The binary input REG-K/8x10 is used to connect eight
floating contacts, push-buttons or switches to the bus
system.
The binary input makes a contact supply voltage (SELV)
available which is electrically isolated from the bus
voltage. A power supply is thus not necessary for the
connected floating contacts.
The binary input has a bus coupler. It is installed on a
DIN rail acc. to EN 60715, with the bus connection
made via a bus connecting terminal. A data rail is not
required.
For your safety
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR
ARC FLASH
Safe electrical installation must be carried out only by
skilled professionals. Skilled professionals must prove
profound knowledge in the following areas:
• Connecting to installation networks
• Connecting several electrical devices
• Laying electric cables
• Connecting and establishing KNX networks
• Safety standards, local wiring rules and regulations
Failure to follow these instructions will result in
death or serious injury.
The device may be damaged!
• Never connect the device to an external power
source.
• The binary input circuits must comply with the safety
extra-low voltage conditions (SELV) in accordance
with IEC 60364-4-41.
• Only operate the device according to the specifica-
tions stated in the Technical data.
• All the devices that are installed next to the binary in-
put must be equipped with basic insulation at the very
least.
Failure to follow these instruction can result in
equipment damage.
Binary input introduction
ACover of the bus connecting terminal
BProgramming button/programming LED
COperational LED
DChannel status LEDs
1Set the binary input onto the DIN rail.
2Connect KNX.
¼
WARNING
Risk of fatal injury from electrical current.
The device could be damaged.
Safety clearance must be guaranteed in
accordance with IEC 60664-1. There must be at
least 4 mm between the individual cores of the
230 V supply cable and the KNX line.
Operating and display elements
Installing the binary input
RUN
E 8E 7
E 6
E 5
E 4E 3E 2
E 1
C
D
B
A
E1 0 V 0 V E2 E3 0 V 0 V E4
E5 0 V 0 V E6 E7 0 V 0 V E8
2
1
3
5 mm
12
34
230 V
4 mm
KNX
3Connect the input cables.
|An installation with Y bell wire or J-FY flat
webbed bell wire is permitted.
1Press the programming button.
The programming LED lights up.
2Load the physical address and the application into
the device from the ETS.
The operating LED lights up: The application was loaded
successfully, the device is ready for operation.
Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92500
France
If you have technical questions, please contact the Cus-
tomer Care Centre in your country.
se.com/contact
Putting the binary input into operation
Te c h n i c a l d a t a
Power supply from
bus: DC 24 V / max.18 mA
Insulation voltage: AC 4 kV bus/inputs
Inputs
Contact voltage: max. 10 V (SELV)
Contact current: max. 2 mA, pulsating
Transfer resistance
(between contact and
cable):
max. 500 when contact
closed,
min. 50 k when contact
open
Permitted cable
length: max. 50 m
Ambient temperature
Operation: -5 °C to +45 °C
Storage: -25 °C to +55 °C
Transport: -25 °C to +70 °C
Max. humidity: 93 % relative humidity, no
moisture condensation
Environment: The device is designed for use
at a height of up to 2000 m
above sea level (MSL).
Connections
Inputs, outputs: Screw terminals
Single-core: 1.5 mm2 to 2.5 mm2
Finely stranded
(with core end sleeve): 1.5 mm2 to 2.5 mm2
Bus: Bus connecting terminal
Dimensions
Height x width x
depth: 90 x 72 x 65 mm
Device width: 4 modules
Schneider Electric -Contact
KNX
+ -
E1
E2
E3
E4
Uk
E5
E6
E7
E8
0 V
0 V
0 V
0 V
Uk
0 V
0 V
0 V
0 V
Schneider Electric Limited
Telford, TF3 3 BL, UK
UK Representative
Stafford Park 5
SpaceLogic KNX Binary input REG-K/8x10
Operating instructions
Art. no. MTN644592
en
RUN
E 8E 7
E 6
E 5
E 4E 3E 2
E 1
V6445-562-01 11/21