications about power, distribution and cooling equipment. The cards also communicate
with Building Management Systems and Network Management Systems. Liebert IntelliSlot Unity cards
support monitoring of sensors to improve system reliability and efficiency.
Figure 1-1 Liebert IntelliSlot Unity-DP card features
1.1 Protocols
Each card supports the Emerson Protocol, Remote Service Delivery Protocol and HTTP Web by default.
The Liebert IntelliSlot Unity-DP supports selecting two third-party protocols; the Liebert IntelliSlot Unity
LIFE card supports the default protocols only (Emerson Protocol, Remote Service Delivery Protocol and
HTTP Web).
Available protocols are
• BACnet IP—BACnet over Internet Protocol
• BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communications protocol over a RS-
485 serial network (also known as BACnet MSTP RS-485)
• Modbus RTU—Modbus Remote Terminal Unit (RTU) communication protocol over a RS-485 serial
network (also known as Modbus RTU RS-485)
• Modbus TCP—Modbus Transmission Control Protocol over Internet Protocol (also known as Modbus
TCP/IP)
•SNMP
• YDN23 - YD-T-1363 specification protocol (also known as YD/T 1363)
Activity
Link 485
IS-UNITY-DP
Liebert Sensor Network
RJ-45-Ethernet—HTTP; Modbus TCP;
BACnet IP; SNMPv1, v2c, v3;
Emerson Protocol
Reset
Button
(Reboot or
reset to
factory
defaults)
BACnet MSTP
Modbus RTU
YDN23
Micro-USB AB
(future release)
Introduction
Liebert® IntelliSlot™ Unity™ Card User Manual 4
1.2 Compatibility With Other Emerson Products
and Communication Protocols
The Liebert IntelliSlot Unity platform includes:
The Liebert IntelliSlot Unity-DP platform supports the following protocols:
The Liebert IntelliSlot Unity platform supports both 10Mbit and 100Mbit communication speeds and either
half or full duplex.
Sensor Support
The Liebert IntelliSlot Unity platform supports these sensors: Liebert SN-2D, Liebert SN-3C, Liebert SN-L,
Liebert SN-T, Liebert SN-TH, Liebert SN-Z01, Liebert SN-Z02 and Liebert SN-Z03.
Password Protection
Control and configuration capabilities are protected by an administrator’s username and password
combination. Optionally, status information can be password-protected. The default user name for the
administrator is Liebert and the default password is also Liebert.
The user name and password can be changed with the Web interface. See 2.2 - Change User Names
and Passwords Immediately for details.
Table 1-1 Compatibility with Liebert equipment
Liebert IntelliSlot Card Compatible with:
Liebert IS-UNITY-DP
Liebert IS-UNITY-LIFE
Alber BDSU-50™
Liebert APM™
Liebert APS™
Liebert Challenger 3000™
Liebert CRV™
Liebert CW™
Liebert DCL™
Liebert DCP™
Liebert Deluxe System/3™
Liebert DS™
Liebert DSE™
Liebert EPM™
Liebert EXC™
Liebert eXL™
Liebert eXM™
Liebert FDC™
Liebert FPC™
Liebert GXT3™
Liebert GXT4™
Liebert HPC™
Liebert HPC-S/M/R/W/Generic™
Liebert HPM™
Liebert NX™ 225-600 kVA
Liebert NXC™
Liebert NXL™ *
Liebert NXR™
Liebert PCW™/PDX™
Liebert PeX™ *
Liebert PPC™
Liebert RDC™
Liebert RX™
Liebert XDC™
Liebert XDP™
Liebert XDP-Cray™
Table 1-2 Liebert IntelliSlot card communication protocols
Liebert IntelliSlot
Card (Part #)
Communication Protocols Available
HTTP
HTTPS
Emerson
Protocol
Remote
Service
Delivery
Protocol Email SMS
SNMP
v1,v2c, v3
BACnet IP
BACnet MSTP
Modbus TCP
Modbus RTU YDN23 *
Liebert IS-UNITY-DP
(IS-UNITY-DP)
Liebert IS-UNITY-LIFE
(IS-UNITY-LIFE)
—— ——
* YDN23 applicable only to Liebert PeX and Liebert NXL.
Introduction
5Liebert
® IntelliSlot™ Unity™ Card User Manual
SNMP Support
The Liebert IntelliSlot Unity card enables SNMP management of Liebert equipment. To integrate the card
into a SNMP implementation, import or compile the Liebert Global Products MIB on the network
management station (NMS).
The Liebert Global Products MIB is available at Liebert’s Web site (www.liebert.com); it supports both
Windows® (192436P1) and Unix (192435P1) file formats.
Web Support
The Liebert IntelliSlot Unity card delivers Web management and control to Liebert equipment over HTTP
and HTTPS. All authorized users on your network will be able to view status information.
Modbus TCP and Modbus RTU Support
The Liebert IntelliSlot Unity card supports Modbus TCP and Modbus RTU for the full range of information
available from the managed device. The Modbus protocol mapping document, SL-28170, is available at
Liebert’s Web site: www.liebert.com
BACnet IP and BACnet MSTP Support
The Liebert IntelliSlot Unity card supports BACnet IP
and BACnet MSTP for the full range of information
available from the managed device. The BACnet
protocol support in the IS_UNITY 6.0 release has
been tested by the BACnet Testing Laboratories
(BTL) and was found in conformance to the BACnet
protocol standards. The BTLCertification listing for the Unity card on the BACnet International website can
be found here. The BACnet protocol mapping document, SL-28170, and the BACnet Protocol
Implementation Conformance Statement (PICS), SL-52647, are available at Liebert’s Web site
(www.liebert.com) as guides to implementing the BACnet protocol.
YDN23 Support
The Liebert IntelliSlot Unity card supports YD/T-1363 specification for the full range of information available
from managed Liebert NXL™ or Liebert PeX™ units.
Trellis™ Support
The Liebert IntelliSlot Unity-DP card communicates a rich set of Emerson Protocol information to the Trellis
DCIM platform.
Trellis can manage and control Liebert equipment using SNMP, Modbus or the Emerson Protocol. This
allows monitoring all Liebert equipment using Liebert IntelliSlot Web, Liebert IntelliSlot 485, Liebert
IntelliSlot IPBML, Liebert IntelliSlot Web ADPT or Liebert IntelliSlot Unity platform communication
interfaces.
Liebert Nform® Support
Utilizing the Emerson Protocol or SNMP and Web technologies built into each Liebert IntelliSlot Unity card,
Liebert Nform will centrally manage alarm notifications to provide an easy interface to access critical
equipment information.
A downloadable version is available online at: nform.liebert.com
Introduction
Liebert® IntelliSlot™ Unity™ Card User Manual 6
Liebert MultiLink® Support
The Liebert IntelliSlot Unity card integrates with Liebert’s MultiLink software to provide unattended,
graceful operating system shutdown of PCs, servers and workstations. The card can be monitored by
Liebert MultiLink over the network, eliminating the need for serial cables.
For more information on Liebert MultiLink and a downloadable version of Liebert MultiLink software, visit
multilink.liebert.com
1.3 Support for Liebert SN Sensors
The Liebert IntelliSlot Unity card supports connection and monitoring up to 10 Liebert SN modular and
integrated sensors. Available sensor types include temperature, humidity, door closure, contact closure
and leak detection. Sensor tab menus permit configuring sensors and putting them in order for easier
checking of high-priority conditions. Sensor data is available via SNMP and the Web user interface.
Installation
7Liebert
® IntelliSlot™ Unity™ Card User Manual
2.0 Installation
NOTICE
Risk of improper installation. Can cause equipment damage.
Only a qualified service professional should install these products. Emerson recommends having
an Emerson Network Power® Liebert Services representative perform the installation in large
UPS’s. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378).
NOTICE
Risk of duplicate node IDs if two or more Liebert IntelliSlot cards are installed. Can cause network
conflicts.
An internal networking conflict may occur within a device when multiple communication cards with
duplicate Node IDs are installed in the device.
Each Liebert IntelliSlot card must have a unique node ID. This will not be a problem if only one
card is installed on your system. Duplicate node IDs are easily averted with the procedure detailed
in 2.4 - Installing Multiple Liebert IntelliSlot Unity Cards in a System.
2.1 Installing the Liebert IntelliSlot Unity Card
The Liebert IntelliSlot Unity card may be installed at the factory or field-installed. To perform a
field-installation:
1. Find the Liebert IntelliSlot bay on your Liebert equipment—It may have a plastic cover.
2. Insert the card into the Liebert IntelliSlot bay.
3. Secure the card with the screws supplied with the cover plate.
!
WARNING
Risk of arc flash and electric shock. Can cause injury or death.
Open all local and remote electric power supply disconnect switches, verify with a voltmeter that
power is off and wear personal protective equipment per NFPA 70E before working within the
electric control enclosure. Failure to comply can cause serious injury or death.
!
WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
Open all local and remote electric power supply disconnect switches and verify with a voltmeter
that power is off before working within any electric connection enclosures.
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations and manufacturers’ specifications.
Opening or removing the covers to any equipment may expose personnel to lethal voltages within
the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
NOTE
The card will only fit one way in the Liebert IntelliSlot bay because the circuit board is not centered
on the faceplate. The slot in the Liebert IntelliSlot bay also is not centered.
Installation
Liebert® IntelliSlot™ Unity™ Card User Manual 8
4. Connect an Ethernet cable to the card’s Ethernet RJ-45 port for IP communication interfaces.
5. Connect a serial cable to the card’s 485 RJ-45 port for RS-485 communication interfaces (see 2.1.3 -
Connect an RS-485 Serial Cable.
2.1.1 Assigning the Card’s IP Address
2.1.1.1 DHCP
The Liebert IntelliSlot Unity card is factory-configured for DHCP. If a Static or BootP network configuration
is required, change the Boot Mode as described in Static IP on page 8. Connect an RJ-45 cable to the
card and it will receive an IP address from the DHCP server. Contact the DHCP administrator to obtain the
IP address using the Liebert IntelliSlot Unity card’s MAC address. The MAC address is printed on the
card’s faceplate.
If the DHCP administrator is not available or there is no way of
determining the IP address assigned by the DHCP server, use a
computer with a direct Ethernet connection to the Liebert IntelliSlot
Unity card, and the Autoconfiguration IPv4 Address convention
described in 2.1.2 - Connect an Ethernet Cable to access the card’s
Web page and configure the card. To see the card’s last DHCP-
assigned IP address, click the Communications tab, then on the left
side menu select Support > Active Networking. The table of
information will show the last IP address assigned by the DHCP
server. The card may retain that IP address when it reconnects to the
DHCP network because most DHCP systems reuse the same IP
address for the same device.
2.1.1.2 Static IP
To assign a static IP address, use the Ethernet connection to configure the card. Proceed to 2.1.2 -
Connect an Ethernet Cable and 2.2 - Change User Names and Passwords Immediately.
Activity
Link 485
IS-UNITY-DP
Last
DHCP
Address
Support>Active
Networking
Communications
Tab
Installation
9Liebert
® IntelliSlot™ Unity™ Card User Manual
2.1.2 Connect an Ethernet Cable
1. Connect a computer running a Microsoft Windows operating system (Microsoft Windows® XP with SP2
[64-bit] or SP3 [32-bit] or later) to the card by plugging a network cable into the RJ-45 port on the
computer and the Liebert IntelliSlot Unity card.
2. Autoconfiguration, which is normally enabled on computers running Microsoft Windows operating
systems, will automatically negotiate the communication settings. This takes about one minute.
3. If the Ethernet adapter being used to attach to the card does not show an Autoconfiguration IPv4
Address, open a new Command Prompt and type ipconfig/renew and press Enter. This forces the
computer to acquire an Autoconfiguration IPv4 Address.
4. When the computer has an Autoconfiguration IPv4 Address, open a browser window on the computer
and type 169.254.24.7 (the card’s default Autoconfiguration IPv4 Address) in the URL address field.
The card’s Web page will appear.
Figure 2-1 Command prompt access
2.1.3 Connect an RS-485 Serial Cable
For Building Management Systems using serial network connections, an RS-485 serial cable connection
will be used.
Liebert IntelliSlot Unity cards come with an Adapter RJ-45-2POS Terminal Block. The adapter has two
screw terminals to attach the ends of a RS-485 cable for communicating to a building management
system.
1. Find the serial cable from the building management system. If it already has an RJ-45 connector on
the end, determine whether it uses the same pin-out as the Liebert IntelliSlot Unity card’s connector. If
the pin-out is the same as the Liebert IntelliSlot Unity card connector’s pin-out, skip to Step 7.
2. Strip the ends of the positive (typically red) and negative (typically black)
leads on the RS-485 cable so that enough bare wire is exposed for
connection, about 1/4” (6mm).
3. Position the adapter so the side with the positive and negative marks is
face up. The small markings are on the same side as the screw heads, as
shown at right.
NOTE
If the computer does not automatically connect, verify that autoconfiguration is enabled by:
Open the Command Prompt window from the computer’s Start menu.
Enter ipconfig/all to verify that Autoconfiguration is enabled on the computer and that an
Autoconfiguration IPv4 Address has been assigned: Enabled = Yes (see Figure 2-1). An
Autoconfiguration IPv4 Address begins with 169.254.)
NOTE
No bare wire should be exposed when the connection is completed.
485
+-
Wires
Screws
Installation
Liebert® IntelliSlot™ Unity™ Card User Manual 10
4. Loosen the screw to the positive terminal and insert the red wire far enough to insert the bare wires
into the terminal block under the screw, then tighten the screw.
5. Be careful not to break the wires.
6. Repeat Step 3 with the negative terminal and the black wire.
7. Plug the cable into the 485 RJ-45 port on the Liebert IntelliSlot Unity card.
2.2 Change User Names and Passwords Immediately
The administrative user name and password are set at the factory: Liebert and Liebert (case-sensitive). All
printable characters are valid except \ : ’ < > ~ ? " #
The general user name and password are also set at the factory: User and User (case-sensitive). The
general user has access only to non-protected configuration and control areas of the Liebert IntelliSlot
Unity card.
To change the user names and passwords:
1. Select the Communications tab > Configuration > User.
2. Click the Edit button and enter the factory-set administrator user name (Liebert) and password
(Liebert).
3. Click OK.
4. Enter a new administrator user name and password.
5. Re-enter the administrator password to confirm it.
6. Enter a new general user name and password.
NOTE
Emerson recommends changing the administrative and general user names
and passwords immediately to safeguard protected configuration and control
areas of the Liebert IntelliSlot Unity card.
Installation
11 Liebert® IntelliSlot™ Unity™ Card User Manual
7. Re-enter the general user’s password to confirm it.
8. Click Save button to confirm the changes or Cancel to discard them.
Figure 2-2 Change administrator and general user names and passwords
2.3 Configure the Card
The Liebert IntelliSlot Unity card requires minor configuration, such as choosing the IP/Web
communication interface, serial RS-485 communication interface, or both. The default for IP/Web
communication is IPv4, but this can be changed to IPv6 for greater security; contact your network
administrator to determine whether it is compatible with your network. To choose the communication
interface refer to Figure 2-3:
1. Select Communications tab > Configuration > Network.
2. Enable the protocol, either IPv4 or IPv6, that will be used to communicate with the Liebert IntelliSlot
Unity card and with the Liebert equipment.
a. Click either IPv4 or IPv6.
b. Click Edit.
c. When prompted with a login display, enter the user name and password (the defaults are Liebert
and Liebert).
d. Click to check enabled.
e. Enter the desired or assigned IP address along with the rest of the required networking
information. Contact your system administrator if necessary.
NOTE
Record the new user names and passwords and save them in a secure place where they can be
found if forgotten.
A lost password cannot be retrieved. If the password is lost, the card must be reset to factory
defaults and reconfigured.
Administrator User
Name and Password
General User Name
and Password
Installation
Liebert® IntelliSlot™ Unity™ Card User Manual 12
3. Click Save to confirm the changes or Cancel to discard them.
The changes take effect after the card is restarted.
Figure 2-3 Enabling the communication protocol—IPv4 or IPv6
2.4 Installing Multiple Liebert IntelliSlot Unity Cards in a System
More than one Liebert IntelliSlot card may be installed in a system, but circular routes and duplicate node
IDs must be avoided during installation. The instructions below apply if the second card to be installed is a
Liebert IntelliSlot Unity card. If the second card is not a Liebert IntelliSlot Unity card, follow instructions in
the user manual for that card.
Before beginning installation of a second Liebert IntelliSlot card, verify that the first card functions properly.
If the first card is a Liebert IntelliSlot card, but not a Liebert IntelliSlot Unity card, and if both cards connect
to the same Ethernet network, then you should disable the router function on the first card. This will avoid
circular routes. Follow instructions in the user manual for the first card.
If the first and second cards are both Liebert IntelliSlot Unity cards, steps must be taken to avoid duplicate
Emerson Protocol MSTP node IDs. By default, the two cards would use the same node ID, and one or both
cards would report a duplicate node error and fail to communicate with the system.
The default node ID for a Liebert IntelliSlot Unity card is 0, so the second card should use 1 or 2 preferably,
or 127 if necessary. Contact your system administrator about the proper node ID for the second card, then
perform the steps below.
1. Open a Web browser and navigate to the second Liebert IntelliSlot Unity card.
2. Click Communications tab > Configuration > Emerson Protocol > MSTP.
3. Click Edit and enter a password and username if required.
4. Enter the new node ID.
5. Click Save to confirm the changes or Cancel to discard them.
6. Restart the card:
a. Select the Communications tab > Support.
b. Click Enable.
c. Click Restart.
IPv4
Settings
Shown
Edit Dialog Box
Enter the Administrator Name and Password;
defaults are Liebert and Liebert
These should have been changed to enhance
security; see 2.2 - Change User Names and
Passwords Immediately
Edit Button Save and Cancel Buttons
Installation
13 Liebert® IntelliSlot™ Unity™ Card User Manual
2.5 Security Best Practices
The default settings on the Unity card support a fast installation and start-up to get basic communication
services up and running quickly. Proper security of critical infrastructure equipment requires proper
configuration of ALL communication services. This section summarizes the settings to examine to reduce
the risk of unauthorized access to critical infrastructure equipment through a Unity card.
Table 2-1 provides a list of items to review. Each should be reviewed, configured based on the operational
needs for managing the equipment, and verified that the settings support the desired operational
functionality without adding unnecessary or unauthorized access to critical infrastructure equipment. A
reference to the proper section in this document is provided for configuring each item.
Table 2-1 Settings to review and verify to reduce risk of unauthorized access
to critical infrastructure equipment
Item Description Reference
Accounts & Passwords
Change the admin and user account names
and passwords immediately to eliminate
default credential access.
2.2 - Change User Names and
Passwords Immediately
IP Network Access
Enable/disable IPV4 and IPV6 network
access to the Unity Card - disable unused
network access.
2.3 - Configure the Card
Telnet and SSH Access
Enable/disable telnet and SSH access for
diagnostic and configuration support - disable
when not in use.
5.4.3 - Configuration—Network Folder
Web Service Protocol
Select HTTPS to use SSL encryption when
accessing data through the web user
interface.
5.4.4 - Configuration—Web Server
Folder
SSL Certificates
When using HTTPS, install your own SSL
Certificates from a trusted certificate authority
or generate alternative self-signed certificates
5.4.4.1 - Certificate
Password Protect Web Access Enable to require users to login before any
device information is displayed to the user.
5.4.4 - Configuration—Web Server
Folder
Remote Write Web Access
Disable to require all updates to the device
and card be made through a local interface,
via an Autoconfiguration connection with a
PC directly connected to the Unity card or
through the device's local user interface
display (if available).
WARNING! - Only disable this if you are
absolutely sure that you do not need to
administer the managed device or the Unity
card through a remote web browser session.
5.4.4 - Configuration—Web Server
Folder
Communication Protocols
Enable/disable BACnet, Modbus, SNMP, and
YDN23 protocols - disable any that are
unused.
3.0 - Enable Communication Protocols
BACnet Settings
Set Managed Device Write Access to Read-
Only to prevent changes to the device
through the BACnet interface.
3.1.2 - Enable BACnet Protocol
Modbus Settings
Set Managed Device Write Access to Read-
Only to prevent changes to the device
through the Modbus interface; Select the
appropriate option for Limit Network Access
Type to restrict which systems may request
Modbus data from the device - access may
be open to any system, limited to those on
the same subnet as the device, or limited to
only those from systems on a Trusted IP
Address List.
3.1.1 - Enable Modbus Protocol
Installation
Liebert® IntelliSlot™ Unity™ Card User Manual 14
For added security, the local network firewall and gateway may be restricted to allow only the necessary
traffic on the required network ports. The ports used by the Unity card are listed in Table 2-2. Some port
settings may be changed by the administrator.
Details for configuration of all options are provided in the remainder of this User Manual.
SNMP Version Settings
Enable/disable the desired SNMP version(s);
Consider using SNMPv3 with user
authentication and encryption.
3.1.3.1 - Configure SNMP Settings
SNMP Access Table Settings
For each SNMPv1/v2c Access table entry,
set the SNMP Access Type to Read-Only to
prevent changes to the device from the hosts
identified in the table entry.
3.1.3.1.4 - Configure SNMPv1/v2c
Access Settings
SNMP Community Strings Change the SNMP v1/v2c Trap and Access
Community Strings from their default values.
3.1.3.1.3 - Configure SNMPv1 Trap
Settings
and
3.1.3.1.4 - Configure SNMPv1/v2c
Access Settings
SNMPv3 Settings
Use the SNMPv3 Authentication and Privacy
settings to make SNMPv3 communications
more secure.
3.1.3.1.2 - Configure SNMPv3 User
Settings
YDN23 Settings
Set Managed Device Write Access to Read-
Only to prevent changes to the device
through the YDN23 interface.
5.5.4 - Protocols—YDN23 Folder
Emerson Protocol Settings
Enable/disable the Emerson Protocol which
is used by Emerson Network Power
management applications for accessing
device data.
5.4.6 - Configuration—Emerson
Protocol Folder
Table 2-2 Ports used by the Unity card
Network Service Port Used Default? Can be Modified?
Web HTTP TCP 80 Yes Yes
HTTPS TCP 443 Yes Yes
DNS TCP & UDP 53 Yes No
NTP TCP & UDP 123 Yes No
SMTP TCP 25 Yes Yes
SSH TCP & UDP 22 Yes No
Telnet TCP 23 Yes No
SNMP UDP 161, 162 Yes Only trap port 162 may be changed
Modbus TCP TCP 502 Yes Yes
BACnet IP UDP 47808 Yes Yes
Emerson Protocol UDP 47808 Yes Yes
LIFE TCP 80 Yes Yes
Table 2-1 Settings to review and verify to reduce risk of unauthorized access
to critical infrastructure equipment (continued)
Item Description Reference
Enable Communication Protocols
15 Liebert® IntelliSlot™ Unity™ Card User Manual
3.0 Enable Communication Protocols
The Liebert IntelliSlot Unity card will communicate with equipment and third-party systems over these
protocols:
• BACnet IP
• BACnet MSTP
• Modbus TCP
• Modbus RTU
•SNMP
• YDN23
3.1 Enable Protocols
Protocols may be enabled after a card has been installed and configured. After a protocol is enabled, it
must be configured, which requires opening that protocol’s folder (Communications tab > Protocols >
(desired protocol).
To enable two communication protocols:
1. Select Communications tab > Protocols.
2. Click Edit and enter the administrator user name and password.
3. Put a check mark next to the protocols to use—Only two may be enabled; only one of the two can use
the 485 port.
4. Click Save to confirm the changes or Cancel to discard them.
NOTE
No more than two protocols may be enabled on one card.
• Only one version of BACnet may be selected, either BACnet IP or BACnet MSTP
• Only one version of Modbus may be selected, either Modbus TCP or Modbus RTU
• Only one of the protocols can use the 485 port; choosing two 485 protocols will cause conflicts.
NOTE
Some Building Management Systems can be configured to send continuous updates for device
setpoints, usually setting the same value. The BMS should be configured to send, on a sustained
average, no more than two writes per second to the device. This will allow the device to catch up
after a burst of updates when required while allowing other communication with the device to
proceed.
Enable Communication Protocols
Liebert® IntelliSlot™ Unity™ Card User Manual 16
5. Configure the protocols selected. See 5.0 - Editing the Liebert IntelliSlot Unity Card Configuration.
6. Restart the card (See 5.7 - Communications—Support Folder).
a. Select Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-1 Enable protocols; enable commands
3.1.1 Enable Modbus Protocol
Protocols may be enabled after a card has been installed and configured.
1. Select Communications tab > Protocols > Modbus.
2. Click Edit and enter a User name and password.
3. Select the access level (Read Only or Read/Write).
4. Select the Modbus interface, (Modbus TCP or Modbus RTU).
5. Click Save to confirm the changes or Cancel to discard them.
6. Configure the Modbus interface chosen.
See 3.1.1.1 - Configure Modbus TCP or 3.1.1.2 - Configure Modbus RTU.
For descriptions of the settings, see 5.5.2 - Protocols—Modbus Folder.
Enable Two
Protocols
Enable Commands
(Communications
Tab>Support Folder)
Enable Communication Protocols
17 Liebert® IntelliSlot™ Unity™ Card User Manual
3.1.1.1 Configure Modbus TCP
1. Select the Communications tab > Protocols > Modbus TCP.
2. Click Edit and enter a User name and password if required.
3. Set the Limit Network Access Type by choosing from the drop-down list
(Open/Same Subnet/Trusted IP List).
Refer to 5.5.2.1 - Modbus TCP Folder for additional details.
4. Enter the Port to be used by the Modbus Server to listen for and respond to Modbus protocol requests
based on limit Network Access Type setting.
5. Enter the Maximum Client Connection Count.
6. Click Save to confirm the changes or Cancel to discard them.
7. Restart the card to confirm the changes.
a. Select Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-2 Modbus TCP-Trusted IP List
... brings up a screen
where this information
may be entered.
Clicking on
one of the five
Trusted IP
List folders...
Enable Communication Protocols
Liebert® IntelliSlot™ Unity™ Card User Manual 18
3.1.1.2 Configure Modbus RTU
1. Select the Communications tab > Protocols > Modbus RTU.
2. Click Edit and enter a user name and password if required.
3. Set the Node ID and the Baud Rate.
• The Node ID defaults to 1, but must have a value from 1 to 255 that is unique among devices
connected through the RS-485 interface.
• The default baud rate is 9600; 19200 and 38400 are also available.
For additional description of the settings, see 5.5.2.2 - Modbus RTU Folder.
4. Click Save to confirm the changes or Cancel to discard them.
5. Restart the card to confirm the changes.
a. Select Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-3 Modbus-RS-485
NOTE
Contact your system administrator if you are uncertain about the settings.
Node ID must
be unique on
the RS-485 bus
this card is
connected to.
Enable Communication Protocols
19 Liebert® IntelliSlot™ Unity™ Card User Manual
3.1.2 Enable BACnet Protocol
1. Select Communications tab > Protocols > BACnet.
2. Click Edit and enter a user name and password if required.
3. Enter the Managed Device Write Access level (Read Only or Read/Write).
This determines a user’s ability to change settings in the Liebert IntelliSlot Unity card.
4. Choose the BACnet interface: BACnet IP or BACnet MSTP.
5. Set the Device Object Instance Number.
6. Set the Device Object Name.
7. Set the APDU Timeout.
8. Set the APDU Retries.
9. Click Save to confirm the changes or Cancel to discard them.
10. Configure the BACnet interface chosen, see 3.1.2.1 - Configure BACnet IP Protocol or 3.1.2.2 -
Configure BACnet MSTP Protocol.
For description of the settings, see 5.5.1 - Protocols—BACnet Folder.
Figure 3-4 BACnet protocol settings
NOTE
Contact your system administrator or building management system administrator if you are
uncertain about the settings.
Enable Communication Protocols
Liebert® IntelliSlot™ Unity™ Card User Manual 20
3.1.2.1 Configure BACnet IP Protocol
1. Select Communications tab > Protocols > BACnet IP.
2. Click Edit and enter a User name and password if required.
3. Set the BACnetIP/Port Number.
If the Liebert IntelliSlot Unity card is on a different subnet (a possibility when the monitored units are
part of a Liebert SiteScan network or other third-party monitoring service):
a. Choose whether or not to enable Register as Foreign Device.
b. Enter the IP address of the BBMD (BACnet Broadcast Management Device).
c. Enter a time in seconds for Foreign Device Time-to-Live.
For descriptions of the settings, see 5.5.1.1 - BACnet IP Folder.
4. Click Save to confirm the changes or Cancel to discard them.
5. Restart the card to activate the changes.
a. Select the Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-5 BACnet IP
NOTE
Contact your system administrator if you are uncertain about the settings.
Enable Communication Protocols
21 Liebert® IntelliSlot™ Unity™ Card User Manual
3.1.2.2 Configure BACnet MSTP Protocol
1. Select Communications tab > Protocols > BACnet MSTP.
2. Click Edit and enter a user name and password if required.
3. Set the BACnet MSTP Node ID.
• The Node ID defaults to 1, but must have a value from 1 to 255 that is unique among devices
connected through the RS-485 interface.
4. Set the BACnet MSTP Data Rate.
5. Set the BACnet MSTP Max Master Address.
6. Set the BACnet MSTP Max Info Frames.
For descriptions of the settings, see 5.5.1.2 - BACnet MSTP Folder.
7. Click Save to confirm the changes or Cancel to discard them.
8. Restart the card to activate the changes.
a. Select Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-6 BACnet MSTP
NOTE
Contact your system administrator if you are uncertain about the settings.
Node ID must
be unique on
the RS-485 bus
this card is
connected to.
Enable Communication Protocols
Liebert® IntelliSlot™ Unity™ Card User Manual 22
3.1.3 Enable SNMP
SNMPv1/v2c and SNMPv3 are enabled by default. The protocols may be configured or their default values
may be accepted. Authentication Traps are not enabled by default. The default Heartbeat Trap interval is
24 hours; this can be disabled or the interval may be changed.
1. Select the Communications tab > Protocols > SNMP.
2. Click Edit and enter a User name and password if required.
3. To enable Authentication Traps, click to check mark the box.
4. To change the Heartbeat Trap Interval, choose a time from the drop-down list or choose Disabled to
prevent any heartbeat traps from being sent.
• The interval times offered are 5 minutes, 30 minutes, or 1, 4, 8, 12 or 24 hours.
5. For each trap, choose whether or not to disable or set the interval to one of the periods on the menu.
For descriptions of the settings, refer to 5.5.3 - Protocols—SNMP Folder.
6. Click Save to confirm the changes or Cancel to discard them.
7. Restart the card to activate the changes.
a. Select the Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-7 SNMP
Enable Communication Protocols
23 Liebert® IntelliSlot™ Unity™ Card User Manual
3.1.3.1 Configure SNMP Settings
SNMPv3 Users or SNMPv1/v2c Trap and Access settings must be made before SNMP access or
notifications can occur. The Liebert IntelliSlot Unity card permits up to 20 SNMPv3 Users, up to 20
SNMPv1 Trap targets, and up to 20 SNMPv1/v2c Access addresses.
The required changes vary according to the type of SNMP protocol used:
• SNMPv1 must have trap settings.
• SNMPv2c must have Access settings.
• SMPv3 users must have settings configured and the method for generating the Engine ID may be
selected.
• the access settings for SNMPv1/v2c are separate from SNMPv1 trap settings.
3.1.3.1.1 Select SNMPv3 Engine ID Format
By default, the Engine ID is automatically generated using the MAC address. Optionally, you can select a
text-based ID instead.
1. Select Communications tab > Protocols > SNMP.
2. Click Edit and enter a User name and password if required.
3. Edit the settings:
Refer to 5.5.3, Protocols—SNMP Folder, page 60, for descriptions of the settings and options.
•In SNMPv3 Engine ID Format Type, select MAC Address or Text.
• If you selected Text, type the text on which the generated engine ID will be based.
• Click Save to confirm the changes, or click on Cancel to discard them.
The new engine ID is not displayed until after rebooting the card in Step 4.
The text-generated engine ID is a hexadecimal representation of ASCII characters similar to that
shown in Figure 3-8.
Figure 3-8 SNMP Engine ID generated using text-format scheme
4. Restart the card to activate the changes.
a. Select the Communications tab > Support.
b. Enable the commands.
c. Click Restart.
NOTE
If the format type or text for the Engine ID are incomplete or invalid, the Engine ID is generated
based on the MAC Address.
Enable Communication Protocols
Liebert® IntelliSlot™ Unity™ Card User Manual 24
3.1.3.1.2 Configure SNMPv3 User Settings
The settings must be made for each user who will receive notifications.
1. Select Communications tab > Protocols > SNMP > SNMPv3 Users Setting (20) >
SNMPv3 Users Setting (1).
2. Click Edit and enter a User name and password if required.
3. Enter the information and set the permissions appropriate to the user, Figure 3-9.
For descriptions of the settings and options, see 5.5.3.1, SNMPv3 User Folder, page 62.
4. Click Save to confirm the changes, or click on Cancel to discard them.
5. Repeat Steps 1 through 4 for additional users.
6. Restart the card to activate the changes.
a. Select the Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-9 SNMPv3 user settings
Settings are
required for
each user
Enable Communication Protocols
25 Liebert® IntelliSlot™ Unity™ Card User Manual
3.1.3.1.3 Configure SNMPv1 Trap Settings
1. Select Communications tab > Protocols > SNMP > SNMPv1 Trap (20).
2. Click Edit and enter a User name and password if required.
3. Enter the information and set the permissions appropriate to the user, Figure 3-10.
For descriptions of the settings, see 5.5.3.3 - SNMPv1 Trap Folder.
4. Click Save to confirm the changes or Cancel to discard them.
5. Repeat Steps 1 through 4 for any additional users.
6. Restart the card to confirm the changes.
a. Select the Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-10 SNMPv1 trap settings
Settings required
for each address
that will receive
SNMP notifications.
Enable Communication Protocols
Liebert® IntelliSlot™ Unity™ Card User Manual 26
3.1.3.1.4 Configure SNMPv1/v2c Access Settings
1. Select Communications tab > Protocols > SNMP > SNMPv1/v2c Access (20)
>SNMPv1/v2c Access (1).
2. Click Edit and enter a User name and password if required.
3. Enter the information and set the permissions appropriate to the user, Figure 3-10.
For description of the settings and options, see 5.5.3.4, SNMPv1/v2c Access Folder, page 66.
4. Click Save to confirm the changes or Cancel to discard them.
5. Restart the card to confirm the changes.
The card must be restarted before another user’s settings may be changed.
a. Select the Communications tab > Support.
b. Enable the commands.
c. Click Restart.
Figure 3-11 SNMPv1/v2c Access settings
Selecting the SNMPv1/v2c Access
folder will bring up the settings
that may be changed.
Enable Communication Protocols
27 Liebert® IntelliSlot™ Unity™ Card User Manual
3.2 Download Protocol Mappings
The Liebert IntelliSlot Unity Card’s permits downloading files listing information available from a managed
device for each enabled protocol. The listings identify the data available from the device and how that data
will be represented, or mapped, into a particular protocol.
To download a data mapping list, click the Managed Device tab, then Summary > Downloads. The Data
Mapping Files heading shows mapping files for each enabled protocol:
•BACnetDataMap.txt for BACnet IP and BACnet MSTP
•ModbusDataMap.txt for Modbus TCP and Modbus RTU
•SNMP_Events.txt, SNMP_Parameters.txt, SNMP_upsMibEvents.txt, and SNMP_upsParams.txt for
SNMP v1/v2c/v3
•Ydn23DataMap.txt for YDN23
More information about BACnet and Modbus protocol mapping is available in the Liebert IntelliSlot Modbus
RTU, Modbus TCP, BACnet MSTP and BACnet IP Reference Guide (SL-28170) at Liebert’s Web site:
www.liebert.com
The SNMP MIB files are also available for download from the Web site.
Enable Communication Protocols
Liebert® IntelliSlot™ Unity™ Card User Manual 28
Page intentionally left blank.
Liebert IntelliSlot Unity Card Web Page Layout
29 Liebert® IntelliSlot™ Unity™ Card User Manual
4.0 Liebert IntelliSlot Unity Card Web Page Layout
Default settings in the Liebert IntelliSlot Unity card permit using it immediately after installation to monitor
the equipment the card is installed in. The Web interface permits customizing the information to ease
monitoring the equipment and troubleshooting problems. Users can name the equipment, enter a location,
set up email and text alerts and change equipment settings.
4.1 Web Page Sections
Each Web page displayed by the Liebert IntelliSlot Unity card has these main areas (see Figure 4-1):
• Identification
• Status
• Tab Menus
• Detail
Identification
Displays the System Name, System Location and System Description
Status
Displays the status of the monitored equipment, the Liebert IntelliSlot Unity card and any Liebert SN
sensors connected to the card.
Tab Menus
The Liebert IntelliSlot Unity card has two tabs by default: the Managed Device tab, which will display the
name of the monitored equipment, and the Communications tab. A third tab, the Sensor tab, appears if
Liebert SN sensors have been installed. The tab selected determines the menu shown.
•Managed Device tab—Information pertaining to the equipment being monitored and controlled. Refer
to 4.3 - Managed Device Tab Menus for details. The tab label refers to the type of Liebert unit the
card is installed in. For example, the Managed Device tab for a card installed in a Liebert GXT4-1000-
RT120 UPS will be labeled GXT4-1000-RT120 (see Figure 4-1 for this example). Figure 4-2 shows a
Web page for a Liebert IntelliSlot Unity card installed in a Liebert CRV.
•Communications tab—Information about the Liebert IntelliSlot Unity card, such as the overall event
status of the equipment and communication interface, logs of third-party information, communication
settings, third-party protocol settings and system status. Refer to 4.4 - Communications Tab Menus
for details.
•Sensor tab—Information about Liebert SN sensors, if any are installed, including status or data from
each sensor and sensor configuration settings. When sensors are connected to the card, this tab
appears between the Managed Device tab and the Communications tab. The tab is not shown when
no sensors are connected to the card (see Figure 4-3). Refer to 4.5 - Sensor Tab Menus—Shown
Only if a Sensor is Connected for details.
NOTE
The Edit button will be grayed-out if the settings on a menu cannot be changed.
Liebert IntelliSlot Unity Card Web Page Layout
Liebert® IntelliSlot™ Unity™ Card User Manual 30
Detail
Displays detailed information about the device based on the menu selection made in the Tab Menu area.
Edits to the device and its configuration are made in this section.
Figure 4-1 Web page sections, UPS example
Figure 4-2 Web page sections, Thermal Management unit example
Identification
Status
(Status of
equipment,
sensors, if any
are installed, and
communications)
Tab Menu
(changes
according to
monitored
equipment)
Communications Tab
Managed Device Tab
Card in a Liebert GXT4™
Information on the
Opening Screen
depends on type of unit
being monitored.
Sensor Tab
Identification
Status
Tab Menu
(changes
according to
monitored
equipment)
Information on
Opening Screen
depends on type of
unit being monitored
Communications Tab
Managed Device Tab
Card in a Liebert CRV™
Sensor Tab
Liebert IntelliSlot Unity Card Web Page Layout
31 Liebert® IntelliSlot™ Unity™ Card User Manual
Figure 4-3 Managed Device Web page without sensors
4.2 Help Text
Each Web page shown by the Liebert IntelliSlot Unity-DP card has informational text that is revealed by
hovering a mouse pointer over the icon to the left of the Status, Events or Settings row, as shown below.
The Web page may display any of six icons beside the Status, Events or Setting entry:
Table 4-1 Help text and icons
Icon Description
a check mark (?
) on a green button (Event Normal)
an i on a blue button (Event Information)
an x on a red button (Event Alarm)
an exclamation point (!) on a yellow shield (Event Warning)
an exclamation point (!) on a red button (Event Critical)
an i in a word balloon (Tool Tip).
Sensor Status
not displayed
Sensor Tab
not displayed
i
x
!
!
i
Liebert IntelliSlot Unity Card Web Page Layout
Liebert® IntelliSlot™ Unity™ Card User Manual 32
Figure 4-4 Help text on mouse-over
Hovering a mouse
pointer over the icon
reveals information
about that entry.
Help text about the
System Input Nominal
Frequency entry on the
Managed Device Tab,
Input Menu.
Liebert IntelliSlot Unity Card Web Page Layout
33 Liebert® IntelliSlot™ Unity™ Card User Manual
4.3 Managed Device Tab Menus
Menus on the Managed Device tab list only data that is relevant to the equipment being monitored. For
example, menus shown by a Liebert IntelliSlot Unity card installed in a UPS differ from menus shown by a
card installed in Thermal Management equipment. Information on those menus will also differ depending
on the equipment the card is installed in.
Figure 4-5 Managed Device tab examples, Liebert GXT4™ and Liebert CRV™
The Managed Device Tab will
display Status or Events for
the applicable equipment
only. Power information is
shown in this Managed
Device Tab for a UPS.
The Managed Device Tab will
display Status, Events or
Settings for the applicable
equipment only.
Environmental information is
shown in this Managed
Device Tab for Thermal
Management equipment.
Liebert IntelliSlot Unity Card Web Page Layout
Liebert® IntelliSlot™ Unity™ Card User Manual 34
4.4 Communications Tab Menus
The Communications tab shows the overall event status of the equipment and communication interface. It
contains logs of third party information, communications settings, third party protocol settings and system
status information as detailed below.
Table 4-2 Communications tab menus
Communications tab Menus Description See Details:
Active Events Displays the current event activity page 40
Downloads
Agent (or Unity Card) Logs
Event Logs
Data Logs
Other files
Downloading files to text-accessible, comma-delimited or
tab-delimited files ease troubleshooting. page 40
Configuration
System
User
Network
Web Server
LIFE
Emerson Protocol
Messaging
Displays information about the system setup, access,
network connections, Emerson Protocol settings and
whether email and SMS messaging are enabled
page 40
Protocols
Modbus
BACnet
SNMP
YDN23
Lists information and settings related to available
third-party protocols employed to monitor equipment. page 56
Status
System Status
System Restart Required
LIFE™ device identity changed-LIFE™ needs to be reconfigured
RS-485 Port Conflict
Duplicate Emerson Protocol MSTP Node ID
Duplicate BACnet MSTP Node ID
Shows the overall condition of the system and whether a
restart is needed to activate configuration changes; restart
is performed only from the Support Folder
page 68
Support
Agent time and Date
Agent Model
Agent App Firmware Version
Agent App Firmware Label
Agent Boot Firmware Version
Agent Boot Firmware Label
Agent Serial Number
Agent Manufacture Date
Agent Hardware Version
GDD Version
FDM Version
Product Sequence ID
Restart Card
Reset Card to Factory Defaults
(see Note below)
Generate and download diagnostic file
Firmware Update
Active Networking
Shows information needed for maintenance or
troubleshooting and shortcuts to reboot the card, reset the
Liebert IntelliSlot Unity card to its factory defaults and to
update the card’s firmware.
page 69
(Firmware
Update also
on page 75)
NOTE
The card may be reset to factory defaults manually by briefly pressing the reset button five times
within 10 seconds.
Do not hold the reset button too long: Pressing the reset button and holding it for 5 seconds will
restart the card without resetting it to factory defaults.
To perform either function, insert a straight, non-conductive tool into the small hole on the front of
the card (see Figure 1-1 for the Reset Button’s location).
Liebert IntelliSlot Unity Card Web Page Layout
35 Liebert® IntelliSlot™ Unity™ Card User Manual
4.5 Sensor Tab Menus—Shown Only if a Sensor is Connected
When Liebert SN sensors are installed and connected to the sensor port on the Liebert IntelliSlot Unity
card, the Sensor tab appears. It contains folders showing an overview of the installed sensors, the event
status of the sensors, download links for log files and sensor configuration settings as detailed below.
Figure 4-6 Sensor tab menu
Table 4-3 Sensor tab folders
Sensor Tab Menus Description
Summary Displays a list of currently discovered sensors, with their status and values.
Also displays a detail section about the sensor that is currently selected
Active Events Displays a list of sensor events that are currently active.
Downloads Displays a list of text files that can be downloaded. The files available are
dependent on the current state of the card.
Sensor Server
System Model Number
System Status
Too Many Sensors
Slots Not Available
Acknowledge Sensor Changes
Displays overall information about the sensors.
Sensor Change Lists events showing sensors that have been added or removed. If the list has
any entries, an Acknowledge button appears. Clicking the Acknowledge
button clears the list. The Acknowledge button on this page has the same
behavior as the Acknowledge button on the Sensor Server page.
Sensor Order Displays a list of sensors, and allows setting the order in which the sensors
are displayed on the Summary page.
Graphs show
sensor
measurements
in relation to
thresholds for
temperature
and humidity.
Icons for door
closure and
contact closure
sensors. The
lower sensor
shows the door
is open.
Actual sensor values
Labels may be assigned to
sensors to aid in monitoring,
such as adding its location
Liebert IntelliSlot Unity Card Web Page Layout
Liebert® IntelliSlot™ Unity™ Card User Manual 36
4.5.1 Sensor Tab Summary Page
The Sensor tab Summary Page shows the status of all installed sensors, details about any selected sensor
and a Setting pane that permits changing a sensor’s label, thresholds if applicable, alarm configuration and
acknowledging alarms and events.
Selecting a sensor permits changing its settings at the lower part of the window.
Events may also be acknowledged on this window.
Figure 4-7 Sensor tab-Summary page layout
4.5.2 Sensor Tab Summary Page-Details Pane
The Details pane of the Sensor tab window appears when the Summary folder is selected. The area shows
the status of all connected sensors (see Figure 4-7).
Supported sensors include:
• Temperature
• Humidity
• Door Closure
• Contact Closure
• Leak Detection
Temperature
sensor selected
Details about
the selected
sensor; the
value will match
the value in the
Summary pane
Selected sensor’s
settings; click Edit
to change a value;
requires password
Graphical
display of
temperature
sensor value
Door Closure
status icons
One open,
One closed
Liebert IntelliSlot Unity Card Web Page Layout
37 Liebert® IntelliSlot™ Unity™ Card User Manual
Selecting a sensor displays details for that sensor. The content of the details section is specific to the type
of sensor selected. For example, a temperature sensor would show the temperature of the area where it is
installed and a door sensor would show whether the door is open. The Unit of Measure used to display the
temperature values is defined in the Display Temperature Units setting under Communications tab >
Configuration > System. See 5.4.1 - Configuration—System Folder.
Details for the sensors include the current state or reading, event status and whether the reading is above
or below the threshold established in the Settings pane.
Figure 4-8 Sensor details—Door closure and temperature sensor examples
Click Edit in the
Settings pane to
change a value
Editing a Door Closure Sensor
A label indicating the sensor’s location
can be added. The alarm configuration
offers a drop-down menu to choose when
an alarm will be activated.
Liebert IntelliSlot Unity Card Web Page Layout
Liebert® IntelliSlot™ Unity™ Card User Manual 38
4.6 Changing Sensor Order
Sensors are listed in the order they are installed. The order can be changed to put sensors deemed more
important at the top of the list.
To change the order of the sensor list:
1. Click Sensor tab > Sensor Order.
2. Click Edit.
3. Enter the user name and password.
4. Select the sensor to be moved higher or lower in the list.
The radio button beside the sensor to be changed is highlighted.
5. Use the arrows at the right side of the list to move the sensor up or down.
6. Click Save.
Repeat the steps for any other sensors to be moved higher or lower in the list.
Figure 4-9 Changing sensor order
This arrow
moves the
selected
sensor higher
in the list.
This arrow
moves the
selected
sensor lower
in the list.
Click on a radio button to
select a sensor to move up
or down the list.
Editing the Liebert IntelliSlot Unity Card Configuration
39 Liebert® IntelliSlot™ Unity™ Card User Manual
5.0 Editing the
Liebert IntelliSlot Unity Card Configuration
The Web-based interface can be used to change settings for the Liebert IntelliSlot Unity card and for the
monitored equipment. The following steps apply to making changes in all sections of the Liebert IntelliSlot
Unity card.
To edit the configuration:
1. Open a Web browser and enter the card’s IP address.
2. Click the Communications tab.
3. Select the menu in the Tab Menu area, Figure 5-1, that contains the configuration setting to be
changed.
4. Click the Edit button near the top of the page.
5. Enter the administrator name and password for the Liebert IntelliSlot Unity card in the dialog box that
opens (the default settings are Liebert and Liebert).
6. Click OK.
7. Change the settings.
8. Click Save to apply the changes or Cancel to discard them.
Figure 5-1 Editing configuration settings
Select Communications Tab
Tab Menu
containing the
setting to be
changed
Edit
Button
Enter Password
Dialog Box (from
clicking on Edit)
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 40
5.1 Communications Tab Folders
The Communications tab of the web-based interface contains information
about the overall event status of the equipment and communication interface.
It presents logs of third-party information, communication settings, third-party
protocol settings and system status information.
The Communications tab folders are shown at right.
5.2 Communications—Active Events Folder
The Communications tab’s Active Events folder contains no configurable settings. The folder displays
events affecting the Liebert IntelliSlot Unity card.
5.3 Communications—Downloads Folder
The Communications tab’s Downloads folder contains no configurable settings. The folder displays links to
download logs of third-party protocols that are enabled on the Liebert IntelliSlot Unity card. The logs help in
configuring and troubleshooting communication between the Network Management or Building
Management Systems being used to monitor the managed device.
5.4 Communications—Configuration Folder
The Configuration folder’s top level displays the System Model Name of the
Liebert IntelliSlot Unity card. This name is factory-set and cannot be changed
(the Edit button is grayed out). The Configuration folder contains seven
subfolders:
• System
• User
•Network
• Web Server
•LIFE
™
• Emerson Protocol
• Messaging
Editing the Liebert IntelliSlot Unity Card Configuration
41 Liebert® IntelliSlot™ Unity™ Card User Manual
5.4.1 Configuration—System Folder
The System subfolder displays general information about the monitored and managed device and the
display of some data. Refer to Figure 5-2. The data displayed is set by the user and can assist in
troubleshooting. To alter the information displayed, click on the Edit button, enter the administrator name
and password and make changes. Click Save to save the changes; click Cancel to discard the changes.
Figure 5-2 Configuration folder, System subfolder
5.4.1.1 Time Service Settings
The System Subfolder contains one folder: Time Service. Each setting offers either a menu of choices or
an enable/disable check box. Users can set these parameters
Figure 5-3 Configuration folder, System subfolder, Time Service
Time Service setting options
External Time Source
The external source to be used for time synchronization.
NTP Time Server
Network Time Server (NTP) URL or IP address
NTP Time Sync Rate
The rate at which time will be synchronized with the Network Time Protocol server, if NTP is the external
time source.
Time Zone
Time zone where the device is located.
Enable Auto-Sync to Managed Device
Enable automatic writing time to the managed device.
Managed Device Auto-Sync Rate
Rate at which time will be written to the managed device, if an external time source has been selected.
Enter the information in the dialog boxes and choose
temperature display, either Celsius or Fahrenheit
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 42
5.4.2 Configuration—User Folder
The User subfolder displays the administrator’s and general user’s name and password. Each can be
changed. The default user name and password for the administrator are Liebert and Liebert. The defaults
for the general user are User and User. To change either, click on Edit, enter the default username and
password and enter the new information. Click on Save to accept the changes or click Cancel to discard
the changes.
5.4.3 Configuration—Network Folder
The top level of the Network subfolder displays:
• Speed Duplex
• Domain Name Suffix List
• Telnet Server
• SSH Server
The Speed Duplex item selects the speed and duplex configuration of the card’s Ethernet port. It is set to
Auto by default. If it requires changing, contact the system administrator for the proper settings.
The Domain Name Suffix List is a listing of domain name suffixes for resolution of host names. If it requires
changing, contact the system administrator for the proper setting.
The Telnet Server item allows disabling telnet access to the card to prevent unauthorized changes. The
default setting disables telnet access.
The SSH Server item allows disabling SSH (Secure SHell) access to the card to prevent unauthorized
changes. The default setting disables SSH access.
The Network subfolder contains three subfolders related to communication:
Editing the Liebert IntelliSlot Unity Card Configuration
43 Liebert® IntelliSlot™ Unity™ Card User Manual
5.4.3.1 IPv4/IPv6
The IPv4 and IPv6 settings determine which Internet Protocol will be used for communication over the
network connected to the Ethernet port. IPv4 and IPv6 networks will run in parallel (dual-stack network),
but the protocols are different. See your network administrator to determine which protocol should be
enabled and to determine the correct settings.
Figure 5-4 IPv4/IPv6 settings
IPv4 Settings
IPv4 Protocol
Enables IPv4 in the card
IP Address Method
Mode the card boots into to be a network ready device (Static, DHCP, BootP)
Static IP Address
Network address for the interface
Subnet Mask
Network mask for the interface which divides a network into manageable segments
Default Gateway
IP address of the gateway for network traffic destined for other networks or subnets
DNS Server Address Source
Source of DNS server identification (None, Automatic, Configured)
Primary DNS Server
Secondary DNS Server
IPv6 Settings
IPv6 Protocol
Enables IPv6 in the card.
IP Address Method
Mode the card boots into to be a network ready device (Static, Auto)
IPv4 Settings IPv6 Settings
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 44
Static IP Address
Network address for the interface.
Prefix Length
Prefix length for the address that divides a network into manageable segments.
Default Gateway
IP address of the gateway for network traffic destined for other networks or subnets.
DNS Server Address Source
Source of DNS server identification (None, Automatic, Configured)
Primary DNS Server
Secondary DNS Server
5.4.3.2 Domain Name Server (DNS) Test
The Domain Name Server Test checks key points of a Domain Name Server (DNS) setup for a given
domain.
Domain Name Server (DNS) Test Settings
Last Query Response
Response from a domain name server (DNS) to the last query.
Example: gxtwebdemo.liebert.com resolved to 126.4.203.234
Type of Query
Type of DNS query. (Hostname, IP Address)
Query Value
Value for the domain name server (DNS) to resolve. Example: gxtwebdemo.liebert.com
Editing the Liebert IntelliSlot Unity Card Configuration
45 Liebert® IntelliSlot™ Unity™ Card User Manual
5.4.4 Configuration—Web Server Folder
The Web Server Settings permits making some security settings, such as HTTP or HTTPS, and password
enabling.
Web Server Settings
Web Server Protocol
Select the operation mode of the Web Server (HTTP, HTTPS)
HTTP Port
Standard web port not encrypted. Required if HTTP is enabled as Web Server Protocol.
HTTPS Port
Standard secure Web port; all communication is encrypted. Required if HTTPS is enabled as Web Server
Protocol.
Password Protected Site
When enabled, a login session is required before any device information is displayed to the user. User
level credentials will allow only viewing of device information. Administrator level credentials are required
to make any changes.
Remote Write Access
When enabled, all web browsers have write access to data on all Unity-card web pages when the user is
logged-in with Administrator credentials. When disabled, write access is restricted to web browsers
connected on an Autoconfiguration IPv4 address. An Autoconfiguration IPv4 address is of the form
169.254.x.x, and is negotiated automatically when a direct connection is made between the Ethernet port
of your PC and the Ethernet port of the Unity card. For additional information, see 2.1.2 - Connect an
Ethernet Cable. Regardless of this setting, all web browsers always have read access to the web pages
(subject to the setting of the Password Protected Site parameter), and the diagnostic information file can
be generated when the user is logged-in with Administrator credentials (see 5.7 - Communications—
Support Folder).
Note: When Remote Write Access is disabled, an indicator is displayed in the upper right corner of the
web page as a reminder, Figure 5-5.
NOTE
Only disable remote-write access if you are absolutely sure that you do not
need to administer the managed device or the Unity card through a remote
web-browser session.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 46
Figure 5-5 Remote write access disabled indicator
Session Idle Timeout
The interval the software will wait before logging off a user unless there is user activity (Default is 5 min.)
5.4.4.1 Certificate
When the Web Server Protocol is configured to use HTTPS communications, all web-server
communication with all browsers is encrypted and validated based upon the security algorithms and
validity checks specified in the SSL certificate that is currently-installed in the card. By default, the card
generates its own unique, self-signed SSL certificate when it is first powered up. However, many
installations want to install and use SSL certificate files that were generated by their own Certificate
Authority (CA).
Selections in Certificate, Figure 5-6, provide commands to Upload SSL Certificate PEM Files or Generate
Self-Signed SSL Certificate.
Figure 5-6 Certificate
Certificate Commands
Upload SSL Certificate PEM Files
Uploads and installs a PEM-encoded SSL key file and certificate file that were generated by a trusted
Certificate Authority and that conform to the Apache mod_ssl module’s SSL CertificateKeyFile and
SSLCertificateFile directives. See 5.4.4.1.1, Uploading SSL Certificate PEM Files, page 48.
Note: For more information on Apache’s use of SSL certificates,
see http://httpd.apache.org/docs/2.4/mod/mod_ssl.html#sslcertificatefile.
Generate Self-Signed SSL Certificate
Generates and installs a new self-signed certificate based on the mode selected for Generate Self-Signed
SSL Certificate Mode. See 5.4.4.1.2, Generating a Self-signed SSL Certificate, page 48.
Editing the Liebert IntelliSlot Unity Card Configuration
47 Liebert® IntelliSlot™ Unity™ Card User Manual
Certificate Settings
Generate Self-Signed SSL Certificate Mode
Method used to generate a self-signed SSL certificate. Options are:
• Use Default Values = the values used in place of the user-configurable fields are the same as those
used when the original SSL certificate was generated by the card on first power-up. The default values
are not displayed.
• Use Configured Settings = the user-entered values in the configurable fields are used to generate the
certificate.
Note: When using configured settings, all of the configurable fields, described below, must have an
entry to successfully generate a certificate.
Common Name
Fully-qualified domain name that browser clients will use to reach the card’s web server when it is running
with the certificate generated with the name entered here.
Organization
Organization or company identified as the owner of the generated certificate.
Organizational Unit
Organizational unit or company division of the organization identified as the owner of the generated
certificate.
City or Locality
City or locality of the organization identified as the owner of the generated certificate.
State or Province
State or province of the organization identified as the owner of the generated certificate.
Country Code
Country-code (2-letter abbreviation) of the organization identified as the owner of the generated certificate.
Email Address
Email-address of the contact within the organization identified as owner of the generated certificate.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 48
5.4.4.1.1 Uploading SSL Certificate PEM Files
1. Select Communications tab > Configuration > Web Server > Certificate.
2. In Commands, click Enable, then click Upload next to Upload SSL Certificate PEM Files.
The upload dialog, Figure 5-7, opens.
3. Follow the instructions in the dialog to select and upload the appropriate files.
Figure 5-7 Upload SSL Key & Certificate PEM Files dialog
5.4.4.1.2 Generating a Self-signed SSL Certificate
1. Select Communications tab > Configuration > Web Server > Certificate.
2. In the Settings section:
a. Click Edit.
b. In Generate Self-Signed SSL Certificate Mode, select the mode to use.
• If you select User Configured Settings, make entries in all of the configurable-value fields
(required), then click Save.
3. In the Commands section, click Enable, then click Generate next to Generate Self-Signed SSL
Certificate.
The generate dialog, Figure 5-8, opens.
4. Follow the instructions in the dialog to generate and install the certificate.
Figure 5-8 Generate Self-Signed SSL Certificate dialog
Editing the Liebert IntelliSlot Unity Card Configuration
49 Liebert® IntelliSlot™ Unity™ Card User Manual
5.4.5 Configuration—LIFE™ Folder
The LIFE subfolder contains settings that affect use of the Emerson® LIFE Technology, a remote
monitoring and diagnostic service for Emerson Network Power units. The LIFE settings are for use by
trained Emerson Network Power personnel only and require no user changes. For information about the
LIFE settings, refer to Appendix A - Configuration Folder—LIFE™Sub Folder.
5.4.6 Configuration—Emerson Protocol Folder
Emerson Protocol contains four subfolders: Managed Device, MSTP, Ethernet and Internal.
Emerson Protocol options
Emerson Protocol IP Access
When disabled, prevents access from a remote, IP-based system using the Emerson Protocol
NOTE
With the exception of changing the node ID when multiple cards are used or when disabling
Emerson-Protocol IP access, the settings in the Emerson Protocol subfolders should not be
modified unless directed by an Emerson Network Power representative.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 50
5.4.7 Configuration—Messaging Folder
The Messaging subfolder permits enabling email and text messaging about events. The subfolder also
contains a test to determine if email and text messages can be successfully sent. Settings for the two
messaging methods permit specifying who gets the messages, the format or the messages and other
details.
Messaging options
Email
May be enabled to send email messages about events
SMS
May be enabled to send text messages about events
Editing the Liebert IntelliSlot Unity Card Configuration
51 Liebert® IntelliSlot™ Unity™ Card User Manual
5.4.7.1 Email
Selections in Email determine how the card sends emails about events.
Email Settings
Email From Address
Sender’s email address. In most cases this will be the email address of the person to whom replies should
be sent. Example Support@company.com
Email To Address
Email address of the recipient. Multiple email addresses should be separated by a semicolon.
Email Subject Type
Subject of the email. This value will default to the event description. The subject line can be customized.
Custom Subject Text
The subject of the email can be changed
SMTP Server Address
Fully qualified domain name or IP address of the server used for relaying email messages. If using a
server name, a DNS server may need to be configured under Network Settings.
SMTP Server Port
SMTP server port.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 52
SMTP Connection
SMTP server connection type. Determines the capabilities of the SMTP server. Options are:
• Clear = Do not use encryption
• SSL/TLS = Encryption using SSL/TLS connection
• STARTTLS = SSL/TLS encryption initiated using STARTTLS.
SMTP Authentication
Enable or disable email SMTP authentication. An email account must be provided for the SMTP service
provider to authenticate.
SMTP Username
Username of the email account to use when email SMTP authentication is enabled.
SMTP Password
Password for the email account to use when email SMTP authentication is enabled.
Include IP Address in Message
If checked, the IP Address of the agent card will be included in outgoing messages.
Include Event Description in Message
If checked, SNMP event description will be included in outgoing messages.
Include Name in Message
If checked, the agent card Name will be included in outgoing messages.
Include Contact in Message
If checked, the agent card Contact will be included in outgoing messages.
Include Location in Message
If checked the agent card Location will be included in outgoing messages.
Include Description in Message
If checked, the agent card Description will be included in outgoing messages.
Include Web Link in Message
If checked, a Web link to the agent card and Web Server listening port number will be included in outgoing
messages.
Enable Event Consolidation
If checked, multiple events will be sent per outgoing message.
NOTE
Some email servers may require account-configuration changes to allow
communication with the Unity card. For example, Gmail only recognizes
Google applications as being secure. However, they provide an account
setting that allows authentication with what they consider “less-secure apps.”
Please see your network administrator or service provider for configuration
details.
Editing the Liebert IntelliSlot Unity Card Configuration
53 Liebert® IntelliSlot™ Unity™ Card User Manual
Consolidation Time Limit
If Event Consolidation is enabled, a message will be sent when 'Consolidation Time Limit' seconds has
passed since the first buffered event was received.
Consolidation Event Limit
If Event Consolidation is enabled, a message will be sent when the number of buffered events reaches the
‘Consolidation Event Limit.’
5.4.7.2 SMS
Selections in SMS determine how the card sends text messages about events.
SMS Settings
SMS From Address
Sender’s SMS address. In most cases this will be the SMS address of the person to whom replies should
be sent. For example: Support@company.com
SMS To Address
SMS address of the recipient. Multiple SMS addresses should be separated by a semicolon.
SMS Subject Type
Subject of the message, either Default or Custom.
Custom Subject Text
The subject of the message; can be customized by the customer
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 54
SMTP Server Address
Fully-qualified domain name or IP address of the server used for relaying SMS messages.
Note: If using a server name, a DNS server may need to be configured under Network Settings.
SMTP Server Port
SMTP server port.
SMTP Connection
SMTP server connection type. Determines the capabilities of the SMTP server. Options are:
• Clear = Do not use encryption
• SSL/TLS = Encryption using SSL/TLS connection
• STARTTLS = SSL/TLS encryption initiated using STARTTLS.
SMTP Authentication
Enable or disable SMS SMTP authentication. An SMS account must be provided for the SMTP service
provider to authenticate.
SMTP Username
Username of the SMS account to use when SMS SMTP authentication is enabled.
SMTP Password
Password for the SMS account to use when SMS SMTP authentication is enabled.
Include IP Address in Message
If checked the IP Address of the agent card will be included in outgoing messages.
Include Event Description in Message
If checked SNMP event description will be included in outgoing messages.
Include Name in Message
If checked the agent card Name will be included in outgoing messages.
Include Contact in Message
If checked the agent card Contact will be included in outgoing messages.
Include Location in Message
If checked the agent card Location will be included in outgoing messages.
Include Description in Message
If checked the agent card Description will be included in outgoing messages.
NOTE
Some messaging servers may require account-configuration changes to allow
communication with the Unity card. For example, Gmail only recognizes
Google applications as being secure. However, they provide an account
setting that allows authentication with what they consider “less-secure apps.”
Please see your network administrator or service provider for configuration
details.
Editing the Liebert IntelliSlot Unity Card Configuration
55 Liebert® IntelliSlot™ Unity™ Card User Manual
Include Web Link in Message
If checked a Web link to the agent card and Web Server listening port number will be included in outgoing
messages.
Enable Event Consolidation
If checked multiple events will be sent per outgoing message.
Consolidation Time Limit
If Event Consolidation is enabled, a message will be sent when “Consolidation Time Limit” seconds has
passed since the first buffered event was received.
Consolidation Event Limit
If Event Consolidation is enabled, a message will be sent when the number of buffered events reaches the
“Consolidation Event Limit.”
5.4.7.3 Messaging Test
Selections here permit testing the setup for email and SMS messages. If the test fails, incorrect settings
should be changed to ensure that the Liebert IntelliSlot Unity card sends proper notifications if an event
should occur.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 56
5.5 Communications—Protocols Folder
The Protocols folder displays the types of protocols that may be enabled for a Liebert IntelliSlot Unity card.
Not all protocols are available at the same time. Some protocols may not be available for some types of
managed devices (see 1.2 - Compatibility With Other Emerson Products and Communication
Protocols). The Liebert IntelliSlot Unity card allows selecting two third-party protocols.
The folders contained by the Protocols folder are:
• BACnet
• BACnet IP
• BACnet MSTP
• Modbus
• Modbus TCP
• Modbus RTU
•SNMP
• SNMPv3 User (20)
• SNMPv1 Trap (20)
• SNMPv1/v2c Access (20)
• YDN23
Settings in each permit configuring the protocols available on the Liebert IntelliSlot Unity card.
Editing the Liebert IntelliSlot Unity Card Configuration
57 Liebert® IntelliSlot™ Unity™ Card User Manual
5.5.1 Protocols—BACnet Folder
BACnet Settings
Managed Device Write Access
Enable or Disable the BACnet server to write to the managed device.
BACnet Interface
BACnet server interface: BACnet IP or BACnet MSTP.
Device Object Instance Number
The instance number (0-4194302) of the BACnet server's device object.
Device Object Name
The name of the BACnet server's device object.
APDU Timeout
The timeout in milliseconds between APDU retries (1-65535).
APDU Retries
The number of times to retransmit an APDU after the initial attempt (0-8).
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 58
5.5.1.1 BACnet IP Folder
BACnet IP Settings
BACnet IP Port Number
The port for the BACnet server's UDP/IP connection.
Register as Foreign Device
Enable or Disable registration as a foreign device.
IP Address of BBMD
IP Address of the BACnet Broadcast Management Device (BBMD) to be accessed for Foreign Device
Registration
Foreign Device Time-to Live
Time to remain in the BBMD Foreign Device table after registration.
5.5.1.2 BACnet MSTP Folder
BACnet MSTP Settings
Node ID
The BACnet server’s MS/TP node ID (MAC).
Data Rate
The BACnet MSTP communication rate (bits per second).
Max Master Address
The maximum node ID (MAC) in use on the MS/TP network.
Max Info Frames
Maximum number of information frames this node may send before it must pass the token.
Editing the Liebert IntelliSlot Unity Card Configuration
59 Liebert® IntelliSlot™ Unity™ Card User Manual
5.5.2 Protocols—Modbus Folder
Modbus Settings
Managed Device Write Access
Enable or Disable the Modbus server to write to the managed device
Modbus Interface
Select the Modbus interface, either Modbus TCP or Modbus RTU
5.5.2.1 Modbus TCP Folder
The Modbus TCP permits connection to the card by:
• any client (Open) permits communication by any IP address
• clients on the same subnet as the Liebert IntelliSlot Unity card
• clients with specific IP addresses (Trusted IP Lists); only five addresses are permitted
Modbus TCP Settings
Limit Network Access Type
IP Access List
(Open, Same Subnet, Trusted IP List)
Port
The TCP port used by the Modbus Server to listen for and respond to Modbus protocol requests based on
Limit Network Access Type setting.
Maximum Client Connection Count
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 60
5.5.2.2 Modbus RTU Folder
Modbus RTU Settings
Node ID
Modbus Server ID for the interface; obtain from network administrator.
Baud Rate
Communication rate (9600, 19200, 38400)
Parity Check
The communication parity check (None, Even, Odd)
5.5.3 Protocols—SNMP Folder
Folders and settings in this folder permit configuring the card for various types of SNMP communication,
including access, traps and other user settings.
SNMP Settings
SNMPv3 Engine ID
Read-only. The generated SNMPv3 engine ID.
Note: A newly-generated ID appears only after rebooting the card.
SNMP v1/v2c Enable
Enable or Disable SNMP v1/v2c.
Editing the Liebert IntelliSlot Unity Card Configuration
61 Liebert® IntelliSlot™ Unity™ Card User Manual
SNMP v3 Enable
Enable or Disable SNMPv3.
Authentication Traps
When enabled, an Authentication Trap is sent if an SNMP host tries to access the card via SNMP, but
either the host address is not in the SNMP Access Settings or it is using the wrong Community String.
Heartbeat Trap Interval
Enable or Disable and set interval 5 minutes, 30 minutes, 1 hour, 4 hours, 8 hours, 12 hours and 24 hours.
RFC-1628 MIB
Enable or Disable support for retrieval of data from the RFC-1628 MIB objects.
Note: Required for proper operation of Liebert MultiLink® and applies only to managed UPS
equipment.
RFC-1628 MIB Traps
Enable or Disable support for sending RFC-1628 traps.
Note: Required for proper operation of Liebert MultiLink and applies only to managed UPS equipment.
Liebert Global Products (LGP) MIB
Enable or Disable support for getting and setting data using the Liebert Global Products MIB.
LGP MIB Traps
Enable or Disable support for Liebert Global Products MIB traps.
Note: LGP traps will not be sent unless LGP MIB is enabled.
LGP MIB System Notify Trap
Enable or Disable support for the LGP System Notification trap. This is a single trap sent each time an
alarm or warning is added or removed from the conditions table. It provides a text description of the event
in a varbind of the trap message.
Note: LGP System Notify Traps will not be generated unless the LGP MIB is enabled.
SNMPv3 Engine ID Format Type
Selects method to build the engine ID. Valid values:
• MAC Address (default) = Engine ID built from the Unity card’s MAC address.
• Text = Engine ID built from text entered in SNMPv3 Engine ID Text. See 3.1.3.1.1, Select SNMPv3
Engine ID Format, page 23.
SNMPv3 Engine ID Text
Text on which the engine ID is built when SNMPv3 Engine ID Format Type is Text.
Note: If this field is left blank, the engine ID is built from the Unity card’s MAC address.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 62
5.5.3.1 SNMPv3 User Folder
The Liebert IntelliSlot-Unity card supports up to 20 SNMPv3 users. The top level page has a table with
settings for all 20. The page displays a link to edit the table columns displayed for each SNMPv3 user. The
same settings may be accessed by clicking on a folder for a user, such as SNMPv3 User [1].
The Web page below shows the settings that can be changed for a SNMPv3 user. To display the settings,
click on any of the SNMPv3 User links. After making any changes, click Save to make the changes
effective; click Cancel to discard the changes.
SNMPv3 User Settings
SNMPv3 User Enable
Select to enable read, write or sending notifications with the user's credentials.
SNMPv3 Username
The User name the authentication and privacy settings apply to. This string can be composed of printable
characters except colon, tab, double quote, and question mark.
SNMPv3 Access Type
Read Only, Read/Write or Traps only
SNMPv3 Authentication
Cryptographic algorithm used for authentication: None, MD5 or SHA-1
SNMPv3 Authentication Secret
Pass phrase or password used for SNMPv3 Get request. This string can be composed of printable
characters with the exception of colon, tab, double quote, and question mark. Note: The entry must be 8 or
more characters but not more than 64.
Click on a SNMPv3 User folder or
a link to get this settings page.
Editing the Liebert IntelliSlot Unity Card Configuration
63 Liebert® IntelliSlot™ Unity™ Card User Manual
SNMPv3 Privacy
Cryptographic algorithm used for encryption. Options are:
•None
•DES
• AES
SNMPv3 Privacy Secret
Pass phrase or password used for SNMPv3 Get request. This string can be composed of printable
characters with the exception of colon, tab, double quote, and question mark. Note: The entry must be 8 or
more characters but not more than 64.
SNMPv3 Trap Target Addresses
Network hosts that will receive SNMPv3 traps, identified with either a network name or IP address. Multiple
addresses must be separated by commas.
SNMPv3 Trap Port
Port used by the target host for receiving SNMPv3 traps; default is 162.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 64
5.5.3.2 Editing the SNMPv3 Table
The table on the SNMPv3 User Settings [20] page may be altered to provide more or less information. To
do so, click on the command above the table (Click here to edit columns displayed in this table). Put a
check mark (?
) in the boxes beside the desired information (see Figure 5-9). The choices permit showing
the same information in this screen that is displayed by clicking on a SNMPv3 User Settings folder or a
SNMPv3 User Settings link.
Figure 5-9 Edit the SNMPv3 table
Click on this link to change the
information shown in the table
Checking all choices will display
the information below on the
SNMPv3 User page.
The information in the table for
one user may be viewed by
clicking on a SNMPv3 User
Settings folder or a SNMPv3 User
Settings link, as shown at right.
Editing the Liebert IntelliSlot Unity Card Configuration
65 Liebert® IntelliSlot™ Unity™ Card User Manual
5.5.3.3 SNMPv1 Trap Folder
This page contains settings for network hosts that will receive SNMPv1 traps. Up to 20 trap recipients may
be enabled and configured. Like the SNMPv3 pages, the settings for each target may be reached by
clicking on the links in the Detail portion of the page or by clicking on the folders for the trap targets. Also,
data shown in the table may be changed by clicking on the link above the table.
SNMPv1 Trap Settings
SNMP Trap Target Addresses
Configure network hosts that will receive alert notifications (i.e., SNMP Traps). The host can be identified
as either an IP address or the host’s network name.
SNMP Trap Port
Port used by the target host for receiving notifications; default is 162.
SNMP Trap Community String
String identifying a 'secret' known only by those hosts that want to be notified of device status changes.
Click on a SNMPv1 Trap
folder or a link to get this
settings page.
Click on this link to
change the information
shown in the table.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 66
5.5.3.4 SNMPv1/v2c Access Folder
This page contains settings for network hosts that can access data using SNMPv1/v2c. Up to 20 access
hosts can be enabled and configured. Like the SNMPv3 pages, the setting for each host may be reached
by clicking on the links in the data portion of the page or by clicking on the folders for the access hosts.
Also, data shown in the table may be changed by clicking on the link above the table.
SNMPv1/v2c Access Settings
SNMP Access IP Address
Configure network hosts interested in device information access. The host can be identified as either an IP
address or the host’s network name
SNMP Access Type
SNMPv1/v2C access type: Read Only or Read/Write
SNMP Access Community String
SNMP Community String
Click on a SNMPv1/v2c Access
folder or a link to get this
settings page.
Click on this link to change
the information shown in the
table on this page to the
information shown below.
Editing the Liebert IntelliSlot Unity Card Configuration
67 Liebert® IntelliSlot™ Unity™ Card User Manual
5.5.4 Protocols—YDN23 Folder
The YDN23 protocol supported is based on the YD-T-1363 specification using an RS-485 network
connection.
YDN23 Protocol settings
Managed Device Write Access
Enable or Disable the YDN23 server to write to the managed device.
Device Address
YDN23 device address
Baud Rate
The communications rate in bps.
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 68
5.6 Communications—Status Folder
The Status folder contains no configurable items. It displays the System Status of the Liebert IntelliSlot
Unity card and a list of events that affect the card’s status. A green check mark (?
) indicates the status is
Normal, as shown in the Status column
Editing the Liebert IntelliSlot Unity Card Configuration
69 Liebert® IntelliSlot™ Unity™ Card User Manual
5.7 Communications—Support Folder
The Support folder permits restarting the Liebert IntelliSlot Unity card, resetting the card to its factory
defaults and updating the card’s firmware. Agent refers to the Liebert IntelliSlot Unity card.
The folder also displays information about the card for help in troubleshooting, such as the card’s firmware
version, label, MAC address and related information.
Support Folder Settings
Agent Date and Time
Date and time setting for the card.
Agent Model
The card’s model (Unity Platform)
Agent App Firmware Version
The card’s firmware version (2.0 or higher)
Agent App Firmware Label
The card’s firmware label
Agent Boot Firmware Version
The card’s Boot firmware version
Agent Boot Firmware Label
The card’s boot firmware label
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 70
Agent Serial Number
The card’s serial number
Agent Manufacture Date
The card’s manufacture date
Agent Hardware Version
The card’s hardware version
GDD Version
The card’s GDD version, current when the card’s firmware was installed; the GDD is a proprietary
reference document for device data.
FDM Version
The card’s FDM version; the FDM is a data model document that defines data supported by devices that
use the Emerson Protocol.
Product Sequence ID
The card’s product sequence identifier
Commands
Enable/Cancel
Restart Card
Restart card and implement configuration changes
Reset Card to Factory Defaults
Reset the card’s configuration to its factory defaults
Generate and download diagnostic file
Generate a file containing diagnostic information and download it with a Web browser.
Editing the Liebert IntelliSlot Unity Card Configuration
71 Liebert® IntelliSlot™ Unity™ Card User Manual
5.7.1 Support—Active Networking Folder
Status of the currently active IP network settings for the Liebert IntelliSlot Unity card along with some
previous values for troubleshooting IP communication issues.
Active Networking Settings
Ethernet MAC Address
Ethernet MAC Address for the Liebert IntelliSlot card
IPv4 Address
Presently used IPv4 network address
IPv4 Default Gateway
Presently used IPv4 network address of the gateway for network traffic destined for other networks or
subnets
Primary DNS
Presently used IPv4 Primary DNS
Secondary DNS
Presently used IPv4 Secondary DNS
Last DHCP/BOOTP Address
Last known IPv4 address assigned by DHCP
Last DHCP Lease
Lease time of last known DHCP address
IPv6 Global Address
Shows if DHCPv6 or Static address is presently being used
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 72
StateLess Address AutoConfiguration
IPv6 SLAAC is assigned automatically from Router Advertisement, if “A” flag is set, combining Prefix with
EUI-64 MAC
Link Local
Presently used IPv6 Link Local Address
IPv6 Default Gateway
Presently used IPv6 network address of the gateway for network traffic destined for other networks or
subnets
Primary DNS Server
IPv6 Primary DNS
Secondary DNS Server
Presently used IPv6 Secondary DNS
Last DHCPv6
Last known IPv6 address assigned by DHCPv6
Last DHCPv6 Lease
Lease time of last known DHCPv6 address
Editing the Liebert IntelliSlot Unity Card Configuration
73 Liebert® IntelliSlot™ Unity™ Card User Manual
5.7.2 Support—Firmware Update Folder
The Firmware Update folder supports updating the firmware of the Liebert IntelliSlot Unity card or reverting
to an alternate firmware version and configuration (if the current firmware is not the initial load).
Firmware Update settings
Current Firmware Version
The version of the firmware running on the card
Current Firmware Label
The label of the firmware running on the card
Current Firmware Date
The build date of the firmware running on the card
Alternate Firmware Version
The version of the firmware in the alternate area
Alternate Firmware Label
The label of the firmware in the alternate area
Alternate Firmware Date
The build date of the firmware in the alternate area
Editing the Liebert IntelliSlot Unity Card Configuration
Liebert® IntelliSlot™ Unity™ Card User Manual 74
Firmware Commands
Run Alternate Firmware
Return the card's firmware to a version in the alternate area (the version in use before the most recent
firmware update).
Firmware Update
Update the card’s firmware to a new version
Firmware Updates
75 Liebert® IntelliSlot™ Unity™ Card User Manual
6.0 Firmware Updates
The Liebert IntelliSlot Unity card has two areas in flash memory for the firmware and the configuration. One
area is currently operating on the card. The other area is the previous firmware on the card and is
considered an alternate. For information on the alternate firmware, see 6.2 - Revert to Alternate
Firmware.
6.1 Updating the Liebert IntelliSlot Unity Card’s Firmware
To update the Liebert IntelliSlot Unity card’s firmware:
1. Download onto your computer the latest Liebert IntelliSlot Unity card firmware update from the Liebert
software download Web site at www.liebert.com
2. If the card’s DHCP or Static-IP address is known, type the IP address in the Web browser address
window.
3. If the card does not have a known IP address and it is configured for DHCP, connect the card to a
computer with an Ethernet cable and open a Web browser. The card has an Ethernet RJ-45 connector
on the front (see Figure 6-1). The card and computer will automatically negotiate communications,
which will take about one minute (for details on auto configuration, see 2.1.2 - Connect an Ethernet
Cable). When communication is established, open a Web browser and enter the address
169.254.24.7, the card’s default Autoconfiguration IPv4 Address. The card’s Web page will appear.
Figure 6-1 Ethernet port
4. Select the Communications tab at the top of the screen, then the Support folder from the
Communications folders on the left of the screen and then the Firmware Update folder.
5. Select the Enable button.
6. Enter the administrator user name and password selected previously (see 2.2 - Change User Names
and Passwords Immediately) in the security dialog box that appears.
Activity
Link 485
IS-UNITY-DP
Liebert IntelliSlot
Card Ethernet Port
Firmware Updates
Liebert® IntelliSlot™ Unity™ Card User Manual 76
7. Click the Web button.
The firmware-update screen opens.
8. Browse to the firmware file to update, select it and click the Update Firmware button.
Figure 6-2 Firmware update screen
NOTE
Do not navigate away from the Firmware Update screen and do not close the browser once the
update begins. Either action will interrupt the download.
Support
Folder
Firmware
Update
Web button becomes
active when enabled and
administrator’s user name
and password are entered
Enable
Button
User name and
password must be
entered to update
firmware
Firmware Updates
77 Liebert® IntelliSlot™ Unity™ Card User Manual
6.2 Revert to Alternate Firmware
The Liebert IntelliSlot Unity card has two areas in flash memory for the firmware and the configuration. One
area is currently operating on the card. The other area is considered an alternate.
When a card’s firmware is updated, the previous firmware and configuration are moved to the alternate
area. The Liebert IntelliSlot Unity card allows returning to the firmware version and configuration that are
kept in the alternate area.
1. Select the Communications tab at the top of the screen.
2. Select the Support folder, then the Update Firmware folder.
3. Select the Enable button.
4. Enter the user name and password in the security dialog box that appears; use the administrator user
name and password from the user settings.
5. Click the Run Alternate button.
A confirmation dialog opens.
6. Click OK on the confirmation dialog.
NOTE
Reverting to an alternate firmware version will not be possible if the currently operating firmware is
the initial version loaded on the Liebert IntelliSlot Unity card. If the initially loaded firmware is still
running on the card, the Alternate Version fields will be blank, and it will not be possible to revert to
an alternate version.
NOTE
The card will reboot. After the reboot, the card will be running the previous version of the firmware
and configuration, which had been stored in flash memory. The previous firmware and
configuration will have been moved to the alternate area.
Firmware Updates
Liebert® IntelliSlot™ Unity™ Card User Manual 78
Page intentionally left blank.
Configuration Folder—LIFE™Sub Folder
79 Liebert® IntelliSlot™ Unity™ Card User Manual
Appendix A - Configuration Folder—
LIFE™Sub Folder
The LIFE sub folder contains settings that affect use of the Emerson® LIFE Technology, a remote
monitoring and diagnostic service for Emerson units. The LIFE settings are for use by trained Emerson
Network Power personnel only and require no user changes.
UPS State SMS Messaging Configuration
Status Description
Connection Media The LIFE Technology connection media
Enable Date and Time The date and time that LIFE Technology support was enabled.
Settings Description
LIFE Technology Enable or disable the LIFE Technology
System Serial Number System serial number, obtained from the unit automatically
Site Equipment Tag Number Site equipment tag number
Site Identifier Site identifier, entered by the Service Technician
Answer Incoming Call Enable answering of LIFE Watch Station incoming calls
Next Call Date and Time Date and Time of next call to make to the LIFE Watch Station server
Call Interval Days Days between routine calls to LIFE Watch Station
Call Interval Hours Number of hours between LIFE Watch Station routine calls
Call Interval Minutes Number of minutes between routine LIFE Watch Station calls. This value is used in
conjunction with val_life_callInterval_hours.
Call Trials Number The number of attempts to retry a call after it fails before rescheduling the call.
Settings Description
Primary Mains Restored SMS Send SMS when Primary Mains are restored
Primary Mains Restored SMS Value Value sent via SMS when Primary Mains are restored
Primary Mains Failure SMS Send SMS when Primary Mains fail
Primary Mains Failure SMS Value Value sent via SMS when Primary Mains fail
Bypass Mains Fail SMS Send SMS when Bypass Mains fail
Bypass Mains Failure SMS Value Value sent via SMS when Bypass Mains fail
Load On Bypass SMS LIFE Load on Bypass SMS Enable
Load On Bypass SMS Delay The amount of time to delay sending an SMS after a Load is on Bypass if the
condition still exists.
Configuration Folder—LIFE™Sub Folder
Liebert® IntelliSlot™ Unity™ Card User Manual 80
Gate Settings
Advanced
Status Description
HTTP Transport Result HTTP Transport Result contains the result of the last HTTP transaction.
HTTP Transport Error Value HTTP Transport Error value from the last HTTP transaction
HTTP Transport Reply Time HTTP transport reply time
Connection Result IP connection result
Bridge State IP Bridge state machine state
Error Count Gate connection error count
Settings Description
Proxy Enable Enable Gate proxy
Proxy Authentication Enable Gate proxy authentication
Proxy IP Address Gate proxy IP address
Proxy IP Port Number Gate proxy IP port number
Proxy User Name Gate proxy user name
Proxy User Password Gate proxy user password
LIFE Gate IP Address LIFE Gate IP address
LIFE Gate IP Port Number LIFE Gate Port Number
Status Description
Device State Whether the device is connected or unconnected
Connection Status
The connection status of the Remote Service Delivery application system
interface. This is the interface by which Remote Service Delivery services
communicates with the Unity system software.
Call Type The type of call currently in progress with the LIFE™ Watch Station server.
Scheduled Call Delay Time The delay time before the next call to the LIFE Watch Station server.
Heartbeat Status Device status as determined by heartbeat traps
Date and Time (UTC) of Last
Call
The date and time (in UTC) of the LIFE Watch Station that was retrieved when the
last successful call was made. YY-MM-DD HH:MM:SS
Commands Description
Make Manual Call Sends all currently collected events
Reset Scheduled Call Delay
Time Forces a rescheduled call to be done immediately
Reset Activity and Data Resets all LIFE in-progress activity and deletes all LIFE data
Settings Description
Service Mode Enable or Disable LIFE service Mode
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Thermal Management Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims
all liability for damages resulting from use of this information or for any errors or omissions.
© 2016 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to changewithout notice.
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Emerson Network Power
www.emersonnetworkpower.com
SL-52645_REV9_8-16
590-1305-501C