Table of Contents
- Important Safety Messages
- Safety and General Information
- Deenergizing safety
- Electrical safety
- Battery safety
- General information
- FCC Class A radio frequency warning
- Package Contents
- Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
- Specifications
- Environmental
- Physical
- Battery
- Electrical
- Remove Battery Module
- Rack-Mount Installation
- Tower Installation
- Rear Panel Features
- Key to identify rear panel features
- UPS Configuration
- Connect Emergency Power Off feature
- Verify input connection
- Configure controllable outlet groups
- UPS Display Interface
- Display interface operation
- Menu overview
- LCD display interface angle adjustment
- Select models are ENERGY STAR® qualified. For more information go to www.apc.com/company/us/en/sustainability/energy-efficiency/
APC SRT2200RMXLA User Manual
Displayed below is the user manual for SRT2200RMXLA by APC which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals

Installation Guide Smart-UPS™On-Line
SRT2200/SRT3000 XLA Tower/Rack-Mount
Important Safety Messages
Read the instructions carefully to become familiar with the equipment before attempting to install, operate, service or
maintain the UPS. The following special me ssages m ay appear throughout this manual or on the equipment to warn of
po t en t ial haza r d s or to cal l at tenti o n to in fo r m at i on th a t cl ar i fi e s or sim p l ifies a proc ed u r e.
The addition of t his symbol to a Danger or Warning product safety label indicates that an ele ctrical hazard
exists which will result in personal injury if the instructions are not followed.
The addition of this symbol to a Warnin g or Caut ion product safet y label indicat es that a hazard exis ts that
can result in injury and product damage if the instructions are not followed.
Information
Safety and General Information
• Adhere to all nationa l and local electric al c odes.
• All wiring m ust be performed b y a qualified electrician.
• Changes and modifications to this unit not expressly approved by APC could void the wa rranty.
• This UPS is intended for in door u se only.
• Do not operate th is UPS in direct sun light, in contact with flu id s, or where th ere is excessive dust or humid ity.
• Be sure the air vents on the UPS are not blocked. Allow a deq uate space for proper ventilation.
• For a UPS w it h a f a ctor y i ns ta l led po we r c ord, c onne ct th e UPS p o wer ca bl e dir e ctl y to a wall outl e t. Do not us e s urge
protectors or extension cords.
• The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambien t
temperatures, po or quality mains power, and frequent short duration discharges will shorten battery life.
• Replac e the ba ttery immediately when the UPS in dicates battery replaceme nt is necessary.
• The equipment is he avy. A lwa ys pr actice sa fe lifting techniques adequate for the weight of th e equipment.
• Th e batterie s are heavy. Remove the batteries before in stalling the UPS and external battery pac ks (XLBPs), in a rack.
• Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the XLBPs.
• Always install peripheral equipment above the UPS in rack-mount configurations.
• Additional safety information can be fo u nd in the Saf ety Guid e s upplied with this unit.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or seri ous i njury.
CAUTION
CAUTION indicates a potential ly hazardous situation which, if not avoided, can re s u lt in minor or moderate injury.
NOTICE
NOTICE used to addr ess practices not related t o physical inj ury. The saf ety a lert symbol is not used with this signal word.

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/ Rack-Mount 2U2
Dee nergizing safety
The U PS contains internal batteries and may pr esent a shock hazard even when disconnected from the branch circuit (mains).
Before installing or servicing the equ ip me n t check that the:
• inp ut circuit breaker is in the OFF position.
• in terna l U P S th e b at teries ar e re m o v e d.
• XLBP battery modules are dis connected.
Electrical safety
• For model s wit h a hard wired i nput, the connection to the branch circui t (mains) m us t be pe rformed by a
qualified electrician.
• The prot ec tive earth conduc tor for the UPS carries the leakage current fr om th e load devices (comput er
equipment). An insulated ground conductor is to be instal led as part of the branch circuit that s upplies the UPS.
The conductor must have the same size and insulation material as the grounded and ungrounded branch circuit
supply conductors. The c onductor will ty pically be green and with or wit hout a yellow stripe.
• The UPS input ground c onductor must be properly bonded to protec tive earth at the service panel.
• If the UPS input power is supplied by a separately derived syste m, the ground conductor must be prope rly
bonded at the supply transformer or motor generator s et.
Battery safety
• Before inst alling or r eplacing t h e batteries, remove jewelry such as wristwatch es and rings .
High sh ort circuit curre nt through conductive ma terials could ca use severe burns.
• Do not dispose of batteries by burning them. The batter ies m ay explode.
• Do not open or mut ilate batter ies. Released elec trolyte is harmful t o the skin and eyes, and may be toxic.
General information
• The UPS will recognize as many as 10 external battery pa cks connected to the UPS.
Note: For each XLBP added, increased recharge time will be requir ed.
• The m odel and serial numbers are located on a small, rear panel label. For some models, an additional la bel is
located on the chassis under the front beze l.
• Always recycle used batteries.
• Recycle the package materials or save them for reuse.
FCC Class A radio frequency warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of
the FCC Rules. T hese limits are intended to provide reasonable protection against harm ful interference when the
equipment is operated in a commerc ial en v ironme n t. T h is equi pment generates, uses, and can radi ate radio frequency
ener gy and, if not in stal led and used in acco rdan ce with the inst ructi on manual, may caus e harmful inte rferenc e to radio
communic ations. Opera tion of this equipment in a residential area is like ly to caus e ha rm ful interference in which case
the use r w ill be required to correct the inte r f erence at his ow n expense.

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower /Rack-M ount 2U 3
Package Contents
Inspect the contents upon receipt. Notify the carrier and dealer if the unit i s damaged.
Included with all models NC models only
Front bezel RJ45 to DB9 ca ble
USB cable
EPO Termina l bloc k
User Documentation CD.
PCBE Software CD
Temperature sensor probe
Serial co nfiguration cabl e
Network Manage ment U tility CD
In cl ude d w it h Tow er models only
• 2 pairs s t ab il ize r br acke ts
• 4 flat head screws to secure tower stabilizer brackets to the UPS
Included with Rack-Mount models only
Rail Kit with instr uctions and h ardware
for installing rails in a ra ck. • 1 pair rac k-mount brackets
• 6 flat head screws to secure rack -mount brackets to the UPS
• 4 ornamenta l s cre ws to se cure rack-mount bracket s to t he rails
User D ocumentat ion
x4
su04
34a
x4
x6

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/ Rack-Mount 2U4
Specifications
For additional specifications refer t o the APC by Schneider Electric web s ite, www.apc.com.
Environmental
Physical
Temperature Operating 0º to 40º C (32º to 104º F)
Storage - 15º to 45º C (5º to 113º F)
Elevation Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (50,000 ft)
Humidity 0 % to 95% relative humidi ty, non-condensing
Protection Class I P 20 rating
Note: Charge the battery modules every six m onths during storage.
Environmental fac tors impact battery life. Elevated ambient temperatur es , high hu mi dity, poor quality mains power, and
frequent short duration discharges will shorten batt ery life.
SRT 2200XLA/SRT2200RMXLA/SRT2200RMXLA-NC model
The U PS is heavy. Follow all lifting guidelines.
Lif t ing guidelines 18 - 32 kg (40 - 70 lb) 32 - 55 kg (70 - 120 lb)
Unit weight batteries included, without packaging 26.5 kg (58.4 lb)
Unit weight batteries included, with packaging Rack-Mount models: 34.6 kg (76.2 lb)
To wer models: 3 1.6 kg (69 .7 lb)
Unit dimensions without packaging
Height x Width x Depth 85 (2U) mm x 432 mm x 560 mm
3.35 (2U) in x 17 in x 22 in
Unit dimensions with packaging
Height x Width x Depth 245 mm x 600 mm x 810 mm
9.7 in x 23. 6 in x 31.9 in
The model and serial numbers are on a small labe l located on the rear panel.
SRT 3000XLA/SRT3000RMXLA/SRT3000RMXLA-NC model
The U PS is heavy. Follow all lifting guidelines.
Lif t ing guidelines 18 - 32 kg (40 - 70 lb) 32 - 55 kg (70 - 120 lb)
Unit weight batteries included, without packaging 32 kg (70.5 lb)
Unit weight batteries included, with packaging Rack-Mount models: 41 kg (90.4 lb)
Tower models: 38 kg (83.8 lb)
Unit dimensions without packaging
Height x Width x Depth 85 (2U) mm x 432 mm x 611 mm
3.35 (2U) in x 17 in x 24 in
Unit dimensions with packaging
Height x Width x Depth 245 mm x 600 mm x 870 mm
9.7 in x 23.6 i n x 34.3 i n
The model and serial numbers are on a small labe l located on the rear panel.

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower /Rack-M ount 2U 5
Battery
NOTICE
RISK OF EQUIPMENT DAMAGE
• Replace the battery at least every 5 years.
• Replace the battery immediately when the UPS indicates battery replacement is necessary.
Failure to follow these instruc tions can result in e quipment damage
SRT 2200 models SRT 3000 models
Battery type Sealed, maintenance-free, Valve Regulated
Lead-Acid battery
Rep l acem e nt ba tt ery module
This UPS has s wappable batte r y modules.
Refer to the ap propriate repla ce ment battery user manua l for
installation instructions.
Contac t your dealer or go the APC by Schneider Electric web sit e,
www.apc.com for information on replacement batteries.
APCRBC141 APCRBC152
Number of battery modules 1 batte r y module
Voltage for ea ch battery module 72 VDC 96 VDC
Total battery voltage for the UPS 72 VDC 96 VDC
Ah rating 5 Ah per batter y mod ule
XL B P ca bl e leng t h 500 mm (19.7 in)

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/ Rack-Mount 2U6
Electrical
Models Rating Bra n ch Circu it
Ov ercurrent Rating /
Building Circuit Breake r
(CB ) Current Rating
Online Green Mode
SRT2200XLA 2200 VA / 1800 W 1800 VA 20 A
SRT2200RMXLA/SRT2200RMXLA-NC
SRT3000XLA 3000 VA / 2700 W 2700 VA 30 A
SRT3000RMXLA/SRT3000RMXLA-NC
CAUTION
RISK OF FIRE, RISK OF DAMAGE T O EQUIPMENT OR PERSONNEL
Connect the UPS models only to a circuit p rovided wi th recomm ended maximum branch circuit overcur rent protect ion in
accordance with the Nati onal Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
Failure t o follow these instructions can re sult in fi re, equipment damage and minor or moderate injury.
Output
Output Frequency 50 Hz / 60 Hz (Selectable)
Nominal Output Voltage 120 V
Input
Input Frequency 40 Hz - 70 Hz
Nominal Input Voltage 120 V
Nominal Input C urrent SRT2200 models: 16 A
SRT 3000 m odels: 24 A

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower /Rack-M ount 2U 7
Remove Battery Module
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Each APCRBC152 bat tery module weighs 16.4 kg (36. 2 lb) and each APCRBC141 battery module
weighs 12.5 kg (27.6lb).
• Always practice saf e li fting techn iques adequate for t he we ight of the equipment.
• Remove the battery modules before installing the UPS.
• Use the battery module handle to slide the battery modules in or out of the UPS.
• Do not use the bat tery module handle to lift or carry the battery module.
Failure to follow these instructi ons can result in equipment damage and minor or moderate injury.
SRT2200 models
SRT3000 models
suo0849b
x3
suo0850c
suo0858c
suo0851b

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/ Rack-Mount 2U8
Rack-Mount Installation
Refer to the Rail Kit Installation Guide for i ns tructions on rail installation.
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always p ractice safe lifting t echniques adeq uate f or the weight of the equipment.
• Always use the recommended numbe r of sc rews to secure brackets t o the UPS.
• Always use the recommended numbe r of sc rews t o secure the UPS to the rack.
• Always install the UPS at th e bott om of th e rack.
• Always install the XLBP bel ow the UPS in the rac k.
Failur e to fol low these instructi ons can result in equipment da mag e and minor or moderate injury
suo0866c
x3
x3
suo0867b
suo0865b
x4
suo0868b

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower /Rack-M ount 2U 9
suo0869b
x3
suo0870b
suo1061a
x4
su0859a

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/ Rack-Mount 2U10
Tower Installation
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is h eavy. Each APCRBC152 battery module weighs 16. 4 kg (36. 2 lb) and each APCRBC141 battery m odule
weighs 12.5 kg (27.6lb).
• Always practice safe li fting techni ques adequate for th e weight of t he equipment.
• Remove the battery modules bef ore installing the UPS.
• Use t he batt ery module handle to slide the battery modules in or out of the UPS.
• Do not use the batter y module handle to lift or carry the battery modul e.
Failur e to fol low these instructi ons can result in equipment da mag e and minor or moderate injury
su0845c
suo0871c
suo0872c
suo0873c
x3
suo0874c
suo1062a
x4

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower /Rack-M ount 2U 11
Rear Pane l Features
Note: Refer to the table “Key to identify rear panel f eatures” on page 12, that provides a key to the c allout numbers for
the rear panel graphics depicted in this manual.
SRT2200XLA/SRT2200RMXLA
SRT2200RMXLA-NC
suo0875c
GROUP 1
20 AMP MAX
suo1092b
GROUP 1
20 AMP MAX
suo1093b

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/ Rack-Mount 2U12
Key to identify rear panel features
SRT3000XLA/SRT3000RMXLA
SRT3000RMXLA-NC
SmartSlot The SmartS lot c an be used to connect optional m anagement accessories.
AC input power cable
or hardwire inpu t box All models ha ve factory installed input power cables.
Hardwired input box is an optional accessory.
External battery
power and
communica tion
connector
Use the external ba ttery cable on the XLBP to connect the UPS and XLBP.
XLBPs provi de extended runtime during power outages. The UPS will automatically
recognize up to 10 exte rnal battery packs.
Controllable
outl et gr oup 1 Connect electronic devices to these outlets.
Chassis ground screw The UPS and XLBP s have ground screws for c onnect ing the ground l eads. Pri or to c onnect ing
a ground lead, disconnect the UPS from main s power.
Controllable
outl et gr oup 2 Connect electronic devices to these outlets.
EPO terminal The Emer gency Power Off (EPO) terminal allows the user to co nnect the UPS to a central
EPO system.
Serial Co m The Serial Com port is used to communicate with the UPS.
Use only interface kits supplie d or approved by APC by Schneider Electric. Any other
s eri a l interf ace cab l e w il l be in c o mpati bl e w it h the UPS co nn e ct o r.
GROUP 3
30 AMP MAX
GROUP 2
20 AMP MAX
GROUP 1
20 AMP MAX
GROUP 1
20 AMP MAX
suo1094b
GROUP 3
30 AMP MAX
GROUP 2
20 AMP MAX
GROUP 1
20 AMP MAX
GROUP 1
20 AMP MAX
suo1095b

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower /Rack-M ount 2U 13
UPS Configuration
Connect Emergency Power Off feature
For instructions on how to connect the Emergency Power Off (E PO) switch, refer to the Operation and Maintenance
manual on the User Docume ntation CD (supplied).
Verify input connection
UPS displa ys Site Wiring Fault if t he line a nd neutra l connec tions are inte rchang ed or if gr ound connecti on is mi ssing.
Correct the input c onnecti ons and pres s OK button to clear the Site Wiri ng Alert. See the Confi g Me nu UPS sectio n in
the UPS operation manual for details.
Configure controllable outlet groups
The outl ets on the UPS are grouped. To conf igure the controlled outlet fea tures, use the Advanced menus on the
display interface an d navigate to: Main Menu > Configuration > Outlets > Outlet Gr oup.
UPS Display Interface
USB port The USB port is us ed to connect eith er a server for native operating system communi cations,
or for software to communicate with the UPS.
Note: Serial and USB communication should not be u sed simultaneously. Use either the Serial
Com or the USB port.
Main outlet Conn ect elec tr onic devices to the main outlet.
POWER ON/OFF button
Button illu min a tion in dications :
-No illumination, the UPS and the output
power are off
-White illuminat ion, the UPS and the output
power are on
-Red illumination, the UPS is on and t he
output power is off
Load ic on
Disable/mute audible alarm icon
UPS status information
Operation mode icons
ESCAPE button
OK button
UP/DOWN buttons
Contr ollable outlet group status icons
Bat t ery status icons
su0870f
Output
120.0
v
LOAD
On-Line
12

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/ Rack-Mount 2U14
Displa y interface operation
Use the UP/DOWN buttons to scrol l thro ugh the options. Press the OK button to acce pt the selected option. Press the
ESC button to return to the previous menu.
The icons on the L CD display interface screen may vary depe nding on the installed firmware version.
Load icon: The approximate load ca pacity percentage is ind icated by the number of loa d bar
sections illuminated. Each bar represents 16% of the load capacity.
Mute icon: Indicates the audible alarm is dis abled/mute.
UPS Status Inform ation
The status information fie ld provides key information on the status of th e UPS.
The Standard menu will allow the user to select one of t he f ive screens listed below. Use th e UP/DOWN butt ons to scrol l
through the sc reens.
The Advanced menu will scroll throu gh the five scree ns au tomatically.
•Input Vol tage
•Output Voltage
•Output Frequenc y
•Load
•Runtime
I n the case of a UPS event , s tatus updates will be di splayed defin ing the event or condit ion that ha s occurred.
The displa y screen il lumina tes amber to indic ate a Mess age and red to in dic ate an Alert de pen ding on the seve rit y of t he event
or condition.
Operation Mode Ico ns
On-Line mode: The UPS is supplying conditioned mai ns p ower to c onnected equipment.
Bypass mo de: The UPS is in Bypass mode and the connected equipment will re ceive mains
power as long as the input voltage a nd frequency are within the configured limits.
Green mode: When in Green mode mains powe r is sent dire ctly to the load.
In the event of a mains power outage, there w ill be an interruption in power to the load of up to
10 m s w h ile the U P S sw i tche s to On-Line or Battery mode.
When enabling Green mode consideration should be given to de vices that may be sensitive to
power fl uctuat ions.
Indicates a UPS alert that requires attention.
UPS S tatus Icon
Battery mode: The UPS is supplying battery power to connected equipment.
The UPS has detected an internal fault with the battery. Follow the instructions on the screen.
LOAD

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower /Rack-M ount 2U 15
Menu overview
The display interf ace has St andard and Advanced menu screens. The preference for St a ndard or Advanced menu
selections is made during initial installation and can be changed at any time through the Configuration menu.
The Standard menus include t he most com monly used opti ons.
The Advanced menus provide additional options.
Note: Ac tual me nu screens may differ by model and f irm ware version.
Refer to the UPS Ope ration Manual for menu configura tion details.
The UP S ha s detected a critical f ault with the batter y. The battery is at the end of its lif e and has
to be repla ce d.
Controllable Outlet Group Icons
Contr ollable Outlet Group Power Avail ab le: The number next to the icon identifies the
specific outlet groups that have available power.
Flashing icon indica tes the outlet group is turning from OFF to ON with delay.
Control lable Outlet Group Power Not Ava ilable: The number next to the ic on identifies
specific outlet groups that do not have available power.
Flashing icon indica tes the outlet group is turning from ON to OFF with dela y.
Battery Status Icons
Battery Char ge Status: Ind i cates th e ba tt e ry ch ar ge sta tu s .
Battery Char ge In Progress : Indica tes the battery is cha rging.
X

Customer support and warranty information a re a vailable on the APC by Schneider Electric web site,
www.apc.com.
© 2015 APC by Schneider Electric. A PC, t he A PC logo, and Sma rt-UPS are own ed by Schneider
Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their
respective owners .
EN 990-97 38
10/2015
LCD display interface angle adjustment
The angle of the LCD di spl ay i nterface can be adjusted for ea se in viewing the displayed mes s ages.
1. Remove the front bezel.
2. Locate the button on the bottom of the display int erface panel.
3. Press the button and slide the bo ttom of the LCD display interface screen out . An audible click will be hea r d
when the screen reaches the maximum angle.
Select models are ENERGY STA R® qua lified.
For more in formation go to www.apc.com/com pany/us/en/sustainability/energy-efficiency/
su0926a