Schneider Electric MTN6503-0201 User Manual
Displayed below is the user manual for MTN6503-0201 by Schneider Electric which is a product in the Gateways/Controllers category. This manual has pages.
Related Manuals
© 2013 Schneider Electric 1
Metering Gateway Modbus REG-K
MTN6503-0201
Application Metering Gateway 7602/1.0
Metering Gateway Modbus REG-K MTN6503-0201© Me rten 200902/13
|Many parameters and their settings are depend-
ent on the settings you have already made for oth-
er parameters. This means that some parameters
will appear or disappear and the values available
for selection will change according to settings you
have already made. These dependencies have
not been shown in the table for reasons of clarity.
All settings are always shown.
|Configurable times are set via the base and factor
parameters. The actual time is given by the multi-
plication of the two values. Example:
Base = 1 second, Factor = 3
Actual time = 3 seconds
|The bold values in a table are the values set dur-
ing factory configuration.
Table of contents
The KNX Metering Gateway is a device which connects
meters via the Modbus open standard to KNX. The
Modbus open standard allows you to receive a more in-
depth analysis of consumption in all areas of your build-
ing.
You can connect up to 10 of the following types of me-
ters based on Modbus remote terminal unit (RTU):
• Schneider Electric energy meters
• Schneider Electric power meters
• Schneider Electric Smart Interface Modules (SIM10M
module)
• Non-Schneider Electric Modbus RTU devices (offer-
ing you greater flexibility)
With the information which the KNX Metering Gateway
provides you can visualise energy or media consump-
tion. This can also be used to reduce consumption
through the use of control strategies within the KNX net-
work.
You can choose from 17 different pre-prepared tem-
plates for the meters and devices in order to quickly
connect to a KNX network. Each template contains the
20 most frequently needed Modbus values for simple
configuration.
From each connected Modbus RTU device the KNX
Metering Gateway can read up to an additional 40 Mod-
bus register values and transfer this data to the KNX
network.
You can read up to 10 meters using one KNX Metering
gateway. This makes the Gateway very cost-efficient.
Integrating a SIM10 module makes it possible to deter-
mine and visualise gas and water consumption.
The KNX Metering Gateway is also suitable for retrofit-
ting or for retroactive connection of existing Modbus
systems to KNX because it is fully compatible with me-
ters from other manufacturers.
The application is influenced by the following events:
•ETS download
• Bus voltage failure
•Bus voltage recovery
The behaviour differs according to function and can in-
fluence the measuring and monitoring function. There-
fore, you can set the behaviour using parameters at the
corresponding point. Refer to the chapter in question
for a precise description.
Application Metering Gateway 7602/1.0
•Function overview 1
• Behaviour of the application 1
• Modbus settings 2
• Metering device templates 3
– Metering device x 3
– Voltage and current monitor 4
–Power monitor 4
– Consumption monitor 5
–Template for SIM10M module 6
• Direct access to Modbus register 7
– Access to register X 7
– Modbus register X 7
• Diagnostic block 8
• Overview of parameters 9
• Overview of communication objects 11
Function overview
Behaviour of the application
2© 2013 Schneider Electric
Metering Gateway Modbus REG-K
MTN6503-0201
Modbus settings
The gateway always works in master mode and the
connected Modbus devices work in slave mode. Com-
munication from KNX bus to the Modbus is not possi-
ble.
Baudrate setting
The Baudrate is set depending on the distance be-
tween Modbus RTU devices. For instance with a Baud
rate of 9,600 bit/sec the maximum communication dis-
tance between 1 - 15 Modbus RTU devices is 1,200
metres. With the Baud rate of 19,200 bit/sec the maxi-
mum communication distance is 900 metres, as the ta-
ble shows below:
Parity refers to the technique of checking if transmis-
sion has been successful when transmitting between
devices. It lets you know if some data has been lost dur-
ing transmission.
Setting of parity
The Modbus supports only 11 bit frames. The ETS ap-
plication sets stop bits automatically depending on the
parity setting. "Parity" refers to the number of 1s in a giv-
en binary number. Odd parity means there are an odd
number of 1s and even parity means that there are an
even number of 1s. Parity bits are used as a means of
error detection as digital data is transmitted and re-
ceived. Both the Gateway and Meter must always be set
to the same as one another, odd, even or none. The de-
fault parity mode of Modbus is "even" parity.
|Make sure that all connected meters are always
set to the same parity as one another, odd, even or
one.
• Parity = None: choose between one and two stop bits
• Parity = Even: one stop bit is set
• Parity = Odd: one stop bit is set
|When parity is set to „None“ it is necessary to pre-
set meters PM2x0, PM7x0 and PM8x0 to one stop
bit (all other meters require a setting of two stop
bits here). This means that under „None“ parity
PM2x0, Pm7x0 and PM8x0 meters cannot be
combined with other meters. In their case it is nec-
essary to work with „Odd“ or „Even“ parity.
Parameters
Delay between frames
Some devices require considerable time after end of re-
sponse until they are ready to receive the following re-
quest from the master. In particular Schneider Electric
SEPAM power devices and legacy slave devices. As
they are slow in dealing with the original request they
may miss the following request.
The time between requests should be less than 3.5
characters according to the Modbus specification.
However, these legacy devices need more time. The
parameter „Delay between frames“ solves this problem.
The time is automatically adapted to 3.5 characters of
the transmission speed, but you have the choice to in-
crease this time if you need to support such slow legacy
devices.
Parameters
Start-up delay
The parameter „Start-up delay“ specifies from what
point measured values are counted in the application.
After an ETS download or bus voltage recovery, the de-
vice starts measuring the connected channels when
the start-up delay is complete.
Parameters
Modbus settings
Baudrate setting Maximum communication
distance for 1 to 15 Modbus
RTU devices
(Typical with Belden 3105A
cables)
9,600 bit/sec 1,200 m
19,200 bit/sec 900 m
Modbus settings
Parameters Setting
Baudrate setting (bit/sec) 1,200
2,400
4,800
9,600
19,200
Parity None
Even
Odd
Stop bit One stop bit
Two stop bits
Modbus settings
Parameters Setting
Delay between frames
1 ms* factor (50 .. 100)
Disabled
50 - 100 adjustable in steps of 10
Modbus Settings
Parameters Setting
Start-up delay
1 s * factor (1-250)
5
adjustable in single steps
© 2013 Schneider Electric 3
Metering Gateway Modbus REG-K
MTN6503-0201
Metering device templates
Pre-installed ETS templates provide you with the 20
most frequently needed values which makes configura-
tion much easier and quicker. This also means there is
no need to map the Modbus register addresses to KNX.
The ETS application has special templates which you
use to implement the Schneider Electric Modbus RTU
based energy or power meters and SIM10M module.
These devices are outlined in the table below:
Metering device x
You can select the metering device you require from the
parameter „Type of metering device“. These are the 17
devices from the previous table.
Each connected device has a unique address, between
1 and 247, as per the Modbus addressing protocol. To
identify the device, you need to set its address at the
parameter „Address of metering device“.
The template allows you to to monitor different kinds of
values. To achieve this it has three monitoring functions
which you can enable by parameter. These are:
• „Voltage and current monitor“
• „Power monitor“
• „Consumption monitor“
With the parameter „Sending behaviour“ you can spec-
ify how all values of the monitors are sent. For a cyclical
sending, you can set the parameter „Time base“ to ei-
ther 1 second or 1 minute. The chosen setting applies
to all values of the whole template.
Parameters
Metering device templates
Supported devic-
es
Typ e Name Description
Energy/power meter PM9C power meter for the installation
distributor (cabinet) for measure-
ment with current transformers
Energy/power meter PM210 current, voltage, power and ener-
gy (each active/idle/apparent),
frequency and power factor
Energy/power meter PM710 slave pointer (min/max), Total
Harmonic Distortion (THD) I/THD
U harmonic distortion
Energy/power meter PM750 like PM710 with alarm contact
Energy/power meter PM810 like PM750 with 4-quadrant
measurement
Energy/power meter PM820 like PM810 with additional inte-
grated memory for logging events
and analysis of harmonics.
Energy/power meter PM850 like PM810 with harmonic content
Energy/power meter PM870 like PM850 with additional detec-
tion and logging of peaks of volt-
age and current
Energy/power meter PM1200 like PM210 withTHD I/THD U har-
monic distortion
Energy/power meter DM6200 Ampere, volt, frequency meter
Energy/power meter iEM3150 direct measurement to 63A,
records energy
Energy/power meter iEM3155 like iEM3150 with alarm contact,
MID compliant
Energy/power meter iEM3250 transformer measurement
Energy/power meter iEM3255 like IEM3250 with alarm contact,
MID compliant
Energy/power meter PM3250 4-quadrant measurement, THD I/
THD U harmonic distortion
Energy/power meter PM3255 like PM3250 with alarm
Smart Interface
Module
SIM10M input module for pulse counting.
Metering device x
Parameters Setting
Type of metering device Disabled
PM9C
PM210
PM710/PM750
PM8x0
DM1200
DM6200
iEM3150
iEM3155
iEM3250
iEM3255
PM3250/PM3255
SIM10M
Address of metering device 1 ..247
Read Modbus values after start Enabled
Disabled
Voltage and current monitor Enabled
Disabled
Power monitor Enabled
Disabled
Consumption monitor Enabled
Disabled
Sending behaviour Cyclically (as configured
time)
If value was changed
Time base 1 sec
1 min
4© 2013 Schneider Electric
Metering Gateway Modbus REG-K
MTN6503-0201
Metering device templates
Voltage and current monitor
You can set the parameter „Voltage and current moni-
tor“ to read Modbus values after start. Values for voltage
and current are available for each phase (1-3) seperate-
ly. When you enable the voltage or current of phase x
you can then set their cyclic sending with integers of 1
second or 1 minute, with a base as configured in previ-
ous parameter „Time base“.
Parameters
Power monitor
The power monitor allows you to enable parameters as
follows:
• Power factor (power factor in cosΦ)
• Active power x, for each phase 1-3
• Reactive power x, for each phase 1-3
• Total active power (total power in kW), sum of phases
1-3
• Total reactive power (total power in kVAr), sum of
phases 1-3
• Total apparent power (total power in kVA), sum of
phases 1-3
With each of these you can then set their cyclic sending
with integers of 1 second or 1 minute, with a base as
configured in previous parameter „Time base“.
Parameters
Voltage and current monitor
Parameters Setting
Voltage unit Millivolt (DPT 9.020)
Volt (DPT 9.*)
Voltage of phase x Enabled
Disabled
Cyclic voltage sending
Time base * factor (1-250)
2, 1 .. 250
Current unit Milliampere (DPT 9.021)
Ampere (DPT 9.*)
Current of phase x Enabled
Disabled
Cyclic current sending
Time base * factor (1-250)
2, 1 .. 250
Frequency Enabled
Disabled
Cyclic frequency sending
Time base * factor (1-250)
2, 1 .. 250
Power monitor
Parameters Setting
Power factor (cos phi) Enabled
Disabled
Cyclic power factor sending
Time base * factor (1-250)
2, 1 .. 250
Active power x Enabled
Disabled
Cyclic active power factor sending
Time base * factor (1-250)
2, 1 .. 250
Power datapoint Power kW (DPT 9.024), 2 Byte
Value power W (DTP 14.056), 4
Byte
Reactive power x Enabled
Disabled
Cyclic reactive power factor send-
ing
Time base * factor (1-250)
2, 1 .. 250
Power datapoint Power kW (DTP 9.024), 2 Byte
Value power W (DTP 14.056), 4
Byte
Total ac tive power
Total reactive powe r
Total apparent power
Enabled
Disabled
Cyclic total active / reactive / apar-
ent power factor sending
Time base * factor (1-250)
2, 1 .. 250
Power datapoint Power kW (DTP 9.024), 2 Byte
Value power W (DTP 14.056), 4
Byte
© 2013 Schneider Electric 5
Metering Gateway Modbus REG-K
MTN6503-0201
Metering device templates
Consumption monitor
With the consumption monitor you can enable the fol-
lowing:
• Active energy counter (total energy - active in kWh)
• Reactive energy counter (total energy - reactive - in
kVArh)
• Apparent energy counter (total energy - apparent - in
kVAh)
These monitor energy consumption within the period.
You can then set their cyclic sending with integers of 1
second or 1 minute, with a base as configured in the
previous parameter „Time base“.
The energy counters each have 3 possible consump-
tion object types which you can set to Active energy,
Active energy kWh or Active energy V64.
Parameters
Application Example
Requirements
• measure and visualise how much energy is used
lighting an office building
• measure the gas and water consumption in the build-
ing
• monitor the quality of the network to ensure the oper-
ational safety of IT equipment
Solution
• install an iEM3150 meter to record the energy con-
sumed by the lighting
• install an iEM3255 meter to determine the network
quality
• install a SIM10M module to measure gas and water
consumption via impulse
• connect the devices to each other via Modbus
By connecting the KNX Metering Gateway to the Mod-
bus line, the data can be configured easily using the
templates supplied and then transmitted to the KNX
bus. The consumption data is then conveniently dis-
played for facility management in their offices on a
touch panel. Incoming alarms triggered by fluctuations
in the network quality are also displayed.
Communication objects
The following communication objects can be selected:
Consumption monitor
Parameters Setting
Active energy counter Enabled
Disabled
Cyclic active consumption send-
ing
Time base * factor (1-250)
2, 1 .. 250
Consumption object type Active energy (DPT 13.010)
Active energy kWh (DPT
13.013)
Active energy V64 (DPT 29.010)
Reactive energy counter Enabled
Disabled
Cyclic reactive consumption send-
ing
Time base * factor (1-250)
2, 1 .. 250
Consumption object type Reactive energy (DPT 13.012)
Reactive energy kVArh (DPT
13.015)
Reactive energy V64 (DPT
29.012)
Apparent energy counter Enabled
Disabled
Cyclic apparent consumption
sending
Time base * factor (1-250)
2, 1 .. 250
Consumption object type Apparent energy (DPT 13.011)
Apparent energy kVAh (DPT
13.014)
Apparent energy V64 (DPT
29.011)
Function Object name Type Prio Flags Behaviour
Metering
device x
Voltage of phase
x
2 Byte Low CTR Send/read
Metering
device x
Current phase x 2 Byte Low CTR Send/read
Metering
device x
Frequency 4 Byte Low CTR Send/read
Metering
device x
Power factor 4 Byte Low CTR Send/read
Metering
device x
Active power kW
x
2/4
Byte
Low CTR Send/read
Metering
device x
Reactive power
kVAr x
2/4
Byte
Low CTR Send/read
Metering
device x
Total active pow-
er kW x
2/4
Byte
Low CTR Send/read
Metering
device x
Total react ive
power kVAr x
2/4
Byte
Low CTR Send/read
Metering
device x
Total apparent
power kVA x
2/4
Byte
Low CTR Send/read
Metering
device x
Active energy
counter kWh
4/8
Byte
Low CTR Send/read
Metering
device x
Reactive energy
counter kVArh
4/8
Byte
Low CTR Send/read
Metering
device x
Apparent ener-
gy counter kVAh
4/8
Byte
Low CTR Send/read
6© 2013 Schneider Electric
Metering Gateway Modbus REG-K
MTN6503-0201
Template for SIM10M
Within the KNX Metering Gateway you can also connect
to a SIM10M module allowing you to:
• read energy consumption
• read the buildings‘ pulse meters that measure gas
and water consumption
• visualise these values
The SIM10M module offers you two different functions:
1. six logic counters with pulse acquisition and on/off
detection by internal 3.6 V DC power and pull-up resis-
tors.
2. two analogue inputs with a range of 0-10 V DC exter-
nally powered.
The SIM10M module is able to control and count the
pulses of up to six simple meters with pulse or relay out-
put.
The binary counters each have a scale, multiple and di-
vide factor implemented. This is because the ETS ap-
plication does not support decimal points, so in each
case there needs to be a multiple and divide factor to
achieve the required value, e.g. when scale factor =
18.32, multiple factor is 1832 and divide factor is 100.
Typical use case of SIM10M module and setting of
ETS application
When connecting the SIM10M module and the power
and pulse meters, you must set the amount of pulses
which are defined for 1kWh (or m3 for gas and water).
Those constants are set in the ETS application (preset
to 3,200 pulses and 1,000 imp/kWh). The result is sent
to the KNX bus via the communication object.
Reset of binary counter
The reset datapoint reacts only to a „true“ telegram. A
“false“ telegram is ignored.
Communication objects
The following communication objects can be selected:
Parameters
Template for SIM10M
Function Object name Type Prio Flags Behaviour
SIM10M
module x
Binary counter x 4 Byte Low CTR Send/read
SIM10M
module x
Analogue input x 2 Byte Low CTR Send/read
SIM10M
module x
Reset of binary
counter x
1 bit Low CW Send
SIM10M module 1
Parameter Setting
Address of SIM10M 1 .. 247
Read input values after start Enabled
Disabled
Binary counter 0 .. 5 Enabled
Disabled
Cyclic object sending
Time base * factor (1 .. 250)
2, 1 .. 250
Multiplication factor 1, 1 .. 10,000
Division factor
(Data*multi / div factor)
1, 1 .. 10,000
Voltage unit Millivolt (DPT 9.020)
Volt (DPT 9.0*)
Analogue input 0, 1 Enabled
Disabled
Cyclic object sending
Time base * factor (1 .. 250)
2, 1 .. 250
Sending behaviour Cyclically (as configured
time)
If value was changed
Time base 1 sec
1 min
© 2013 Schneider Electric 7
Metering Gateway Modbus REG-K
MTN6503-0201
Direct access to Modbus register
The KNX Metering Gateway is only able to read basic
Modbus register values. For access to other Modbus
registers you must use an additional functionality, „Ac-
cess to Register x“. Within this parameter you can se-
lect which registers you wish to access. The registers
are grouped in five groups with eight registers each.
Access to Modbus register x
By enabling or disabling groups of registers, you can
then disable or enable access to individual registers.
Modbus register x
You can set parameter „Register type“ to either „Read
holding register“ (set as default) or „Read input regis-
ter“.
With the Read input register you can read from 1 to 125
contiguous input registers in a remote device. The Re-
quest protocol date unit (PDU) specifies the starting
register address and the number of registers. In the
PDU addresses start from zero, therefore registers
numbered 1 - 16 are addressed as 0 - 15.
You can set parameter „Modbus data is“ to Unsigned, to
Float or to Float (words are swapped).
You can set the Modbus value to convert to 2, 4 or 8
Byte. Within this datapoint the object type can be set to
„unsigned“, „signed“ or „float“. You must be careful
when setting the Modbus value as each datapoint has
a set range. If the value falls out of this range the send-
ing of the value will be blocked and will not reach the
KNX bus.
Parameters
Communication objects
The following communication objects can be selected:
Direct access to Modbus register
Direct access to Modbus regis-
ter
Parameters Setting
Access to Modbus register 1 - 8 Disabled
Enabled
Access to Modbus register 9- 16 Disabled
Enabled
Access to Modbus register 17 - 24 Disabled
Enabled
Access to Modbus register 25 - 32 Disabled
Enabled
Access to Modbus register 33- 40 Disabled
Enabled
Access to Modbus register x
Parameters Setting
Access to Modbus register x Disabled
Enabled
Datapoint Range
2 Byte unsigned 0 .. 65 535
2 Byte signed -32 768 .. 32 767
2 Byte float -670 760.. 670 760
4 Byte unsigned 0 .. 4 294 967 295
4 Byte signed -2 147 483 648.. 2 147 483 647
4 Byte float Object_x Byte
8 Byte unsigned 0 .. 18 446 744 073 709 551 615
Modbus register x - Modbus
side
Parameters Setting
Address of modbus device 1 .. 247
Register address 1,000 .. 50,000
Register type Read holding register
Read input register
Modbus data is Unsigned
Float
Float (words are swapped)
Multiplication factor 1, 1 .. 10,000
Division factor
(data*multi/div factor)
1, 1 .. 10,000
Modbus register x - KNX side
Parameters Setting
Quantity of coils 1
(Modbus datapoint) 2
4
Modbus value convert to 2 Byte
4 Byte
8 Byte
Type of object 2/4 Byte unsigned
2/4 Byte signed
2/4 Byte float
Time base 1 sec
1 min
Cyclic sending
Time base * factor (1 .. 250)
2, 1 .. 10,000
Sending behaviour Cyclically (as configured
time)
If value was changed
Function Object name Type Prio Flags Behaviour
Access to
register x
Object_x Byte 2/4/8
Byte
Low CTR Send/read
8© 2013 Schneider Electric
Metering Gateway Modbus REG-K
MTN6503-0201
Diagnostic block
The Metering Gateway supports two different communi-
cation objects for the diagnostics of modbus devices.
These are „Active Modbus status“ and „Passive Mod-
bus status“.
The „Active Modbus status“ object sends an error code
to the KNX bus after recognising that a problem exists
on the Modbus. The sending of this status is controlled
by the parameter „Sending behaviour“. The status will
either be sent every time after reading of register (mini-
mum 20 times per device template) or it will only be sent
if Modbus exception code is changed. The range of ex-
ception codes is 0 - 6. All information about errors is
stored in external FRAM memory.
The last reported status of a slave can be forced to be
sent by the "Active Modbus status" object by sending
the slave ID to the "Passive Modbus status object.
When you enable the parameter „Reset“, a reset tele-
gram is sent and the gateway will stop reading all Mod-
bus registers and make a restart. If the parameter
"Reset" is enabled it is possible to restart the gateway
with a "1"-telegram on object "Reset of gateway".
The table of error codes is listed below:
Communication objects
The following communication objects can be selected:
Parameters
Diagnostic block
Excep-
tion
code
Name Description
0 hex No error
(slave is ok)
01 hex Illegal
function
The function code received in the query is
not an allowable action for the slave. This
may be because the function code is only
applicable to newer devices, and was not im-
plemented in the unit selected.
It could also indicate that the slave is in the
wrong state to process a request of this type,
for example because it is unconfigured and
is being asked to return register values, If a
Poll Program Complete command was is-
sued, this code indicates that no program
function proceeds
02 hex Illegal data
address
The data address received in the query is not
an allowable address for the slave. The com-
bination of reference number and transfer
length is invalid.
03 hex Illegal
data value
A value contained in the query data field is
not an allowable value for the slave. This in-
dicates a fault in the structure of remainder of
a complex request, e.g. that the implied
length is incorrect.
It specifically does NOT mean that a data
item submitted for storage in a register has a
value outside the expectation of the applica-
tion program since the Modbus protocol is
unaware of the significance of any particular
value of any particular register.
04 hex Slave de-
vice failure
An unrecoverable error occurred while the
slave was attempting to perform the request-
ed action.
05 hex Acknowl-
edge
Specialized use in conjunction with program-
ming commands.
The slave has accepted the request and is
processing it, but a long duration of time will
be needed for it to do so. This response is re-
turned to prevent a timeout error from occur-
ring in the master. The master can issue a
Poll Program Complete message to deter-
mine if programming is complete.
06 hex Slave de-
vice busy
Specialized use in conjunction with program-
ming commands. The slave is engaged in
processing a long-duration program com-
mand. The master should re-transmit the
message later when the slave is free.
Function Object name Type Prio Flags Behaviour
Diagnostic
block
Active Modbus
status
2 Byte Low CRT Send/read
Diagnostic
block
Passive Modbus
status
1 Byte Low CRT
W
Receive/
read
Diagnostic
block
Reset of gateway 1 bit Low CW Receive
Diagnostic block
Parameters Setting
Diagnostic block Disabled
Enabled
Active status Disabled
Enabled
Sending behaviour Evey time
If value was changed
Passive status Disabled
Enabled
Reset Disabled
Enabled
Excep-
tion
code
Name Description
© 2013 Schneider Electric 9
Metering Gateway Modbus REG-K
MTN6503-0201
Overview of parameters
Overview of parameters
Modbus settings
Parameters Setting
Baudrate setting (bit/sec) 1,200
2,400
4,800
9,600
19,200
Parity None
Even
Odd
Stop bits One stop bit
Delay between frames
1 msec * factor (50..100)
Disabled
50
60
70
80
90
100
Start-up delay
1s * factor (1 .. 250)
5, 1 .. 250
Metering device templates
Parameters Setting
Metering device x Enabled
Disabled
Metering device x
Parameters Setting
Type of metering device Disabled
PM9C
PM210
PM710/PM750
PM8x0
PM1200
DM6200
iEM3150
iEM3155
iEM3250
iEM3255
PM3250/PM3255
SIM10M
Address of metering device/
SIM10 module
1 .. 247
Read Modbus values after start Enabled
Disabled
Voltage and current monitor Enabled
Disabled
Power monitor Enabled
Disabled
Consumption monitor Enabled
Disabled
Sending behaviour Cyclically (as configured
time)
If value was changed
Time base 1 sec
1 min
Voltage and current monitor
Parameters Setting
Voltage unit Millivolt (DPT 9.020)
Volt (DPT 9.*)
Voltage of phase 1, 2, 3 Enabled
Disabled
Cyclic voltage sending
Time base * factor (1 . 250)
2, 1 .. 250
Current unit Milliampere (DPT 9.021)
Ampere (DPT 9.*)
Current of phase x Enabled
Disabled
Cyclic current sending
Time base * factor(1 . 250)
2, 1 .. 250
Frequency Enabled
Disabled
Cyclic frequency sending
Time base * factor(1 . 250)
2, 1 .. 250
Power monitor
Parameters Setting
Power factor (cos phi) Enabled
Disabled
Cyclic power factor sending
Time base * factor (1 .. 250)
2, 1 .. 250
Active power x Enabled
Disabled
Cyclic active power sending
Time base * factor (1 .. 2500
2, 1 .. 250
Power datapoint Power kW (DTP 9.024), 2 Byte
Value power W (DTP14.056), 4
Byte
Reactive power x Enabled
Disabled
Cyclic reactive power sending
Time base * factor (1 .. 250)
2, 1 .. 250
Power datapoint Power kW (DTP 9.024), 2 Byte
Value power W (DTP 14.056), 4
Byte
Total ac tive power
Total reactive powe r
Total apparent power
Enabled
Disabled
Cyclic total x power sending
Time base * factor (1 .. 2500
2, 1 .. 250
Power datapoint Power kW (DTP 9.024), 2 Byte
Value power W (DTP 14.056), 4
Byte
Metering device x
Parameters Setting
10 © 2013 Schneider Electric
Metering Gateway Modbus REG-K
MTN6503-0201
Overview of parameters
Consumption monitor
Parameters Setting
Active energy counter Enabled
Disabled
Cyclic active consumption sending
Time base * factor (1 .. 2500
2, 1 .. 250
Consumption object type Active energy (DPT 13.010)
Active energy kWh(DPT
13.013)
Active energy V64 (DPT
29.010)
Reactive energy counter Enabled
Disabled
Cyclic reactive consumption sending
Time base * factor (1 .. 2500
2, 1 .. 250
Consumption object type Reactive energy (DPT
13.012)
Reactive energy kVArh
(DPT 13.015)
Reactive energy V64 (DPT
29.012)
Apparent energy counter Enabled
Disabled
Cyclic apparent consumption send-
ing
Time base * factor (1 .. 2500
2, 1 .. 250
Consumption object type Apparent energy (DPT
13.011)
Apparent energy kVAh
(DPT 13.014)
Apparent energy V64 (DPT
29.011)
Direct access to Modbus register
Parameters Setting
Access to Modbus register 1 - 8 Enabled
Disabled
Access to Modbus register 9 - 16 Enabled
Disabled
Access to Modbus register 17 - 24 Enabled
Disabled
Access to Modbus register 25 - 32 Enabled
Disabled
Access to Modbus register 33 - 40 Enabled
Disabled
Access to Modbus register x
Parameters Setting
Access to Modbus register x Enabled
Disabled
Modbus register x - Modbus side
Parameters Setting
Address of Modbus device 1 .. 247
Register address 1 .. 50,000
Register type Read holding register
Read input register
Modbus data is Unsigned
Float
Float (words are swapped)
Multiplication factor 1, 1 .. 10,000
Division factor
(Data*multi/div factor)
1, 1 .. 10,000
Modbus register x - KNX side
Parameters Setting
Quantity of coils
(Modbus datapoint)
1
2
4
Modbus value convert to 2 Byte
4 Byte
8 Byte
Type of object 2/4 Byte Unsigned
2/4 Byte signed
2/4 Byte Float
Time base 1 sec
1 min
Cyclic sending
Time base * factor (1 .. 250)
2, 1 .. 250
Sending behaviour Cyclically (as configured
time)
If value was changed
Diagnostic block
Parameters Setting
Diagnostic block Disabled
Enabled
Active status Disabled
Enabled
Sending behaviour Every time
If value was changed
Passive status Disabled
Enabled
Reset Disabled
Enabled
© 2013 Schneider Electric 11
Metering Gateway Modbus REG-K
MTN6503-0201
Overview of communication objects
Metering Device x
SIM10M module x
Access to Register x
Diagnostic block
If you have technical questions, please contact the Cus-
tomer Care Centre in your country.
www.schneider-electric.com
Overview of communication objects
Function Object name Type Prio Flags Behaviour
Metering
device x
Voltage phase x 2 Byte Low CTR Send/read
Metering
device x
Current phase x 2 Byte Low CTR Send/read
Metering
device x
Frequency 4 Byte Low CTR Send/read
Metering
device x
Power factor 4 Byte Low CTR Send/read
Metering
device x
Active power kW
x
2/4
Byte
Low CTR Send/read
Metering
device x
Reactive power
kVAr x
2/4
Byte
Low CTR Send/read
Metering
device x
Total ac tive pow-
er kW x
2/4
Byte
Low CTR Send/read
Metering
device x
Total reactive
power kVAr x
2/4
Byte
Low CTR Send/read
Metering
device x
Total ap parent
power kVA x
2/4
Byte
Low CTR Send/read
Metering
device x
Active energy
counter kWh
4/8
Byte
Low CTR Send/read
Metering
device x
Reactive energy
counter kVArh
4/8
Byte
Low CTR Send/read
Metering
device x
Apparent ener-
gy counter kVAh
4/8
Byte
Low CTR Send/read
Function Object name Type Prio Flags Behaviour
SIM10M
module x
Binary counter x 4 Byte Low CTR Send/read
SIM10M
module x
Analogue input x 2 Byte Low CTR Send/read
SIM10M
module x
Reset of binary
counter x
1 bit Low CW Send
Function Object name Type Prio Flags Behaviour
Access to
register x
Object_2 Byte 2 Byte Low CTR Send/read
Access to
register x
Object_4 Byte 4 Byte Low CTR Send/read
Access to
register x
Object_8 Byte 8 Byte Low CTR Send/read
Function Object name Type Prio Flags Behaviour
Diagnostic
block
Active Modbus
status
2 Byte Low CRT Send/read
Diagnostic
block
Passive Modbus
status
1 Byte Low CRT
W
Receive/
read
Diagnostic
block
Reset of gateway 1 bit Low CW Receive
Schneider Electric Industries SAS