Table of Contents
- Safety Messages
- Safety and General Information
- Deenergizing safety
- Electrical safety
- Battery safety
- Hardwire safety
- General information
- FCC Class A radio frequency warning
- Package Contents
- Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
- Specifications
- Environmental
- Physical
- Battery
- Electrical
- Remove Battery Modules
- Rack-Mount Installation
- Tower Installation
- Front Panel Features
- Rear Panel Features
- Key to identify rear panel features
- Wiring Specifications
- Hardwire the UPS
- Input hardwire
- Output hardwire
- UPS Configuration
- Connect Emergency Power Off feature
- Configure controllable outlet groups
- UPS Display Interface
- Display interface operation
- Menu overview
- LCD display interface angle adjustment
- Select models are ENERGY STAR® qualified. For more information go to www.apc.com/site/recycle/index.cfm/energy-efficiency/energy-star/
APC SRT8KRMXLT User Manual
Displayed below is the user manual for SRT8KRMXLT by APC which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals
Installation Guide Smart-UPS™On-Line
SRT8K/SRT10K Tower/Rack-Mount 6U
Safety Messages
Read the instructions carefully to become familiar with the equipment before attempting to install, operate, service or
maintain the UPS. The following special messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning product safety label indicates that an electrical hazard
exists which will result in personal in jury if the instructions are not followed.
The addition of this symbol to a Warning or Caution pr odu c t safety label indicat es that a hazard exists that
can result in injury and product damage if the instructions are not followed.
Information
Safety and General Information
• Adhere to all national and local electrical codes.
• All wiring must be performed by a qualified electrician.
• Changes and modifications to this unit not expressly approved by APC could void the warranty.
• This unit is intended only for indoor use in a controlled environment.
• Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
• Be sure the air vents on the unit are not blocked. Allow adequate space for proper ventilation.
• For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors
or extension cords.
• The battery typically lasts for two to five years. Environme ntal factors imp act battery life. Elevated ambient temperatures, high
humidity, poor quality mains power, and frequent short duration discharges will shorten battery life.
• Replace the battery immediately when the UPS indicates battery replacement is necessary.
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• The batteries are heavy. Remove the batteries before installing the UPS and external battery packs (XLBPs), in a rack.
• Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the XLBPs.
• Always install peripheral equipment above the UPS in rack-m ount conf iguratio ns.
• Additional safety information can be found in the Safety Guide supplied with this unit.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can re sul t in minor or moderate injury.
NOTICE
NOTICE addresses practices not related to physical injury including certain environmental hazards, potential damage or loss
of data.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U2
Deenergizing safety
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit (mains).
Before installing or servicing the equipment verify that the:
• Mains circuit breaker is in the OFF position.
• Internal UPS batteries are removed.
• XLBP battery modules are disconnected.
Electrical safety
• For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a qualified electrician.
• 230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe, output cords attached to
the UPS must not exceed 10 meters in length.
• The protective earth conductor for the UPS carries the leakage current from the load devi ces (comp uter equ ipment). An insulated
ground conductor is to be installed as part of the branch circuit that supplies the UPS. The conductor must have the same size and
insulation material as the grounded and ungrounded branch circuit supply conductors. The conductor will typically be green and
with or without a yellow stripe.
• The UPS input ground conductor must be properly bonded to protective earth at the service panel.
• If the UPS input power is supplied by a separately derived system, the ground conductor must be properly bonded at the
supply transformer or motor generator set.
Battery safety
• Before installing or replacing the batteries, remove jewelry such as wristwatches and rings.
High short circuit current through conductive materials could cause severe burns.
• Do not dispose of batteries by b urnin g them. The batteri es may expl ode .
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
Hardwire safe ty
• Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out before installing cables or
making connections, whether in the junction box or to the UPS.
• Wiring by a qualified electrician is required.
• Check nat ional and local code s be f or e wiri n g.
• Strain relief is required for all hard wiring (not supplied). Snap in type strain reliefs are recommended.
• All openings that allow access to UPS hardwire terminals must be covered. Failure to do so may result in personal injury or
equipment damage.
• Select wire size and connectors according to national and local codes.
Gen eral in f orma t ion
• The UPS will recognize as many as 10 external battery packs connected to the UPS. However there is no limit to the number of
XLBPs that can be used with the UPS.
Note: For each XLBP added, increased recharge time will be required.
• The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the
chassis under the front bezel.
• Always recycle used batteries.
• Recycle the package materials or save them for reus e.
FCC Class A radio frequen cy warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the
FCC Rules. These limits are intended to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environ ment. This equip ment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required
to correct the interference at his own expense.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 3
Package Contents
Inspect the conten ts upon receipt. Notify the carrier and dealer if the unit is damaged.
Included with all models
Front bezels Console to DB9 cable
RJ45 to DB9 cable
USB cable
EPO Terminal block
Temperature sensor probe
User Documentation CD.
Network Management Utilit y CD
Included with XLI/XLT-IEC models only
Three output power cords
One C 13/C14, 10 A, 2 m Two C19/C20, 16 A, 2.5 m
Included with Rack-Mount models only
Rail Kit with instructions and hardware
for installing rails in a rack. • 2 pairs of rack-mount brackets
• 16 flat head screws to secure rack-mount brackets to the UPS
• 8 ornamental screws to secure rack-mount brackets to the rails
• 6 cage nuts
U s er D ocume ntation
su04
34a
x8
x16
x6
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U4
Specifications
For additional specifications refer to the APC web site, www.apc.com.
Environmental
Physical
Battery
Temperature Operating 0º to 40º C (32º to 104º F)
Storage -15º to 45º C (5º to 113º F)
Maximum Elevation Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing
Protection Class IP 20 rating
Note: Charge the battery modules every six months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor
quality mains power, and frequent short duration discharges will shorten battery life.
The UPS is heavy. Follo w all lifting guidelines.
Lifting guidelines >55 kg (>120 lb)
Unit weight without packaging 111.8 kg (246 lb)
Unit weight with packaging Rack-Mount models: 126.8 kg (279 lb)
Tower models: 130 kg (286 lb)
Unit dimensions without packaging
Height x Width x Depth 263 mm x 432 mm x 715 mm
10.35 in x 17 in x 28.15 in
Unit dimensions with packagi ng
Height x Width x Depth 461 mm x 600 mm x 1000 mm
18.2 in x 23.62 in x 39.4 in
The model and serial numbers are on a small label located on the rear panel.
Battery type Maintenance free, leak proof, sealed, lead acid
Replacement battery module
This UPS has replaceable battery modules.
Refer to the appropriate replacement battery user manual for installation
instructions.
Contact your dealer or go the APC web site, www.apc.com for
information on replacement batteries.
APCRBC140
Number of battery modules 4 battery modules
Voltage for each battery module
Total voltage for the UPS
Ah rating
96 VDC
± 192 VDC
5.1 Ah per battery module
XLBP cable length 500 mm (19.7 in)
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 5
Electrical
Models Rating
SRT8KXLT
8 kVA/8 kW
SRT8KRMXLT
SRT8KXLT-IEC
SRT8KRMXLT-IEC
SRT8KXLI
SRT8KRMXLI
SRT10KXLT
10 kVA/10 kW
SRT10KRMXLT
SRT10KXLT-IEC
SRT10KRMXLT-IEC
SRT10KXLI
SRT10KRMXLI
Output
Output Frequency 50 Hz/60 Hz ± 3 Hz
Nominal Output
Voltage SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI: 220Vac/230Vac/240Vac
SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT: 208Vac/240Vac
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC: 208Vac/240Vac
Input
Input Frequency 40 Hz-70 Hz
Nominal Input
Voltage SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI: 220Vac/230Vac/240Vac
SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT: 208Vac/240Vac
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC: 208Vac/240Vac
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U6
Remove Battery Modules
Rack-Mount Installation
Refer to the Rail Kit Installation Guide for instructio ns on rai l installation.
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Each battery module weighs 17 kg (37 lb).
• Always practice safe lifting techniques adequate for the weight of the equipment.
• Remove the battery modules before installing the UPS.
• Use the battery module handle to slide the battery modules in or out of the UPS.
• Do not use the battery module handle to lift or carry the battery module.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Loosen the thumbscrews, and remove the battery
compartment doors.
Disconnect and remove four battery modules.
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• Always use the recommended number of screws to secure brackets to the UPS.
• Always use the recommended number of screws and cage nuts to secure the UPS to the rack.
• Always install the UPS at the bottom of the rack.
• Always install the XLBP below the UPS in the rack.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Secure four brackets to the UPS.
Use four screws in each bracket.
Install the rails. Follow the rail installat ion in struction in the
rail kit.
Install six cage nuts.
suo0786a
x4
suo0787a
x8
x8
suo0773a
suo0788a
x3 x3
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 7
Rest the UPS on the rail shelves. Slide the UPS into the rack.
Secure the UPS to the rack.
Use two screws in each bracket.
Install four battery modules.
After the UPS is hardwired to branch circuit mains complete steps 6 -8.
Connect all four battery modules.
Reinstall the battery compartment doors.
Tighten the thumbscrews to secure the doors. Install two bezels.
suo0774a
rail
cleat
suo0775a
x4
x4
suo0776a
suo0777a
suo0778a
x4
suo0779a
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U8
Tower Installation
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is he avy. Each battery module weighs 17 kg (37 lb).
• Always practice safe lifting techniques adequate for the weight of the equipment.
• Remove the battery modules before installing the UPS.
• Use the battery module handle to slide the battery modules in or out of the UPS.
• Do not use the battery module handle to lift or carry the battery module.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Install four battery modules. After the UPS is hardwired to branch circuit mains,
complete steps 2-5.
Connect all four battery modules.
Reinstall the battery compartment doors.
Tighten the thumbscrews to secure the doors.
Install two bezels.
suo0782a
suo0783b
suo0781a
x4
suo0785a
suo
0
7
8
4
a
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 9
Front Panel Features
Rear Panel Features
Note: Refer to the table “Key to identify rear panel features” on page 11, that provides a key to the ca llout numbers for
the rear panel graphics depicted in this manual.
Display interface panel
UPS battery compartment
doors x2
UPS battery connectors x4
Bezels x2
SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT
suo0796a
GROUP 1
20 AMP MAX
GROUP 2
20 AMP MAX
10 100/
Reset
Cons
ole Network
USBSerial
EPO
1234
1 234
NO
NC
HARDWIRED OUTPUT
GROUP 3
30 AMP MAX
suo0772a
192VDC
+
-
BATT COMM
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U10
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC
SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI
GROUP 3
15 AMP MAX
HARDW I RED OUTP UT
10 100/
Reset
Co
nsole Network
USBSerial
EPO
1234
1234
NO
NC
GROUP 2
20 AMP MAX GROUP 1
20 AMP MAX
suo0770a
192VDC
+
-
BATT COMM
HARDW I RED OUTPUT
10 100/
Reset
Co
nsole Network
USBSerial
EPO
1234
1 234
NO
NC
GROUP 2
16 AMP MAX GROUP 1
16 AMP MAX
suo0771a
GROUP 3
10 AMP MAX
192VDC
+
-
BATT COMM
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 11
Key to identify rear panel features
Network port Use the Network port to connect the UPS to the network.
Console port Use the Console port to configure the network management features.
Universal I/O port Use to connect:
• Temperature sensor AP9335T (supplied)
• Temperature/humidity sensor AP9335TH (not supplied)
• Relay input/output connector AP9810 (not supplied), supports two input contacts and one output relay
USB port The USB port is used to connect either a server for native operating system communications, or for software
to communicate with the UP S.
Note: Seri al and USB communication sho ul d not be used simultaneously. Use either the Seria l Com or the
USB port.
Serial Com The Serial Com port is used to communicate wi th the UPS.
Use only interface kits supplied or approved by APC by Schneider Electric. Any other serial interface
cable will be i ncompatible with the UPS connector.
EPO terminal The Emergency Power Off (EPO) terminal allows the user to con nect the UPS to a central EPO system.
Controllable outlet
group 1, with
circuit breaker
Connect electronic devi ces to these out lets.
In the event an overload condition occurs, disconnect none ssential equipment.
Then reset the circuit breaker.
Controllable outlet
group 2, with
circuit breaker
Connect electronic devi ces to these out lets.
In the event an overload condition occurs, disconnect none ssential equipment.
Then reset the circuit breaker.
Controllable outlet
group 3, with
circuit breaker
Connect electronic devi ces to these out lets.
In the event an overload condition occurs, disconnect none ssential equipment.
Then reset the circuit breaker.
AC output
inspection pa nel Remove the panel to inspect the output terminal block wiring configuration.
The terminal block is located behind the inspection cover.
Refer to “Wiring Specifications” on page 9 for hardwire specifications.
AC input
inspection pa nel Remove the panel to inspect the input terminal block wiring configuration.
The terminal block is located behind the inspection cover.
Refer to “Wiring Specifications” on page 9 for hardwire specifications.
AC hardwire
knockouts Remove the 38.1 mm (1.5 in) knockou t panels for AC input and output hardwiring.
Install appropriate strain reliefs (not supplied).
Hardwire box
input/output Remove the box to connect input and output wires to the hardwire terminal blocks.
Chassis ground
screws The UPS and XLBPs have ground screws for connect ing the gr ound lea ds.
Prior to connecting a ground lead, disconnect the UP S from mains power.
External battery
power and
communication
connectors
Use the external battery power and communicati on cables to connect the UP S and XLBP.
XLBPs provide extended runtime during power outages.
The UPS will automatically recognize up to 10 external battery packs.
SmartSlot The SmartSlot can be used to conn ect optio na l man age men t ac cessor ies.
PRL COMM po r t This port is not used with these products.
Reset button Use the Reset button to restart the Network Management Interface.
Note: A restart of the Net work Management Interface does not affect UPS op eration.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U12
Wiring Specifications
* Phase 1 (L1) current while in bypass mode
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Adhere to all national and local electrical codes.
• Wiring should be performed by a qualified electrician.
• Strain reliefs are not supplied with the unit. 38.1 mm (1 1/2 in) Snap in type strain reliefs are recommended.
• The UPS must be wired into a branch circuit, equipped with a circuit breaker rated as specified in the tables below.
• Actual wire size must comply with required ampacity and national and local electrical codes.
Select wire size based on wire insulation, installatio n method, and environmental conditions.
• Recommended terminal screw torque:
16 mm2 or 6 AWG = 5.09 Nm (45 lbf-in)
25 mm2 or 4 AWG = 5.09 Nm (45 lbf-in)
4 mm2 or 12 AWG = 3.969 Nm (35 lbf-in)
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Single Feed
System Wiring Number
of
Phases Voltage Current Full
Load
(nominal)
External Input
Circuit Breaker Mains
(typical)
Wire Size Mains
(typical)
SRT8KXLT
Input 1 208/240 Vac 47 A 60 A / 2- pole 16 mm2
or 6 AWG
Output 1 208/240 Vac 40 A 16 mm2
or 6 AWG
SRT10KXLT
Input 1 208/240 Vac 56 A 70 A / 2- pole 25 mm2
or 4 AWG
Output 1 208/240 Vac 49 A 16 mm2
or 6 AWG
SRT8KXLI
Input 1 220/230/240 Vac 44 A 63 A / 2-pole 16 mm2
or 6 AWG
Output 1 220/230/240 Vac 38 A 16 mm2
or 6 AWG
Input 3 380/400/415 Vac 15 A
44 A* 63 A / 4-pole 16 mm2
or 6 AWG
Output 1 220/230/240 Vac 38 A 16 mm2
or 6 AWG
SRT10KXLI
Input 1 220/230/240 Vac 54 A 80 A / 2-pole 25 mm2
or 4 AWG
Output 1 220/230/240 Vac 47 A 16 mm2
or 6 AWG
Input 3 380/400/415 Vac 18 A
54 A*80 A / 4-pole 25 mm2
or 4 AWG
Output 1 220/230/240 Vac 47 A 16 mm2
or 6 AWG
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 13
Dual Feed
System Wiring Number
of
Phases Voltage Current
Full Load
(nominal)
External
Input
Circuit
Breaker
Mains
(typical)
External
Input
Circuit
Bypass
Mains
(typical)
Wire Size
Mains
(typical)
Wire Size
Bypass
(typical)
SRT8KXLI
Input 1 220/230/240 Vac 44 A 63 A / 2-pole 63 A / 2-pole 16 mm 2
or 6 AWG 16 mm2
or 6 AWG
Input 3 380/400/415 Vac 15 A 20 A / 4-pole 63 A / 2- pole 4 mm2
or 12 AW G 16 mm2
or 6 AWG
Output 1 220/230/240 Vac 38 A 16 mm2
or 6 AWG 16 mm2
or 6 AWG
SRT10KXLI
Input 1 220/230/240 Vac 54 A 80 A / 2-pole 80 A / 2-pole 25 mm 2
or 4 AWG 25 mm2
or 4 AWG
Input 3 380/400/415 Vac 18 A 25 A / 4-pole 80 A / 2- pole 4 mm2
or 12 AW G 25 mm2
or 4 AWG
Output 1 220/230/240 Vac 47 A 16 mm2
or 6 AWG 16 mm2
or 6 AWG
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U14
Hardwire the UPS
Input hardwire
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment.
• Disconnect internal and external batteries before installing or servicing the UPS or connected equipment.
• The UPS contains internal and external batteries that may present a shock hazard even when disconn ected from the mains.
• UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
• Disconnect equipment from the UPS before servicing any equipment.
• Do not use the UPS as a safety disconnect.
• Install appropriate strain reliefs (not supplied). Snap in type strain reliefs are recommended.
• Strip wire insulation 20 mm (.75 inches) to expose the wire. Secure the exposed wire with the lug.
• The jumpers use T25 Torx screws.
• The terminal blocks use 4 mm, (5/32 inch) Hex screws.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Remove the five #2 Phillips screws th at secure the hardwire
box to the UPS.
Pull the hardwire box out of the UPS.
Install strain reliefs (not supplied), for the hardwire
configuration that will be used.
XLI single phase, single feed
Leave bypass and phase jumpers in place. XLI single phase, dual feed
Remove bypass jum per.
x5
output
input
input
NB1L3L2
L1
N
bypass jumper
phase jumper
N
B1 L3 L2 L1
N
bypass jumper
phase jumper
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 15
XLI three phase, single feed
Remove phase jumper. XLI three phase, dual feed
Remove bypass and phase jumpers.
XLT
N
B1 L3 L2 L1
N
bypass jumper
phase jumper
N
B1 L3 L2 L1
N
bypass jumper
phase jumper
L2 L1
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U16
Output hardwire
UPS Configuration
Connect Emergency Power Off feature
For instructions on how to connect the Emergency Power Off (EPO) switch, refer to the Operation and Maintenance
manual on the User Document ati on CD (supplied).
Config ure control l abl e outlet g rou ps
The outlet s on the UPS are gr ouped. To configure the controlled outlet featur es, use the Advanced menus on th e display
interface and navigate to: Main Menu > Configuration > Outlets > Outlet Group.
XLT XLI
Reinstall the hardwire box in the UPS.
Secure the hardwire box with the five screws previously removed.
L2
L1
N
L1
x5
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 17
UPS Display Interface
POWER ON/OFF button
Button illum ination indications:
-No illumination, the UPS and the output
power are off
-White illuminatio n, th e UPS and the output
power are on
-Red illumination, the UPS is on and the
output power is off
Load icon
Disable/mute audible alarm i con
UPS status information
Operation mode icons
ESCAPE button
OK button
UP/DOWN buttons
Controllable outlet grou p st atus icons
Battery status icons
The icons on the LCD display interface screen may vary depending on the installed firmware version.
Load icon: The approximate load capacity percentage is indicated by the number of load bar
sections illuminated. Each bar represents 16% of the load capacity.
Mute icon: Indicates the audible alarm is disabled/mute.
UPS Status Information
The status information field provides key information on the status of the UPS.
The Standard menu will allow the user to select one of the following screens.
The Advanced menu will scroll through the following five screens.
Input Voltage
Output Voltage
Output Frequency
Load
Runtime
In the case of a UPS event, status updates will be displayed defining the event or condition that has occurred.
The display screen illuminates yellow to indicate a Warning and red to indicate an Alert depending on the severity of the event
or condition.
su0870a
Output
230.0
v
On-Line
12 3
LOAD
LOAD
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U18
Operation Mode Icons
On-Line mode: The UPS is supplying conditioned mains power to connected equipment.
Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains
power as long as the input voltage and frequency are within the configured limits.
Green mode: When in Green mode mains power is sent directly to the load.
In the event of a mains power outage, there will be an interruption in power to the load of
up to 8 ms while the UPS switches to On-Line or Battery mode.
When enabling Green mode consideration should be given to devices that may be sensitive to
power fluctu ations.
Battery mode: The UPS is supplying battery power to connected equipment.
Controllable Outlet Group Icons
Controllable Outlet Group Power Available: The number next to the icon iden tifies the specific
outlet groups that have available power.
Controllable Outlet Group Power Not Available: The number next to the icon identifies
specific outlet groups that do not have available power.
Battery Status Icons
Battery Charge Status: Indicates the battery charge status.
Battery Charge In Progress: Indicates the battery is charging.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U 19
Display interface operation
Use the UP/DOWN buttons to scroll through the options. Press the OK button to accept the selected option.
Press the ESC button to return to the previous menu.
Menu overview
The display interface has Standard and Advanced menu screens. The preference for Standard or Advanced menu
selections is made during initial installation and can be changed at any time through the Configuration menu.
The Standard menus include the most commonly used options.
The Advanced menus provide additional options.
Note: Actual menu screens may differ by model and firmware version.
Refer to the UPS Operation Manual for menu configuration details.
LCD display interface angle adjustment
The angle of the LCD display interface can be adjusted for ease in viewing the displayed messages.
1. Remove the front bezel.
2. Locate the button on the bottom of the display interface panel.
3. Press the button and slide the bottom of the LCD display interface screen out. An audible click will be heard
when the screen reaches the maximum angle.
Select models are ENERGY STAR® qualified.
For more information go to www.apc.com/site/recycle/index.cfm/energy-efficiency/energy-star/
su0926a
© 2015 APC by Schnei der Electr ic. APC, the APC logo, Smart-UPS and PowerChute are owned by
Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of
their respective owners.
EN 990-4816C
06/2015
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship
for a period of three (3) years excluding the batteries, which are warranted for two (2) years from the date of purchase.
The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective
products. Repair or replacement of a defective product or part thereof does not extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of
purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product
does not exist or was caused by end user or any third person misuse, negligence, improper installation, testing,
operation or use of the product contrary to SEIT recommendations of specifications. Further, SEIT shall not be liable
for defects resulting from: 1) unauthorized attempts to repair or modify the p roduct, 2) incorrect or inadequate electrical
voltage or connect i on, 3 ) i nap propr iate on site ope ration co nditions, 4) Acts of G od, 5 ) expo sure to the elem ents, or 6)
theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been
altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIE D, BY
OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR
FURNISHED UNDER THIS AGREE MENT OR IN CONNECTION HEREWITH.
SEIT DISCL AIMS ALL IMPL IED WARRANTIES OF ME RCHANTABILITY, SATISFACTION A ND
FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO
OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDE RING OF TECHNICAL OR OTHER
ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND RE MEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE
LIABILITY AND PURCHASER EXCLUSIVE REM EDY FOR ANY B REACH OF SUCH WARRANTIES.
SEIT WARRANT IES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY
THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE
FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQ UENTIAL OR PUNITIVE DAMAGES, ARISING
OUT OF THE USE, SE RVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES
ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY
OR WHETHE R SEIT HAS BEEN ADVISE D IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES.
SPECIFICA LLY, SE IT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE,
WHETHER DIREC T OR INDI RECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF
SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PART IES, OR
OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SE IT LIABILITY
FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGE NCE OR ITS FRAUDULENT
MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LI MITED BY
APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer
support. C ustomers with warranty claims issues may access the SEIT worldwide cus tomer suppor t network throu gh the
APC web site: www.apc.com. Select your country fro m the country selecti on drop down menu. Open the Supp ort tab at
the top of the web page to obtain information for customer support in your region. Products must be returned with
transportation charges prepaid and must be accompan ied by a brief d escription o f the prob lem encoun tered and p roof of
date and place of purchase.