APC EPDU1016B User Manual
Displayed below is the user manual for EPDU1016B by APC which is a product in the Power Distribution Units (PDUs) category. This manual has pages.
Related Manuals

Installation
Mount the Rack PDU in a 19-inch NetShelter™ rack or
other EIA-310-D standard 19-inch rack.
1. Choose a mounting position for the Rack PDU
with either the front or the rear of the unit facing
out of the rack. Your Rack PDU will occupy one
(1) U-space.
NOTE: A notched hole on the NetShelter rack’s
vertical rail indicates the middle of a U-space.
NOTE: Install cage nuts properly.
See the illustration for proper cage nut
orientation.
2. Use the provided hardware,
four (4) M6 x 16 mm screws
and four (4) cage nuts.
Specifications
WARNING
FIRE HAZARD
• This equipment should be connected to a single-outlet dedicated circuit protected by a circuit breaker or fuse
with the same current rating as the Rack PDU.
• The plug or inlet serves as the disconnect for the Rack PDU. Make sure the utility power outlet for the Rack
PDU will be close to the Rack PDU and readily accessible.
• Some models of Rack PDUs are provided with IEC C14 or C20 inlets. Use of the proper power cord is the
user’s responsibility.
Failure to follow these instructions can result in death or serious injury.
Electrical
Nominal Input Voltage 200 - 240 VAC
Maximum Input Current (Phase) 16A
Input Frequency 50/60Hz
Input Connection IEC-320 C20 (16A)
Output Voltage 200 - 240 VAC
Maximum Output Current (Outlet) 10A
Maximum Output Current (Phase) 16A
Output Connections IEC 320 C13 (10A)
Output Quantities Eight (8)
Physical
Dimensions (H x W x D) 44.4 x 482 x 44.4 mm (1.75 x 19 x 1.75 in)
Input power cord length 2.5 m (8.2 ft)
Shipping dimensions (H x W x D) 150 x 560 x 80 mm (3.8 x 22.8 x 3.15 in)
Weight/Shipping weight 0.58 kg (1.27 lb) / 1.18kg (2.60 lb)
Environmental
Maximum elevation (above MSL)
Operating/Storage 0–3000 m (0–10,000 ft) / 0–15000 m (0–50,000 ft)
Temperature: Operating/Storage –5 to 45°C (23 to 113°F) / –25 to 65°C (–13 to 149°F)
Humidity: Operating/Storage 5–95% RH, non-condensing
Compliance
EMC verification CE EN55035, EN55032, EN55024
Safety verification CE, TUV, EN/IEC62368-1
CE EU Contact Address Schneider Electric, 35 rue Joseph Monier
92500 Rueil Malmaison France
Environmental RoHS & Reach
1 U
ns0750a
pdu0093b
Easy PDU Basic Rack PDU Installation
EPDU1016B
Worldwide Customer Support
Customer support for this product is available at www.apc.com
© 2019 APC by Schneider Electric. APC and NetShelter are trademarks owned by Schneider
Electric SE. All other trademarks are property of their respective owners.
Overview
This sheet provides installation information for your Easy PDU. Read the instructions carefully.
Receiving
Inspect the package and contents for shipping damage. Make sure all parts were sent.
Immediately report any shipping damage to the shipping agent. Report missing contents, product
damage, or other problems with the product to APC by Schneider Electric or your APC by
Schneider Electric reseller.
Material recycling
The shipping materials are recyclable. Please save them for later use, or dispose of them
appropriately.
Safety
Read the following information before installing or operating your APC by Schneider Electric Rack
Power Distribution Unit (PDU).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The Rack PDU is intended to be installed and operated by a skilled person in a controlled location.
• Do not operate the Rack PDU with the covers removed.
• This Rack PDU is intended for indoor use only.
• Do not install this Rack PDU where excessive moisture or heat is present.
• Never install any wiring, equipment, or Rack PDUs during a lightning storm.
• Plug this Rack PDU into a grounded power outlet only. The power outlet must be connected to appropriate
branch circuit/mains protection (fuse or circuit breaker). Connection to any other type of power outlet may
result in a shock hazard.
• Do not use extension cords or adapters with this Rack PDU.
• If a socket-outlet is not accessible to the equipment, a socket-outlet shall be installed.
• Do not work alone under hazardous conditions.
• Check that the power cord, plug, and socket are in good condition.
• Disconnect the Rack PDU from the power outlet before you install or connect equipment to reduce the risk
of electric shock when you cannot verify grounding. Reconnect the Rack PDU to the power outlet only after
you make all connections.
• Do not handle any kind of metallic connector before the power has been removed.
• Use one hand, whenever possible, to connect or disconnect signal cables to avoid a possible shock from
touching two surfaces with different grounds.
• This unit does not have any user-serviceable parts. Repairs are to be performed only by factory-trained
service personnel.
Failure to follow these instructions will result in death or serious injury.
990-6249 11/2019
Life Support Policy
General policy
APC by Schneider Electric does not recommend the use of any of its products in the following
situations:
• In life-support applications where failure or malfunction of the APC by Schneider Electric
product can be reasonably expected to cause failure of the life-support device or to affect
significantly its safety or effectiveness.
• In direct patient care.
APC by Schneider Electric will not knowingly sell its products for use in such applications unless it
receives in writing assurances satisfactory to APC by Schneider Electric that (a) the risks of injury or
damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of APC by
Schneider Electric is adequately protected under the circumstances.
Examples of life-support devices
The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve
stimulators (whether used for anesthesia, pain relief, or other purposes), autotransfusion devices,
blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems,
peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults and infants),
anesthesia ventilators, infusion pumps, and any other devices designated as “critical” by the U.S.
FDA.
Hospital-grade wiring devices and leakage current protection may be ordered as options on many
APC by Schneider Electric UPS systems. APC by Schneider Electric does not claim that units with
these modifications are certified or listed as hospital-grade APC by Schneider Electric or any other
organization. Therefore these units do not meet the requirements for use in direct patient care.
Radio frequency interference
Changes or modifications to this unit not expressly approved by the party responsible for compliance
could void the user's authority to operate this equipment.
Factory Warranty
This warranty applies only to the products you purchase for your use in accordance with this manual.
Terms of warranty
APC by Schneider Electric warrants its products to be free from defects in materials and
workmanship for a period of one year from the date of purchase. APC by Schneider Electric will
repair or replace defective products covered by this warranty. This warranty does not apply to
equipment that has been damaged by accident, negligence or misapplication or has been altered or
modified in any way. Repair or replacement of a defective product or part thereof does not extend the
original warranty period. Any parts furnished under this warranty may be new or
factory-remanufactured.
Non-transferable warranty
This warranty extends only to the original purchaser who must have properly registered the product.
The product may be registered at the APC by Schneider Electric website, www.apc.com.
Exclusions
APC by Schneider Electric shall not be liable under the warranty if its testing and examination
disclose that the alleged defect in the product does not exist or was caused by end user’s or any third
person’s misuse, negligence, improper installation or testing. Further, APC by Schneider Electric
shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or
inadequate electrical voltage or connection, inappropriate on-site operation conditions, corrosive
atmosphere, repair, installation, exposure to the elements, Acts of God, fire, theft, or installation
contrary to APC by Schneider Electric recommendations or specifications or in any event if the APC
by Schneider Electric serial number has been altered, defaced, or removed, or any other cause
beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR
OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT
OR IN CONNECTION HEREWITH. APC BY SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED
WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR
PURPOSE. APC BY SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE
ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE
OUT OF, APC BY SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND
REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE
WARRANTIES SET FORTH ABOVE CONSTITUTE APC BY SCHNEIDER ELECTRIC’S SOLE
LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT EXTENDED TO
ANY THIRD PARTIES.
IN NO EVENT SHALL APC BY SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL,
CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR
INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR
TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC BY
SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES. SPECIFICALLY, APC BY SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS,
SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF
EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUENTS, CLAIMS BY
THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC BY SCHNEIDER ELECTRIC IS AUTHORIZED
TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE
MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC BY SCHNEIDER ELECTRIC
OFFICER AND LEGAL DEPARTMENT.
Warranty claims
Customers with warranty claims issues may access the APC by Schneider Electric customer support
network through the Support page of the APC by Schneider Electric website, www.apc.com/support.
Select your country from the country selection pull-down menu at the top of the Web page. Select the
Support tab to obtain contact information for customer support in your region.

安装
将机架 PDU 安装在 19 英寸 NetShelter™机架或其他
EIA-310-D 标准 19 英寸机架中。选择机架 PDU 的安
装位置,使设备的前部或后部朝向机架。
1. 您的机架 PDU 将占用一 (1)个 U 空间。
注意:NetShelter 机架垂直导轨上的缺口孔表示
U 空间的中间位置
注意:正确安装锁紧螺母。 见插图。
2. 使用随附的硬件,四个 M6 x
16mm 螺钉和锁紧螺母将设备安
装在 NetShelter 机架或 EIA-
310-D 标准 19 英寸机架中。
规格参数
警告
起火危险
• 该设备应当连接到单一插座的专用电路,并利用具有与机架 PDU 相同电流等级的断路器或保
险丝加以保护。
• 插头或引入线用作机架 PDU 的断路器。确保机架 PDU 的市电电源插座靠近机架 PDU,且容
易接近。
• 一些型号的机架 PDU 提供有 IEC C14 或 C20 引入线。用户应负责使用合适的电源线。
否则,可能导致死亡或严重受伤。
电气参数
额定输入电压 200 - 240 VAC
最大输入电流 16A
额定输入频率 50/60Hz
输入接口 IEC-320 C13 (16A)
输出电压 200 - 240 VAC
单口输出电流 10A
最大输出总电流 16A
输出接口 IEC 320 C13 (10A)
插口数量 八 (8)
结构参数
产品尺寸 [ 高 X 宽 X 深 ] 44.4 x 482 x 44.4mm (1.75 x 19 x 1.75 in)
电源线的长度 2.5 m (8.2 ft)
包装尺寸 [ 高 X 宽 X 深 ] 150 x 560 x 80 mm (3.8 x 22.8 x 3.15 in)
产品重量 / 包装重量 0.58 kg (1.27 lb) / 1.18kg (2.60 lb)
适应环境
海拔高度 (基于平均海平面 )
工作条件 / 储存条件 0–3000 m (0–10,000 ft) / 0–15000 m (0–50,000 ft)
温度 : 工作条件 / 储存条件 –5 to 45°C (23 to 113°F) / –25 to 65°C (–13 to 149°F)
湿度 : 工作条件 / 储存条件 5–95% 相对湿度非凝结
认证
电磁兼容标准 遵循标准 EN55035, EN55032, EN55024
安全标准 CE, TUV, 遵循标准 EN/IEC62368-1
CE EU Contact Address Schneider Electric, 35 rue Joseph Monier
92500 Rueil Malmaison France
环境 RoHS & Reach
1 U
ns0750a
pdu0093b
生命支持政策
一般策略
APC by Schneider Electric 不建议在以下情况下使用其任何产品:
在 APC 产品的故障或失效可能导致生命保障设备的故障,或极大地影响其安全性或
效率的生命保障应用中。
直接护理病人。
APC by Schneider Electric 将不会有意地针对此类应用场合销售其产品,除非 APC by
Schneider Electric 收到令其满意的书面担保,明确表示:(a) 人身伤害或设备的损坏风险已
降至最低,(b) 客户承担所有风险,(c) 如有此类情况发生,APC 的责任将受到充分地保护。
生命保障设备的实例
生命保障设备
包括但不仅限于:新生儿氧气分析仪、神经模拟器 (用于麻醉、减轻疼痛
等)、自体输血设备、抽血、去纤颤器、心率不齐探测器和警报器、起搏器、血液透析系
统、腹膜透析系统、新生儿通风保育器、通风设备 (用于成人和婴儿)、麻醉手术通风设
备、输血以及由 U.S. FDA 指定为 “ 关键 ” 的其他设备。
对于很多 APC by Schneider Electric UPS 系统,可以作为可选项订购医院级的接线设备和
漏电保护设备。APC by Schneider Electric 未声明经过这些更改的设备经过 APC by
Schneider Electric 或其他组织验证或被列为医院级的设备。因此这些设备不符合直接护理
病人的要求。
射频干扰
未经合规负责方明确批准而对本设备进行更改或修改可能会使用户无权操作此设备。
一年出厂担保
此担保适用于购买后遵照手册进行使用的产品。
担保条款
APC by Schneider Electric 保证其产品自购买之日起一年内不会出现材料和工艺缺陷。APC
by Schneider Electric 将对本担保适用的故障产品提供修理或更换服务。本担保不适用于因
偶然、疏忽或误用所造成的损坏或以任何方式更改或改装过的产品。
故障产品或部件的修理或更换并不会延长原保修期。根据本担保所提供的任何部件可能是全
新的,也可能是工厂 - 翻新品。
不可转让担保
本担保只适用于适当注册过产品的原始购买者。可以通过 APC by Schneider Electric 网站
www.apc.com 注册该产品。
免责条款
若经 APC 测试和检测发现,购买者所声称的缺陷根本不存在或由购买者或任何第三方误用、
疏忽、安装或测试不当引起,则 APC by Schneider Electric 不给予保修服务。如属下列情
况,APC by Schneider Electric 亦不提供保修服务:未经授权擅自修理或改装、错误或不
当电压或连接、现场操作条件不当、腐蚀性环境、修理、安装和打开设备外壳、自然因素、
火灾、失窃,或不依照 APC by Schneider Electric 建议或规格安装或更改、损坏、移除
APC by Schneider Electric 序列号的任何情形,或者进行其它超出使用范围的操作。
对于根据本协议及其相关条款销售、维修或提供的产品,APC by Schneider Electric 在法
律或相关法规允许的范围内不提供任何明示或暗示的担保。对于本产品用于特殊目的适销
性、满意度和适用性,APC by Schneider Electric 不提供任何形式的暗示担保。APC by
Schneider Electric 的明示担保不应被扩展、缩减或受到责任义务影响,APC by Schneider
Electric 只提供与产品相关的技术或其他建议或服务。上述的担保和补救措施仅适用于本产
品并取代所有其他担保和补救措施。针对任何违反担保的情况,上述担保规定了 APC by
Schneider Electric 的全部责任以及购买者的全部补偿。APC by Schneider Electric 提供的
担保仅授予本产品购买者,任何第三方不得享受本担保。
APC by Schneider Electric 及其官员、主管、子公司或员工不对使用、修理或安装产品过
程中发生的任何间接的、特殊结果的或惩罚性的损害负责,不论此类损害是来自于合同或民
事侵权,不论是属于故障、疏忽或严格责任,或者 APC by Schneider Electric 是否已预先
被告知损害的可能性。特别需要指出的是,APC by Schneider Electric 对任何费用不承担
责任,例如损失利润和收入、设备损坏、无法使用设备、软件损坏、丢失数据、替代物的成
本、第三方索赔或其它方面的费用。
APC by Schneider Electric 的任何销售人员、雇员或代理商无权对本担保进行任何增补或
修改。如有必要,仅可由 APC by Schneider Electric 官员和法律部门以书面形式签署对本
担保条款的修改。
担保索赔
发生担保索赔问题的客户可以通过 APC by Schneider Electric 网站 www.apc.com/
support 上的 “ 支持 ” 页面访问 APC by Schneider Electric 客户支持网络。
从网页顶部的国家 / 地区选择下拉菜单中选择您的国家 / 地区。选择 “ 支持 ” 选项卡以获
得您所在地区的客户支持联系信息。
总览
此表提供了 Easy PDU 的安装信息。 请仔细阅读说明。
接收
检查包装和内容是否有运输损坏。 确保所有部件都已发送。 立即向运输代理商报告任何运输损坏。
请通过 apc.com 联系您的 APC by Schneider Electric 经销商或全球客户支持,以报告产品缺失的
内容,产品损坏或其他问题。
材料回收
运输材料是可回收的。 请妥善保管以备日后使用,或妥善处理。
安全
在安装或操作您的 APC by Schneider Electric Rack 配电单元 (PDU)之前,请阅读以下信息。
危险
触电、爆炸或电弧闪光的危险
• 如果盖板拆除,请勿操作机架 PDU。
• 内部没有用户可以检修的零件。请安排具有资历的人员进行检修。
• 连接固定和电缆控制附件时,只能使用我们提供的器件。
• 只能在室内的干燥位置使用。
• 安装机架 PDU 时,请遵守当地和国家的所有法规。
• 在无法确认是否接地时,在机架 PDU 连接设备前,请从市电电源插座断开机架 PDU。
• 机架 PDU 适当安装到机架式机柜,且完成了所有负载和信号连接后,在市电电源插座,连接
机架 PDU 的电源线。
• 确保市电电源插座和机架 PDU 电源线和插头状况良好。
• 请勿独自作业,亦不得在危险条件下作业。
• 高电流通过导电材料会引起严重烧伤。
• 检修负载设备或电源线前,从该产品断开负载电源线。
• 请务必使用具有合适额定电压的传感设备,确认电源已经关闭。
否则,可能导致死亡或严重受伤。
Basic Rack PDU 机架配电单元安装手册
EPDU1016B
全球客户支持
客户支持和保修信息,请访问:www.apc.com。
© 2019 施耐德电气 版权所有。
990-6249
11/2019