Schneider Electric A9K24306 User Manual
Displayed below is the user manual for A9K24306 by Schneider Electric which is a product in the Circuit Breakers category. This manual has pages.
Related Manuals
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Nov 27, 2013
1
Product data sheet
Characteristics
A9K24306
miniature circuit breaker - iK60N - 3 poles - 6 A
- C curve
Main
Circuit breaker applica-
tion
Distribution
Range of product IK60
Device short name IK60N
Poles description 3P
Number of protected
poles
3
[In] rated current 6 A
Network type AC
Trip unit technology Thermal-magnetic
Curve code C
Utilisation category Category A EN 60947-2
Category A IEC 60947-2
Suitability for isolation Yes EN 60898-1
Yes IEC 60898-1
Complementary
Network frequency 50/60 Hz
[Ue] rated operational voltage 400 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
Breaking capacity 6000 A Icn EN 60898-1 400 V AC 50/60 Hz
6000 A Icn IEC 60898-1 400 V AC 50/60 Hz
Limitation class 3 EN 60898-1
3 IEC 60898-1
[Ui] rated insulation voltage 400 V AC 50/60 Hz EN 60898-1
400 V AC 50/60 Hz IEC 60898-1
[Uimp] rated impulse withstand voltage 4 kV EN 60898-1
4 kV IEC 60898-1
Contact position indicator No
Control type Toggle
Local signalling Without
Mounting mode Removable comb busbar installed
Mounting support DIN rail
9 mm pitches 6
Width 54 mm
Colour White
Connections - terminals Tunnel type terminals top or bottom 1...25 mm² solid 1
Tunnel type terminals top or bottom 0.5...16 mm² flexible with cable end 1
Tunnel type terminals top or bottom 0.5...16 mm² flexible without cable end 1
Tunnel type terminals top or bottom 1.5 mm² flexible without cable end 1...5
Tunnel type terminals top or bottom 1.5 mm² solid 1...5
Tunnel type terminals top or bottom 2.5 mm² flexible without cable end 1...3
Tunnel type terminals top or bottom 2.5 mm² solid 1...3
Wire stripping length 14 mm top or bottom
Tightening torque 2 nm top or bottom
Earth-leakage protection Without
2
Environment
Standards EN 60898-1
IEC 60898-1
IP degree of protection IP3 EN 60947-2
IP3 IEC 60947-2
Pollution degree 2 IEC 60898-1
2 EN 60898-1
Electrical shock protection class Class II front face
Tropicalisation 2 EN/IEC 60068-2-78
Relative humidity 95 %
Operating altitude 0...2000 m
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...85 °C