InRow®Direct Expansion Air Conditioners
ACRD300 and ACCU30000 Series
Technical Specifications
Up to 30 kW
990-91209A-001
Release Date: 05/2019
www.schneider-electric.com

Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.

ACRD300 and ACCU30000 Series
Table of Contents
Technical Data.............................................................................................5
Model Identification.....................................................................................5
Overview ...................................................................................................7
Capacities ............................................................................................7
Room Air Distribution ............................................................................7
Compliance Approval ............................................................................8
Working Conditions and Environmental Limits.........................................9
Scalable Solution for Critical Environments................................................. 11
InRow Advantages.............................................................................. 11
Scalable for High Density .................................................................... 11
Standard Features and Options .................................................................12
Standard Features ..............................................................................12
Optional Features ...............................................................................14
Microprocessor Controller .........................................................................16
Display Interface.................................................................................16
Microprocessor Controller....................................................................16
Open Architecture...............................................................................16
Control Type.......................................................................................16
Functions ...........................................................................................17
Control...............................................................................................17
Alarms ...............................................................................................17
Component Identification ..........................................................................19
External Components..........................................................................19
Internal Components...........................................................................21
Electrical Panels .................................................................................25
Performance Specifications.......................................................................32
Cooling Capacity ................................................................................32
General Data......................................................................................33
Altitude Correction Factors ..................................................................35
Electrical Data ....................................................................................36
Sound Data ........................................................................................37
Dimensions and Weights...........................................................................38
Indoor Unit .........................................................................................38
Outdoor Unit.......................................................................................39
Service Access...................................................................................40
Airflow Clearance................................................................................41
Piping and Electrical Access Locations ................................................. 42
Refrigeration Piping Diagram.....................................................................47
Facility Planning........................................................................................48
990-91209A-001 3


Technical Data ACRD300 and ACCU30000 Series
Technical Data
Model Identification
Indoor Unit
The model number can be found on
the outside of the shipping crate and
on the name plate located on the unit
as shown. Use the table below to
verify that the equipment is the right
type and voltage.
REAR
NAME PLATE
na4402b
NOTE: The unit is not to be accessed by the general public.
SKU Voltage Frequency 65 kAIC Power Feed Number of
Fan Power
Supplies
Drainage
System
Airflow
Pattern
ACRD300 220 V~ 50 Hz No Dual feed 1 Condensate
pump
Rear to front
ACRD300D 220 V~ 50 Hz No Dual feed 2 Condensate
pump
Rear to front
ACRD300G 220 V~ 50 Hz No Dual feed 1 Gravity drain Rear to front
ACRD300GD 220 V~ 50 Hz No Dual feed 2 Gravity drain Rear to front
ACRD300-LT 220 V~ 50 Hz No Dual feed 1 Condensate
pump
Rear to front
ACRD300D-LT 220 V~ 50 Hz No Dual feed 2 Condensate
pump
Rear to front
ACRD300G-LT 220 V~ 50 Hz No Dual feed 1 Gravity drain Rear to front
ACRD300GD-LT 220 V~ 50 Hz No Dual feed 2 Gravity drain Rear to front
ACRD301 100–120 V~* /
200–240 V~
50/60 Hz Yes Dual feed 1 Condensate
pump
Rear to front
ACRD301G 100–120 V~* /
200–240 V~
50/60 Hz Yes Dual feed 1 Gravity drain Rear to front
ACRD306 100–120 V~* /
200–240 V~
50/60 Hz Yes Dual feed 1 Condensate
pump
Rear to front
ACRD306G 100–120 V~* /
200–240 V~
50/60 Hz Yes Dual feed 1 Gravity drain Rear to front
ACRD307 100–120 V~* /
200–240 V~
50/60 Hz Yes Dual feed 1 Condensate
pump
Rear to front
ACRD307G 100–120 V~* /
200–240 V~
50/60 Hz Yes Dual feed 1 Gravity drain Rear to front
*Configure proper voltage before applying power to the cooling unit.
990-91209A-001 5

ACRD300 and ACCU30000 Series Technical Data
Outdoor Unit
The model number can be found on
the outside of the shipping crate and
on the name plate located on the unit
as shown. Use the table below to
verify that the equipment is the right
type and voltage.
na6990a
NAME PLATE
NOTE: The unit is not to be accessed by the general public.
SKU Voltage Frequency 65 kAIC Power Feed Accumulator Outdoor Temperature Minimum
Operation Temperature
ACCU30301 380 V 3~ 50 Hz No Single feed Yes –25°C (–13°F)
ACCU30302 380 V 3~ 50 Hz No Dual feed Yes –25°C (–13°F)
ACCU30001 200–240 V 3~ 50/60 Hz Yes Single feed Yes (UL) –25°C (–13°F)
ACCU30002 200–240 V 3~ 50/60 Hz Yes Dual feed Yes (UL) –25°C (–13°F)
ACCU30201 380–415 V 3~ 50/60 Hz Yes Single feed Yes (PED) –25°C (–13°F)
ACCU30202 380–415 V 3~ 50/60 Hz Yes Dual feed Yes (PED) –25°C (–13°F)
ACCU30101 460–480 V 3~ 50/60 Hz Yes Single feed Yes (UL) –25°C (–13°F)
ACCU30102 460–480 V 3~ 50/60 Hz Yes Dual feed Yes (UL) –25°C (–13°F)
6 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Overview
The ACRD300 series of indoor units can provide a cooling capacity up to 30 kW
based on a half-rack platform (300 mm (12 in.)) with an ACCU30000 series
outdoor condensing unit. A variable-speed compressor works with EC fans and a
fin-tube exchanger to reach the best cooling efficiency. This modular, row-based
computer room cooling system offers efficient, predictable, and economical
cooling for a variety of spaces.
Critical environmental requirements now reach far beyond the confines of the
traditional data center or computer room to encompass a larger suite of
applications, referred to as technology rooms. Critical environment applications
include the following:
• Computer rooms
• Telecommunication facilities
• Clean rooms
• Power equipment
• Medical equipment rooms
• LAN/WAN environments
A worldwide network by Schneider Electric representatives is fully qualified to
provide engineering, sales, installation, and service for our products.
Capacities
InRow®Direct Expansion (DX) units in the ACRD300 series are available as a
300-mm unit with nominal capacities up to 30 kW.
Room Air Distribution
Row-based systems are placed in line with rack enclosures. At least one system is
used per hot aisle. Air is drawn in through the rear of the system, cooled, and
discharged into the cold aisle, thereby neutralizing the sensible heating effects of
the data processing equipment. InRow DX products deliver high volumes of
airflow to eliminate hot spots in densely populated environments.
Configuration:
• Air-cooled
990-91209A-001 7

ACRD300 and ACCU30000 Series Technical Data
Compliance Approval
Indoor Unit
Agency ACRD300 ACRD300D ACRD300G ACRD300GD ACRD301 ACRD301G
UL and cUL X X
RCM
CE X X
EAC
CCC X X X X
CMIM X X
Agency ACRD300-LT ACRD300D-LT ACRD300G-LT ACRD300GD-LT
UL and cUL
RCM
CE
EAC
CCC X X X X
CMIM
Agency ACRD306 ACRD306G ACRD307 ACRD307G
UL and cUL X X
RCM
CE X X
EAC
CCC
CMIM
Outdoor Unit
Agency ACCU30301 ACCU30302 ACCU30001 ACCU30002
UL and cUL X X
RCM
CE
EAC
CCC X X
CMIM
Agency ACCU30201 ACCU30202 ACCU30101 ACCU30102
UL and cUL X X
RCM
CE X X
EAC
CCC
CMIM X X
8 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Working Conditions and Environmental Limits
InRow DX units have a minimum heat load to ensure proper operation. Failure to
operate the unit with at least the minimum load will result in one or more of the
following conditions:
• Unstable unit operation
• Decreased operating efficiency
• Equipment on/off cycling
• Inadequate dehumidification
• Increased wear and tear caused by frequent on/off cycles
• Decreased group control effectiveness
• Potential increase in cost of ownership
Limit Working Conditions—Indoor Units (ACRD300, ACRD300D, ACRD300G, ACRD300GD, ACRD301,
ACRD301G)
Refrigerant type R410A
Voltage input tolerance ±10%
Minimum recommended load 9.5 kW (32,400 BTU/hr)
Outdoor ambient temperature Down to –15°C (+5°F)
Up to 48°C (118°F)
Ambient %RH 5 to 80%RH
Altitude 3000 m (9843 ft)
Storage Conditions
Temperature –25°C to +65°C (–13°F to +149°F)
Humidity 5 to 95%RH
Limit Working Conditions—Indoor Units (ACRD300-LT, ACRD300D-LT, ACRD300G-LT, ACRD300GD-LT,
ACRD306, ACRD306G, ACRD307, ACRD307G)
Refrigerant type R410A
Voltage input tolerance ±10%
Minimum recommended load 9.5 kW (32,400 BTU/hr)
Outdoor ambient temperature Down to –25°C (–13°F)
Up to 48°C (118°F)
Ambient %RH 5 to 80%RH
Altitude 3000 m (9843 ft)
Storage Conditions
Temperature –25°C to +65°C (–13°F to +149°F)
Humidity 5 to 95%RH
NOTE: ACRD301, ACRD301G, ACRD306, ACRD306G, ACRD307, and ACRD307G are in accordance
with the Electromagnetic Compatibility Standard (EMC): EN 55032, EN55024, EN61000-3-2, EN61000-3-
3, EN61000-6-3, EN61000-6-1, EN61000-3-11, EN 61000-3-12.
ACRD301, ACRD301G, ACRD306, ACRD306G, ACRD307, and ACRD307G are in accordance with FCC:
ANSI C63.4.
NOTE: The SKUs comply with EN61000-3-12 provided that the short-circuit power SSC is greater than or
equal to 350 at the interface point between the user supply and the public system. It is the responsibility of
the installer or user of the equipment to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with a short-circuit power SSC greater than or
equal to 350.
990-91209A-001 9

ACRD300 and ACCU30000 Series Technical Data
Limit Working Conditions—Outdoor Units
Refrigerant type R410A
Compressor oil type PVE (Daphne Hermetic Oil FVC32D)
Operating outdoor temperature –25°C to +48°C (-13°F to +118°F)
Altitude 3000 m (9843 ft)
Storage Conditions
Temperature –25°C to +65°C (–13°F to +149°F)
Humidity 5 to 95%RH
NOTE: ACCU30201 and ACCU30202 are in accordance with the Electromagnetic Compatibility Standard
(EMC): EN 55032, EN55024, EN61000-3-2, EN61000-3-3, EN61000-6-3, EN61000-6-1, EN61000-3-11,
EN 61000-3-12.
ACCU30001, ACCU30002, ACCU30101, and ACCU30102 are in accordance with FCC: ANSI C63.4.
NOTE: The SKUs comply with EN61000-3-12 provided that the short-circuit power SSC is greater than or
equal to 350 at the interface point between the user supply and the public system. It is the responsibility of
the installer or user of the equipment to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with a short-circuit power SSC greater than or
equal to 350.
10 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Scalable Solution for Critical Environments
InRow Advantages
The row-based solution improves energy efficiency and cooling ability in a number
of ways. First, the InRow DX unit draws air directly from the hot aisle, allowing the
InRow DX unit to take advantage of higher heat transfer efficiency due to higher
temperature differences. It can then discharge room-temperature air directly in
front of the servers it is cooling. Placing the unit in the row enables the unit to
operate at higher return and supply air temperatures, yielding 100% sensible
capacity. This significantly reduces the need for humidification.
na5859a
HOT AISLE
Scalable for High Density
The predictable performance of the row-based architecture makes it well-suited
for high density applications. The focus on heat removal instead of cold-air
delivery is the key to making this approach scalable. The modular design of the
InRow DX unit allows it to be easily added in the row as the demand for cooling
increases.
The additional benefit of the row-based architecture is the ability to add hot-aisle
containment. Containing the hot aisle further reduces any chance of hot and cold
air streams mixing. This provides ultimate predictability and allows the cooling
capacity to be matched to the IT heat load.
990-91209A-001 11

ACRD300 and ACCU30000 Series Technical Data
Standard Features and Options
Standard Features
EcoStruxure™Ready
The ACRD300 Series is ready to connect to the world-leading DCIM platform.
Cabinet
The frame of the ACRD300 series units is constructed of 16-gauge formed steel
for maximum strength. The cabinet is serviceable from the front and rear. All
exterior panels and corner posts on the frame are powder coated for durability and
an attractive finish. The front and rear exterior panels are constructed of 18 gauge
perforated steel with 80% open free area. All panels, which include a key latch for
safety and security, allow easy access and removal. The footprint of 300 mm
takes up less space in the data center.
Air Flow
ACRD300 Series units can provide 5440 m3/h (3200 CFM) of rated air flow.
Condensate Pump
•ACRD301, ACRD300, ACRD300D, ACRD301-LT, ACRD300D-LT,
ACRD306, and ACRD307: A condensate pump is factory wired and piped
internally to the condensate drain pan. Within the condensate pump, there is
a dual position float. The first position is used for condensate pump control
and the other float generates a condensate pump failure alarm to prevent
condensate pan overflow.
Counterflow Cooling Coil/Condensate Pan
Designed for high-sensible heat ratios, the coil is constructed with copper tubes,
raised-lance-type aluminum fins, and 18-gauge galvanized steel end plates. Coil
headers are equipped with anti-drip shields in the event of condensation. The
condensate pan is thermal formed non-ferrous material, and is sloped for positive
drainage to provide higher indoor air quality.
Filters
Filtration of conditioned air is extremely vital to maintaining the clean, particle-free
environment required by electrical equipment. Filters are easily replaceable from
the rear of the unit. ACRD300 series units use greater-than 20% efficiency
ASHRAE 52.1, 12.7 mm (1/2 in.) washable filters that meet HF-1 standards for
electronics (MERV 1 per ASHRAE 52.2)
Network Management Card
The Network Management Card (NMC) allows communication with the local area
network (LAN). In addition, the NMC permits multi-level access to monitoring,
control, and event notification features over the building network.
Remote Temperature Sensors
To control the cooling unit based on rack inlet temperature, remote temperature
sensors are provided. The ACRD300 series units come equipped with one
temperature sensor. These sensors measure temperature at a point 4 m (13 ft)
from the connection inside the InRow DX unit. These sensors are used for remote
placement in the field on an adjacent IT rack.
12 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Shutdown Input/Alarm Output
The unit provides one field connection input for remote shutdown and one field
connection alarm output.
Power
• 3.2 rated SCOP (EER)
◦Substantially lower power consumption
• Power by UPS
◦Due to low current draw, connect the indoor unit secondary power feed to
the UPS for easy power backup.
Selectable Top or Bottom Piping Connections
The cooling unit includes both top and bottom piping connections. All ACRD300
series connections use threaded ring seals for ease of installation and service.
Variable-Speed Fans
Each unit is equipped with variable speed fans to allow for varying heat loads. In
order to provide uniform airflow over the cooling coil, the fans provide a draw-
through air pattern. ACRD300 series units are equipped with eight direct-drive fan
modules. These fans are easily replaceable while the unit is in operation.
R410A Refrigerant
R410A refrigerant does not harm the ozone layer and has a very low contribution
to the global warming impact.
Outdoor Condensing Unit
The outdoor condensing unit has a small footprint of 1 m2(10.8 ft2). Moving the
compressor to the outdoor condensing unit improves serviceability for the indoor
unit and lowers the sound level in the IT space.
Electronic Expansion Valve
The EEV provides accurate control of the refrigerant superheat in order to ensure
an increase in efficiency at low external temperatures because it enables the unit
to operate at much lower condensing pressures than would be possible with a
traditional mechanical valve.
Display Interface
The standard arrangement of the touch-screen display, RS 485 serial card, and
USB connection allows direct connection to BMSs based on serial lines. The USB
port allows quick downloads of the unit settings and parameters.
Microprocessor
The control system consists of two sections: the J5 controller containing the
regulation software and is installed in the unit electrical panel, and the 4.3-inch,
touch-screen display interface on the exterior of the unit.
The control system uses sophisticated algorithms to control the outlet water
temperature within a minimal range and to monitor and protect the various unit
components. The display interface provides clear information on the unit status
and any current alarms.
990-91209A-001 13

ACRD300 and ACCU30000 Series Technical Data
Optional Features
Aisle Containment
This containment solution isolates pods (two rows of InRow cooling units sharing a
common aisle) from the whole IT environment, increasing cooling efficiency at any
density.
Cable Water Detector
A leak detection cable is placed on the floor or sub-floor around all possible leak
sources. If water or other conductive liquids contact the cable anywhere along its
length, the microprocessor controller announces the leak visually, audibly, and
across the network. The 6.1-m (20-ft) cable may be cascaded to make custom
lengths up to 24.4 m (80 ft).
Humidity Monitoring
An optional remote sensor is available to monitor the humidity level of the data
center.
Dual Power Circuits
Optional integrated redundant power circuits provide full power redundancy.
Compressor Acoustic Hood
An optional compressor acoustic hood reduces the sound level.
Data Partition
Overhead cable distribution between adjacent NetShelter racks allows for removal
of the InRow DX units without disrupting overhead cabling.
Filters
Electrical equipment requires clean, particle-free air, thus making air filtration
extremely important. As an optional feature, higher efficiency filters can be
purchased for the InRow DX units. The ACRD300 series units optionally use an
50.8 mm (2 in.) pleated, deep loading, 30% ASHRAE 52.1 filter (MERV 8 per
ASHRAE 52.2).
Height Adapters
To match height of the InRow DX cooling units to various rack heights, height
adapters are available for NetShelter 42-U VX and 48-U SX racks.
Network Cable
Various lengths of network cable are available to ship with your cooling system.
The network cable is used to interconnect multiple units in a redundant group, as
well as to connect the Network Management Card to your LAN.
Power Trough
Overhead power distribution between adjacent NetShelter racks allows for
removal of the InRow DX cooling units without disrupting overhead power cabling.
14 990-91209A-001

ACRD300 and ACCU30000 Series Technical Data
Microprocessor Controller
Display Interface
Display
Reset
Micro
SD
Service
Port
USB
Console
10/100
na4820a
Item Description Function
LCD Display 4.3-inch touch-screen color display
Power LED The cooling unit is powered when the LED is
illuminated. Unit firmware is updating when
LED is blinking.
Check Log LED When this LED is illuminated, a new entry has
been made to the event log.
Alarm LED Displays current alarm condition of unit.
Status LED Displays current network management card
status.
Display Reset button Resets the display microprocessor. This has
no effect on the air conditioner controller.
Link-RX/TX (10/100)
LED
Displays current network link status.
Micro SD card slot Memory card expansion slot.
Service port USB-B port used only by service personnel.
USB-A port Supports firmware upgrades.
Serial Configuration
port
Connects the display to a local computer to
configure initial network settings or access the
command line interface (CLI).
Microprocessor Controller
The microprocessor controller is standard on each system. The easy-to-use
touch-screen display allows the operator to select options from the menu-driven
interface to control and monitor the connected air conditioning system.
Open Architecture
The InRow Direct Expansion protocol is open for integration with all building
management systems. Communication interface on the system can be MODBUS
RS485 or Ethernet.
Control Type
The controller uses proportional/integral/derivative (PID), a time-proven precision
environmental control method. This allows for custom tuning of control variables to
achieve desired system response.
16 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Functions
• Supply and return air conditions
• Operational mode control
• Event logging
• Alarms
• Redundant group control
• Fan speed adjustment
• Input/Output module programming
Control
The touch-screen LCD display interface is protected by a configurable password
and provides access to information and settings for the unit.
• Supply Temperature Setpoint: 15.0–30.2°C (59.0–86.4°F)
• Cool Setpoint: 18.0–32.2°C (64.4–90.0°F)
• Rack Inlet High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
• Supply Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
• Return Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
Alarms
The microprocessor controller shall activate a visible and audible alarm in the
following occurrences:
• Cool fail
• Air filter clogged
• Return air sensor fault
• Supply air sensor fault
• Rack temperature sensor fault
• High discharge pressure
• Low suction pressure
• Fan fault
• Water detected (if optional leak detector used)
• Check condensate management system
• Air filter run hours violation
• Group communication fault
• Supply air high temperature violation
• Return air high temperature violation
• Filter DP sensor failure
• Suction pressure sensor failure
• Discharge pressure sensor failure
• Persistent high discharge pressure fault
• Rack inlet temperature high violation
• External communication fault
• Internal communication fault
• On standby input contact fault
• A-link isolation relay fault
• Condensate pan full
• Upper fan power supply fault
990-91209A-001 17

ACRD300 and ACCU30000 Series Technical Data
• Lower fan power supply fault
• Suction temperature sensor failure
• Persistent low suction pressure fault
• Factory configuration not completed
• Liquid refrigerant sensor failure
• Compressor drive communication fault
• Compressor drive fault
• Compressor run hours violation
• Condensate pump run hours violation
• Fan run hours violation
• Idle mode active
• High pressure switch active
• Compressor high pressure
• Supply humidity sensor fault
• High suction pressure
• Excessive compressor cycling
• VFD inverter overheat
• Compressor drive locked
18 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Component Identification
External Components
Indoor Unit—All ACRD30X Units
na6950a
Item Description
Upper side panel
Upper piping connection openings
Filters
Rear panel
Lower side panel
Rear casters (non-swiveling)
Lower piping connection openings
Front casters (swiveling)
Leveling feet
Front panel
Display interface
990-91209A-001 19

ACRD300 and ACCU30000 Series Technical Data
Outdoor Unit—All ACCU30XXX Units
na6953a
NOTE: Model ACCU30301 is shown.
Item Description Item Description
Fan Mounting holes
Main disconnect switch handle (field
installed)
Signal cable inlet
Electrical panel access doors Liquid line inlet
Quarter-turn latches Suction line inlet
Service panel Coil grilles
Power feed A inlet Lifting eyebolts (field supplied)
Power feed B inlet
20 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Internal Components
Indoor Unit
ACRD300, ACRD300D, ACRD300G, ACRD300GD, ACRD301,
ACRD301G
na6951a
NOTE: Some components not shown for easier viewing.
Item Description Item Description
Power supply connections (top) Lower return air temperature sensor
Fans Gas line service port
Upper supply air temperature sensor Automatic transfer switch (ATS)
Solenoid valve Condensate drain pump
(ACRD300, ACRD300D, and ACRD301 only)
Liquid line service port Temperature and humidity sensor (optional)
Cooling coil Inlet connection
Lower supply air temperature Outlet connection
Refrigerant temperature sensor Electronic expansion valve (EEV)
Leveling feet Sight glass
Condensate drain pan Filter drier
Drain pan float switch Electrical box
Temperature sensor (suction) Upper return air temperature sensor
Joining bracket
990-91209A-001 21

ACRD300 and ACCU30000 Series Technical Data
ACRD300-LT, ACRD300D-LT, ACRD300G-LT, ACRD300GD-LT,
ACRD306, ACRD306G, ACRD307, ACRD307G
na7240a
NOTE: Some components not shown for easier viewing.
Item Description Item Description
Power supply connections (top) Liquid receiver*
Fans Gas line service port
Upper supply air temperature sensor Automatic transfer switch (ATS)
Solenoid valve Condensate drain pump
(ACRD300-LT, ACRD300D-LT, ACRD306, and
ACRD307 only)
Liquid line service port Temperature and humidity sensor (optional)
Cooling coil Lower return air temperature sensor
Lower supply air temperature Inlet connection
Refrigerant temperature sensor Outlet connection
Leveling feet Electronic expansion valve (EEV)
Condensate drain pan Sight glass
Drain pan float switch Filter drier
Temperature sensor (suction) Electrical box
Joining bracket Upper return air temperature sensor
*The liquid receiver in ACRD306 and ACRD306G units is equipped with a safety valve; the liquid receiver in all other units is equipped with
a fusible plug.
22 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Outdoor Unit
ACCU30301, ACCU30302, ACCU30001, ACCU30002,
ACCU30101, ACCU30102
na6954a
Item Description Item Description
Electrical panel Variable frequency drive (VFD)
Accumulator Interior protection panel
Liquid line connection EMI filter
Suction line connection Service port
Oil separator High pressure switch
Compressor sight glass High (discharge) pressure sensor
Low (suction) pressure sensor Service port
Variable-speed compressor
990-91209A-001 23

ACRD300 and ACCU30000 Series Technical Data
ACCU30201, ACCU30202
na6954b
Item Description Item Description
Electrical panel Variable frequency drive (VFD)
Accumulator Interior protection panel
Liquid line connection Line reactor and EMI filter
Suction line connection Service port
Oil separator High pressure switch
Compressor sight glass High (discharge) pressure sensor
Low (suction) pressure sensor Service port
Variable-speed compressor
24 990-91209A-001

ACRD300 and ACCU30000 Series Technical Data
Outdoor Unit
ACCU30301
na6981a
Item Description Item Description
Crank case heater power transformer Fan motor switch
Terminal block Compressor variable-speed drive
switch
Crank case heater switch Main switch
Crank case heater power transformer
switch
26 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
ACCU30302
na6980a
Item Description Item Description
Crank case heater power transformer Supply line selector relay
Terminal block Supply A line monitor
Crank case heater switch Supply B line monitor
Crank case heater power transformer
switch
Supply A contactor timer
Fan motor switch Supply B contactor timer
Compressor variable-speed drive
switch
ATS circuit fuse
Main switch Supply line selector A/B
ATS supply A power transformer Supply A contactor
ATS supply B power transformer Supply B contactor
990-91209A-001 27

Technical Data ACRD300 and ACCU30000 Series
ACCU30002
na7035a
Item Description Item Description
Terminal block Supply A contactor timer
Crank case heater switch Supply B contactor timer
Fan motor switch ATS circuit fuse
Compressor variable-speed drive
switch
Supply line selector A/B
Power supply A main switch Supply A contactor
Supply line selector relay Supply B contactor
Supply A line monitor Power supply B main switch
Supply B line monitor
990-91209A-001 29

ACRD300 and ACCU30000 Series Technical Data
ACCU30101 and ACCU30201
na7032a
Item Description Item Description
Crank case heater power transformer Fan motor switch
Terminal block Compressor variable-speed drive
switch
Crank case heater switch Main switch
Crank case heater power transformer
switch
30 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
ACCU30102 and ACCU30202
na7033a
Item Description Item Description
Crank case heater power transformer Supply B line monitor
Terminal block Supply A contactor timer
Crank case heater switch Supply B contactor timer
Crank case heater power transformer
switch
ATS circuit fuse
Fan motor switch Supply line selector A/B
Compressor variable-speed drive
switch
Supply A contactor
Power supply A main switch Supply B contactor
ATS supply A power transformer Power supply B main switch
Supply line selector relay ATS supply B power transformer
Supply A line monitor
990-91209A-001 31

ACRD300 and ACCU30000 Series Technical Data
Performance Specifications
Cooling Capacity
Operating Conditions Sensible Net Capacity – kW
(BTU/h)
Energy Efficiency (W/W)
Minimum Load* 9.5 (32,400) —
GB19413 16.3 (55,600) 4.0 AEER
ASHRAE 127 Class 3 25 (85,300) 3.2 SCOP
Maximum at 35°C (95°F) Return
Air Temperature
27 (92,100) —
Maximum at 40°C (104°F) Return
Air Temperature
30 (102,400) —
*If lower than the minimum load, the unit may cycle the compressor.
NOTE: Outdoor air temperature is 35°C (95°F) unless otherwise stated.
NOTE: Data is for evaporator fans, condenser fans, and compressors operating at maximum capacity.
32 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
General Data
Indoor Units
Air System—Fan
Fan Type EC
Size – mm (in.) 220 (8.7)
Number of Fans 8
Air Volume – CMH (SCFM) 5440 (3200)
Fan Power – W (total) 850
Emergency Air Volume* – CMH (SCFM)*6300 (3700)
Cooling Coil
Face Area – m2(ft2) 0.51 (5.49)
Rows Deep 3
Filters—Washable (Standard)
Quantity 2
Size – mm (in.) 238 x 933 (9.375 x 36.75)
Depth – mm (in.) 12.7 (0.5)
Efficiency MERV 1
Filters—Pleated (Optional)
Quantity 2
Size – mm (in.) 238 x 933 (9.375 x 36.75)
Depth – mm (in.) 51 (2)
Efficiency MERV 8
Physical Data
Height – mm (in.) 1991 (78.39)
Width – mm (in.) 300 (11.81)
Depth – mm (in.) 1095 (43.11)
Connection Sizes (Not Piping Sizes)
Suction Piping 1 1/4 in. (12 UNF), 7/8 in. tube
Liquid Piping 1 in. (14 UNS), 1/2 in. tube
Condensate Drain 4.77 mm (3/16 in.) ID
6.35 mm (1/4 in.) OD
Refrigerant
Type R410A
Standard Charge for Standard Units – kg (lb) 15.0 (33.0)
Standard Charge for Low Temperature Units –
kg (lb)
19.5 (43.0)
*Emergency air flow is available with dual fan power supplies and a humidity sensor.
990-91209A-001 33

ACRD300 and ACCU30000 Series Technical Data
Outdoor Units
Air System—Fan
Fan Type EC
Size – mm (in.) 710 (28.0)
Number of Fans 1
Cooling Coil
Face Area – m2(ft2) 3.024 (32.55)
Rows Deep 3
Physical Data
Height – mm (in.) 1555 (61.2)
Width – mm (in.) 1000 (39.4)
Depth – mm (in.) 1000 (39.4)
Connection Sizes (Not Piping Sizes)
Gas Piping 7/8 in. ODF
Liquid Piping 1/2 in. ODF
Refrigerant Piping*
Maximum Equivalent Length – m (ft) 120 (393)
Maximum Elevation** – m (ft) 30 (98)
*See the Installation Manual for more information.
**Condensing units may be level with or higher than the indoor unit.
See the Installation Manual for more information on refrigerant piping.
34 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Altitude Correction Factors
Room Conditions: 22°C (72°F) DB/50%RH
Altitude – m (ft) Specific Volume – cm3/
kg (ft3/lb)
Density –g/m3(lb/ft3) Density Ratio* Capacity Correction**
0 (0) 847.77 (13.58) 1185.37 (0.074) 1.000 1.000
305 (1000) 879.61 (14.09) 1137.31 (0.071) 0.964 0.981
610 (2000) 912.70 (14.62) 1089.26 (0.068) 0.929 0.962
915 (3000) 947.66 (15.18) 1057.22 (0.066) 0.895 0.933
1219 (4000) 983.86 (15.76) 1009.16 (0.063) 0.862 0.913
1524 (5000) 1021.32 (16.36) 977.13 (0.061) 0.830 0.884
1829 (6000) 1061.28 (17.00) 945.10 (0.059) 0.799 0.865
2134 (7000) 1103.10 (17.67) 913.05 (0.057) 0.769 0.846
2438 (8000) 1146.80 (18.37) 865.00 (0.054) 0.739 0.826
2743 (9000) 1193.00 (19.11) 832.97 (0.052) 0.711 0.807
3048 (10,000) 1241.69 (19.89) 80.92 (0.050) 0.683 0.787
*Density ratio is used for air flow correction factor.
**Capacity correction is used to de-rate performance.
990-91209A-001 35

ACRD300 and ACCU30000 Series Technical Data
Electrical Data
Indoor Units
Model MCA MOP FLA
ACRD300 n/a n/a 8.0–6.7
ACRD300D n/a n/a 8.0-6.7
ACRD300G n/a n/a 8.0–6.7
ACRD300GD n/a n/a 8.0–6.7
ACRD300-LT n/a n/a 8.0–6.7
ACRD300D-LT n/a n/a 8.0–6.7
ACRD300G-LT n/a n/a 8.0–6.7
ACRD300GD-LT n/a n/a 8.0–6.7
ACRD301 20.3* / 9.3** 25.0* / 15.0** 16.5–13.8* / 8.0–6.7**
ACRD301G 20.3* / 9.3** 25.0* / 15.0** 16.5–13.8* / 8.0–6.7**
ACRD306 20.3* / 9.3** 25.0* / 15.0** 16.5–13.8* / 8.0–6.7**
ACRD306G 20.3* / 9.3** 25.0* / 15.0** 16.5–13.8* / 8.0–6.7**
ACRD307 20.3* / 9.3** 25.0* / 15.0** 16.5–13.8* / 8.0–6.7**
ACRD307G 20.3* / 9.3** 25.0* / 15.0** 16.5–13.8* / 8.0–6.7**
*Data for units with 100–120-V~ power supplies.
**Data for units with 200–240-V~ power supplies.
Outdoor Units
Model MCA MOP FLA
ACCU30301 n/a n/a 15.8
ACCU30302 n/a n/a 15.8
ACCU30001 50.05 80 n/a
ACCU30002 50.05 80 n/a
ACCU30101 23.1 40 n/a
ACCU30102 23.1 40 n/a
ACCU30201 n/a n/a 15.8
ACCU30202 n/a n/a 15.8
36 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Sound Data
Indoor Units—All Units
Fan Speed
%
Airflow –
l/s (SCFM)
Weighted Sound Pressure dBA* at Frequency – Hz re: 20μPa
Lp Sound
Pressure – dB
re: 20μPa
125 250 500 1000 2000 4000 8000 dBA*
30 430 (900) 36.5 36.1 44.7 46.3 40.3 35.8 22.9 49.8
40 610 (1300) 36.2 42.1 52.6 51.2 47.7 45.9 34.3 56.4
50 780 (1650) 30.2 48.8 54.7 61.5 53.1 52.0 42.8 63.4
60 940 (2000) 32.9 55.2 56.0 62.3 57.7 56.2 48.3 65.4
70 1110 (2350) 33.8 60.3 59.3 65.7 62.1 59.5 52.9 69.2
80 1240
(2700)
34.6 61.8 63.5 71.9 64.1 63.0 56.8 73.9
90 1390
(2950)
35.1 54.3 67.9 72.3 68.1 65.9 60.1 75.4
100 1510
(3200)
43.1 53.8 70.0 73.3 70.1 68.9 62.9 77.1
130 1750
(3700)
44.8 55.1 77.5 74.4 74.1 70.3 63.6 80.9
*Weighted Sound Pressure (dBA) data is measured in a semi-anechoic room in accordance with ISO 3745, at 1.8-m (6.0-ft) distance from
the unit and 1-m (3.3-ft) height.
Outdoor Units—All Units
Fan Speed
%
Compressor
RPM
Acoustic
Hood
Weighted Sound Pressure dBA* at Frequency – Hz re: 20μPa
Lp Sound
Pressure – dB
re: 20μPa
125 250 500 1000 2000 4000 8000 dBA*
70 5400 Without 39.6 56.3 54.8 56.6 55.8 55.5 47.2 63.0
100 6000 Without 41.7 54.8 55.4 56.5 56.6 57.9 48.4 63.6
70 5400 With 38.3 52.7 52.3 54.3 51.2 50.1 41.1 59.5
100 6000 With 41.4 53.6 54.5 55.8 53.2 53.6 43.3 61.4
*Weighted Sound Pressure (dBA) data is measured in a semi-anechoic room in accordance with ISO 3745, at 2.0-m (6.6-ft) distance from
the unit and 1-m (3.3-ft) height.
990-91209A-001 37

ACRD300 and ACCU30000 Series Technical Data
Dimensions and Weights
Indoor Unit
na6955b
1095 (43.11)
300 (11.80)
1991 (78.39)
1137 (44.76)
661 (26.02)
2152 (84.72)
NOTE: Image is an example only to show dimensions of unit: your unit may
differ.
SKU Net Weight
– kg (lb)
Shipping Weight
– kg (lb)
ACRD300, ACRD300D, ACRD300G,
ACRD300GD, ACRD301, ACRD301G
160 (352.7) 200 (440.9)
ACRD300-LT, ACRD300D-LT,
ACRD300G-LT, ACRD300GD-LT,
ACRD306, ACRD306G
175 (385.8) 215 (474.0)
ACRD307, ACRD307G 180 (396.8) 220 (485.0)
38 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Outdoor Unit
A
B
C
A
B
C
na6956a
SKU Unit Dimensions – mm (in.) Shipping Dimensions – mm
(in.)
Net
Weight –
kg (lb)
Shipping
Weight –
kg (lb)
A B CA B C
ACCU30301 1000
(39.4)
1000
(39.4)
1555
(61.2)
1136
(44.7)
1085
(42.7)
1745
(68.7)
267
(588.6)
297 (654.8)
ACCU30302 1000
(39.4)
1000
(39.4)
1555
(61.2)
1136
(44.7)
1085
(42.7)
1745
(68.7)
272
(600.0)
305 (672.4)
ACCU30001 1000
(39.4)
1000
(39.4)
1600
(63.0)
1136
(44.7)
1085
(42.7)
1745
(68.7)
267
(588.6)
297 (654.8)
ACCU30002 1000
(39.4)
1000
(39.4)
1600
(63.0)
1136
(44.7)
1085
(42.7)
1745
(68.7)
272
(600.0)
305 (672.4)
ACCU30201 1000
(39.4)
1000
(39.4)
1555
(61.2)
1136
(44.7)
1085
(42.7)
1745
(68.7)
273
(601.9)
303 (668.0)
ACCU30202 1000
(39.4)
1000
(39.4)
1555
(61.2)
1136
(44.7)
1085
(42.7)
1745
(68.7)
278
(612.9)
308 (679.0)
ACCU30101 1000
(39.4)
1000
(39.4)
1555
(61.2)
1136
(44.7)
1085
(42.7)
1745
(68.7)
267
(588.6)
297 (654.8)
ACCU30102 1000
(39.4)
1000
(39.4)
1555
(61.2)
1136
(44.7)
1085
(42.7)
1745
(68.7)
272
(600.0)
305 (672.4)
990-91209A-001 39

ACRD300 and ACCU30000 Series Technical Data
Service Access
Indoor Unit
A minimum of 900 mm (36 in.) of clear floor space in front of and behind the
equipment is recommended for service access. All required normal maintenance
is performed from the front and rear of the equipment.
Most of the cooling components in the equipment can be replaced while the unit is
installed in row and without the use of heavy lift equipment or a welding torch.
However, if it is necessary to remove the unit for repair, use the casters on the
equipment to remove it from the row. An area of minimum 1200 mm (48 in.) of
clear floor space in front of or behind the equipment is recommended to roll out
the equipment.
NOTE: Check local and national codes and regulations for further service
access requirements.
NOTE: Image is an example only: your unit may differ.
na5810a
900 (36.00) 900 (36.00)
1200 (48.00) 1200 (48.00)
SERVICE ACCESS REQUIRED
WHEN EQUIPMENT IS
INSIDE THE ROW
FREE SPACE NEEDED TO
MOVE EQUIPMENT
OUTSIDE THE ROW
NOTE: Dimensions are shown in mm (in.).
40 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
Outdoor Unit
A minimum of 1 m (39 in.) of clear space on all sides of the equipment is
recommended for service access.
1m (39 in.)
1m (39 in.) 1m (39 in.)
1m (39 in.)
1m (39 in.)
na6963a
Airflow Clearance
The following clearances are required for proper airflow around the outdoor unit.
na7029a
> 1 m
(3.3 ft)
> 1 m (3.3 ft)
> 3 m (9.8 ft)
990-91209A-001 41

ACRD300 and ACCU30000 Series Technical Data
Piping and Electrical Access Locations
Indoor Unit
ACRD300, ACRD300G, ACRD300D, ACRD300GD, ACRD300-LT,
ACRD300G-LT, ACRD300D-LT, ACRD300GD-LT
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6957a
47.0 (1.9)
47.8 (1.9)
55.1 (2.2)
73.5 (2.9) 42.8 (1.7)
78.4
(3.1)
123.4 (4.9)
182.8 (7.2)
150.4 (5.9)
190.4 (7.5)
177.9 (7.0)
217.9 (8.6)
148.8 (5.6)
157.9 (6.2)
213.6 (8.4)
102.0 (4.0)
73.5 (2.9)
55.1 (2.2)
62.8 (2.5)
188.8 (7.4)
111 (4.37)
101.7 (4.0)
437.1 (17.2)
92.66
(3.6)
NOTE: Dimensions are shown in mm (in.).
42 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6958a
Item Description
Low voltage input wiring inlets
Power supply 1 inlet
Power supply 2 inlet
Suction line connection—1 1/4 in. (12 UNF)
Liquid line connection—1 in. (14 UNS)
Condensate drain line outlet
Gravity drain connection
990-91209A-001 43

ACRD300 and ACCU30000 Series Technical Data
ACRD301, ACRD301G, ACRD306, ACRD306G, ACRD307,
ACRD307G
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6957a
56.5 (2.2)
47.8 (1.9)
55.1 (2.2)
73.5 (2.9) 87.3 (3.4)
78.4
(3.1)
123.4 (4.9)
182.8 (7.2)
150.4
(5.9)
190.4 (7.5)
227.0 (8.9)
274.0 (10.8)
148.8 (5.6)
157.9 (6.2)
213.6 (8.4)
102.0 (4.0)
73.5 (2.9)
55.1 (2.2)
62.8 (2.5)
188.8 (7.4)
111 (4.37)
101.7 (4.0)
437.1 (17.2)
92.66
(3.6)
44 990-91209A-001

Technical Data ACRD300 and ACCU30000 Series
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6958b
Item Description
Low voltage input wiring inlets
Power supply 1 inlet
Power supply 2 inlet
Suction line connection—1 1/4 in. (12 UNF)
Liquid line connection—1 in. (14 UNS)
Condensate drain line outlet
Gravity drain connection
990-91209A-001 45

ACRD300 and ACCU30000 Series Technical Data
Outdoor Unit
na6961a
309.3 (12.2)
371.0 (14.6)
105.6 (4.2)
121.8 (4.8)
169.0 (6.7)
206.5 (8.1)
na6962a
NOTE: Dimensions are shown in mm (in.).
Item Description
Power supply 1 inlet
Power supply 2 inlet
Communication cable inlet
Liquid line connection inlet
Suction line connection inlet
46 990-91209A-001

ACRD300 and ACCU30000 Series Facility Planning
Facility Planning
Indoor Units—Standard
Model ACRD300 ACRD300D ACRD300G ACRD300GD
Input Voltage 200–240 V 200–240 V 200–240 V 200–240 V
Phases 1 1 1 1
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Cabinet Width – mm (in.) 300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)
Cabinet Height – mm
(in.)
1991 (78.39) 1991 (78.39) 1991 (78.39) 1991 (78.39)
Cabinet Depth – mm (in.) 1087 (42.80) 1087 (42.80) 1087 (42.80) 1087 (42.80)
Net Weight – kg (lb) 160 (352.7) 160 (352.7) 160 (352.7) 160 (352.7)
Power Connection Type Hardwired Hardwired Hardwired Hardwired
Full Load Amps (FLA)* 8.0–6.7 8.0–6.7 8.0–6.7 8.0–6.7
Minimum Circuit
Ampacity (MCA)*
N/A N/A N/A N/A
Maximum Overcurrent
Protection (MOP)*
N/A N/A N/A N/A
Features/Options
Fan Type Electronically
commutated
Electronically
commutated
Electronically
commutated
Electronically
commutated
Maximum Airflow – l/s
(CFM)
5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM)
Fan Control Variable speed Variable speed Variable speed Variable speed
Number of Fans 8 8 8 8
Hot Swappable Fans Yes Yes Yes Yes
Hot Aisle Containment
Compatible
Yes Yes Yes Yes
Rack Aisle Containment
Compatible
Yes Yes Yes Yes
Refrigerant Type R410A R410A R410A R410A
Network Management
Card
Included Included Included Included
Standard Filter Type 0.5–in. washable 0.5–in. washable 0.5–in. washable 0.5–in. washable
Standard Filter Efficiency MERV 1 MERV 1 MERV 1 MERV 1
Optional Filter Type 2–in. pleated 2–in. pleated 2–in. pleated 2–in. pleated
Optional Filter Efficiency MERV 8 MERV 8 MERV 8 MERV 8
Drainage System Condensate pump Condensate pump Gravity drain Gravity drain
Number of Rack Inlet
Temperature Sensors
1 1 1 1
Piping Connections Top or bottom Top or bottom Top or bottom Top or bottom
Electrical Connections Top or bottom Top or bottom Top or bottom Top or bottom
Cable Type Water
Detector
Optional Optional Optional Optional
*Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
48 990-91209A-001

Facility Planning ACRD300 and ACCU30000 Series
Model ACRD301 ACRD301G
Input Voltage 100–120 V / 200–240 V 100–120 V / 200–240 V
Phases 1 1
Frequency 50/60 Hz 50/60 Hz
Cabinet Width – mm (in.) 300 (11.81) 300 (11.81)
Cabinet Height – mm (in.) 1991 (78.39) 1991 (78.39)
Cabinet Depth – mm (in.) 1087 (42.80) 1087 (42.80)
Net Weight – kg (lb) 160 (352.7) 160 (352.7)
Power Connection Type Hardwired Hardwired
Full Load Amps (FLA)* 16.5–13.8 / 8.0–6.7 16.5–13.8 / 8.0–6.7
Minimum Circuit Ampacity (MCA)* 20.3 / 9.3 20.3 / 9.3
Maximum Overcurrent Protection (MOP)* 25.0 / 15.0 25.0 / 15.0
Features/Options
Fan Type Electronically commutated Electronically commutated
Maximum Airflow – l/s (CFM) 5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM)
Fan Control Variable speed Variable speed
Number of Fans 8 8
Hot Swappable Fans Yes Yes
Hot Aisle Containment Compatible Yes Yes
Rack Aisle Containment Compatible Yes Yes
Refrigerant Type R410A R410A
Network Management Card Included Included
Standard Filter Type 0.5–in. washable 0.5–in. washable
Standard Filter Efficiency MERV 1 MERV 1
Optional Filter Type 2–in. pleated 2–in. pleated
Optional Filter Efficiency MERV 8 MERV 8
Drainage System Condensate pump Gravity drain
Number of Rack Inlet Temperature Sensors 1 1
Piping Connections Top or bottom Top or bottom
Electrical Connections Top or bottom Top or bottom
Cable Type Water Detector Optional Optional
*Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
990-91209A-001 49

ACRD300 and ACCU30000 Series Facility Planning
Indoor Units—Low Temperature
Model ACRD300-LT ACRD300D-LT ACRD300G-LT ACRD300GD-LT
Input Voltage 200–240 V 200–240 V 200–240 V 200–240 V
Phases 1 1 1 1
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Cabinet Width – mm (in.) 300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)
Cabinet Height – mm
(in.)
1991 (78.39) 1991 (78.39) 1991 (78.39) 1991 (78.39)
Cabinet Depth – mm (in.) 1087 (42.80) 1087 (42.80) 1087 (42.80) 1087 (42.80)
Net Weight – kg (lb) 160 (352.7) 160 (352.7) 160 (352.7) 160 (352.7)
Power Connection Type Hardwired Hardwired Hardwired Hardwired
Full Load Amps (FLA)* 8.0–6.7 8.0–6.7 8.0–6.7 8.0–6.7
Minimum Circuit
Ampacity (MCA)*
N/A N/A N/A N/A
Maximum Overcurrent
Protection (MOP)*
N/A N/A N/A N/A
Features/Options
Fan Type Electronically
commutated
Electronically
commutated
Electronically
commutated
Electronically
commutated
Maximum Airflow – l/s
(CFM)
5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM)
Fan Control Variable speed Variable speed Variable speed Variable speed
Number of Fans 8 8 8 8
Hot Swappable Fans Yes Yes Yes Yes
Hot Aisle Containment
Compatible
Yes Yes Yes Yes
Rack Aisle Containment
Compatible
Yes Yes Yes Yes
Refrigerant Type R410A R410A R410A R410A
Network Management
Card
Included Included Included Included
Standard Filter Type 0.5–in. washable 0.5–in. washable 0.5–in. washable 0.5–in. washable
Standard Filter Efficiency MERV 1 MERV 1 MERV 1 MERV 1
Optional Filter Type 2–in. pleated 2–in. pleated 2–in. pleated 2–in. pleated
Optional Filter Efficiency MERV 8 MERV 8 MERV 8 MERV 8
Drainage System Condensate pump Condensate pump Gravity drain Gravity drain
Number of Rack Inlet
Temperature Sensors
1 1 1 1
Piping Connections Top or bottom Top or bottom Top or bottom Top or bottom
Electrical Connections Top or bottom Top or bottom Top or bottom Top or bottom
Cable Type Water
Detector
Optional Optional Optional Optional
*Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
50 990-91209A-001

Facility Planning ACRD300 and ACCU30000 Series
Model ACRD306 ACRD306G ACRD307 ACRD3067G
Input Voltage 100–120 V / 200–240 V 100–120 V / 200–240 V 100–120 V / 200–240 V 100–120 V / 200–240 V
Phases 1 1 1 1
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Cabinet Width – mm (in.) 300 (11.81) 300 (11.81) 300 (11.81) 300 (11.81)
Cabinet Height – mm
(in.)
1991 (78.39) 1991 (78.39) 1991 (78.39) 1991 (78.39)
Cabinet Depth – mm (in.) 1087 (42.80) 1087 (42.80) 1087 (42.80) 1087 (42.80)
Net Weight – kg (lb) 160 (352.7) 160 (352.7) 160 (352.7) 160 (352.7)
Power Connection Type Hardwired Hardwired Hardwired Hardwired
Full Load Amps (FLA)* 16.5–13.8 / 8.0–6.7 16.5–13.8 / 8.0–6.7 16.5–13.8 / 8.0–6.7 16.5–13.8 / 8.0–6.7
Minimum Circuit
Ampacity (MCA)*
20.3 / 9.3 20.3 / 9.3 20.3 / 9.3 20.3 / 9.3
Maximum Overcurrent
Protection (MOP)*
25.0 / 15.0 25.0 / 15.0 25.0 / 15.0 25.0 / 15.0
Features/Options
Fan Type Electronically
commutated
Electronically
commutated
Electronically
commutated
Electronically
commutated
Maximum Airflow – l/s
(CFM)
5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM) 5437 m3/h (3200 CFM)
Fan Control Variable speed Variable speed Variable speed Variable speed
Number of Fans 8 8 8 8
Hot Swappable Fans Yes Yes Yes Yes
Hot Aisle Containment
Compatible
Yes Yes Yes Yes
Rack Aisle Containment
Compatible
Yes Yes Yes Yes
Refrigerant Type R410A R410A R410A R410A
Network Management
Card
Included Included Included Included
Standard Filter Type 0.5–in. washable 0.5–in. washable 0.5–in. washable 0.5–in. washable
Standard Filter Efficiency MERV 1 MERV 1 MERV 1 MERV 1
Optional Filter Type 2–in. pleated 2–in. pleated 2–in. pleated 2–in. pleated
Optional Filter Efficiency MERV 8 MERV 8 MERV 8 MERV 8
Drainage System Condensate pump Gravity drain Condensate pump Gravity drain
Number of Rack Inlet
Temperature Sensors
1 1 1 1
Piping Connections Top or bottom Top or bottom Top or bottom Top or bottom
Electrical Connections Top or bottom Top or bottom Top or bottom Top or bottom
Cable Type Water
Detector
Optional Optional Optional Optional
*Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
990-91209A-001 51

ACRD300 and ACCU30000 Series Facility Planning
Outdoor Units
Model ACCU30301 ACCU30302 ACCU30001 ACCU30002
Input Voltage 380–415 V 380–415 V 200–240 V 200–240 V
Phases 3 3 3 3
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Cabinet Width – mm (in.) 1000 (39.4) 1000 (39.4) 1000 (39.4) 1000 (39.4)
Cabinet Height – mm
(in.)
1555 (61.2) 1555 (61.2) 1600 (63.0) 1600 (63.0)
Cabinet Depth – mm (in.) 1000 (39.4) 1000 (39.4) 1000 (39.4) 1000 (39.4)
Net Weight – kg (lb) 267 (588.6) 272 (600.0) 267 (588.6) 272 (600.0)
Power Connection Type Hardwired Hardwired Hardwired Hardwired
Full Load Amps (FLA)* 15.8 15.8 N/A N/A
Minimum Circuit
Ampacity (MCA)*
N/A N/A 50.05 50.05
Maximum Overcurrent
Protection (MOP)*
N/A N/A 80 80
Power Connection
Quantity
1 2 1 2
Features/Options
Fan Type Electronically
commutated
Electronically
commutated
Electronically
commutated
Electronically
commutated
Fan Control RS485 Modbus-RTU RS485 Modbus-RTU RS485 Modbus-RTU RS485 Modbus-RTU
Number of Fans 1 1 1 1
Hot Swappable Fans No No No No
Refrigerant Type R410A R410A R410A R410A
Compressor Type Variable speed Variable speed Variable speed Variable speed
*Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
52 990-91209A-001

Facility Planning ACRD300 and ACCU30000 Series
Model ACCU30201 ACCU30202 ACCU30101 ACCU30102
Input Voltage 380–415 V 380–415 V 460–480 V 460–480 V
Phases 3 3 3 3
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Cabinet Width – mm (in.) 1000 (39.4) 1000 (39.4) 1000 (39.4) 1000 (39.4)
Cabinet Height – mm
(in.)
1555 (61.2) 1555 (61.2) 1555 (61.2) 1555 (61.2)
Cabinet Depth – mm (in.) 1000 (39.4) 1000 (39.4) 1000 (39.4) 1000 (39.4)
Net Weight – kg (lb) 273 (601.9) 278 (612.9) 267 (588.6) 272 (600.0)
Power Connection Type Hardwired Hardwired Hardwired Hardwired
Full Load Amps (FLA)* N/A N/A 15.8 15.8
Minimum Circuit
Ampacity (MCA)*
23.1 23.1 N/A N/A
Maximum Overcurrent
Protection (MOP)*
40 40 N/A N/A
Power Connection
Quantity
1 2 1 2
Features/Options
Fan Type Electronically
commutated
Electronically
commutated
Electronically
commutated
Electronically
commutated
Fan Control RS485 Modbus-RTU RS485 Modbus-RTU RS485 Modbus-RTU RS485 Modbus-RTU
Number of Fans 1 1 1 1
Hot Swappable Fans No No No No
Refrigerant Type R410A R410A R410A R410A
Compressor Type Variable speed Variable speed Variable speed Variable speed
*Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
990-91209A-001 53

Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com