Galaxy VS
Parallel Maintenance Bypass Panel for Two UPSs
Installation
GVSBPAR10K30H, GVSBPAR40K50H, GVSBPAR60K120H
7/2019
www.schneider-electric.com

Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Go to
https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_iec/
or scan the QR code above for digital experience and translated manuals.

Parallel Maintenance Bypass Panel for Two UPSs
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS.........................................................................................5
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Additional Safety Precautions After Installation........................................8
Electrical Safety....................................................................................8
Specifications ..............................................................................................9
Recommended Upstream Protection............................................................9
Recommended Cable Sizes ......................................................................10
Torque Specifications................................................................................12
Parallel Maintenance Bypass Panel Weights and Dimensions......................13
Clearance ................................................................................................13
Environment.............................................................................................13
One Line Diagram ....................................................................................14
Installation Procedure ..............................................................................15
Mount the Parallel Maintenance Bypass Panel to the Wall ................16
Prepare for Cables....................................................................................19
Remove the Neutral Jumper (Option)....................................................20
Connect the Power Cables on GVSBPAR10K30H..............................22
Connect the Power Cables on GVSBPAR40K50H..............................23
Connect the Power Cables on GVSBPAR60K120H............................24
Connect the Signal Cables......................................................................25
Add Translated Safety Labels to Your Product.....................................27
990-91216A-001 3


Important Safety Instructions — SAVE THESE
INSTRUCTIONS Parallel Maintenance Bypass Panel for Two UPSs
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a “Danger” or “Warning” safety
message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990-91216A-001 5

Parallel Maintenance Bypass Panel for Two UPSs
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Electromagnetic Compatibility
NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product category C2 UPS product. In a residential environment, this
product may cause radio inference, in which case the user may be required to
take additional measures.
Failure to follow these instructions can result in equipment damage.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the installation manual before installing or working on
this product.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the product until all construction work has been completed and the
installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be installed according to the specifications and requirements
as defined by Schneider Electric. It concerns in particular the external and
internal protections (upstream breakers, battery breakers, cabling, etc.) and
environmental requirements. No responsibility is assumed by Schneider Electric
if these requirements are not respected.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
6 990-91216A-001

Important Safety Instructions — SAVE THESE
INSTRUCTIONS Parallel Maintenance Bypass Panel for Two UPSs
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the product in a temperature controlled indoor environment free of
conductive contaminants and humidity.
• Install the product on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product is not designed for and must therefore not be installed in the
following unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the installation manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE
RISK OF OVERHEATING
Respect the space requirements around the product and do not cover the
ventilation openings when the product is in operation.
Failure to follow these instructions can result in equipment damage.
990-91216A-001 7

Parallel Maintenance Bypass Panel for Two UPSs
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Additional Safety Precautions After Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned. If additional construction work is
needed in the installation room after this product has been installed, turn off the
product and cover the product with the protective packaging bag the product
was delivered in.
Failure to follow these instructions will result in death or serious injury.
Electrical Safety
This manual contains important safety instructions that should be followed during
the installation and maintenance of the UPS system.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
• Disconnection devices for AC and DC must be provided by others, be readily
accessible, and the function of the disconnect device marked for its function.
• Turn off all power supplying the UPS system before working on or inside the
equipment.
• Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
• The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the mains supply. Before installing or
servicing the UPS system, ensure that the units are OFF and that mains and
batteries are disconnected. Wait five minutes before opening the UPS to
allow the capacitors to discharge.
• The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
When the UPS input is connected through external isolators that, when opened,
isolate the neutral or when the automatic backfeed isolation is provided external to
the equipment or is connected to an IT power distribution system, a label must be
fitted at the UPS input terminals, and on all primary power isolators installed
remotely from the UPS area and on external access points between such isolators
and the UPS, by the user, displaying the following text (or equivalent in a language
which is acceptable in the country in which the UPS system is installed):
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of voltage backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective
earth.
Failure to follow these instructions will result in death or serious injury.
8 990-91216A-001

Specifications Parallel Maintenance Bypass Panel for Two UPSs
Specifications
NOTE: Maximum short circuit rating: 10 kA RMS symmetrical.
For a 1+1 parallel system for redundancy, the parallel maintenance bypass panel
can support a load of up to 120 kW/kVA as long as the neutral current (250 A) is
not exceeded:
• at 380 V, the maximum neutral current capability is reached with a 95 kVA
non-linear load.
• at 400 V, the maximum neutral current capability is reached with a 100 kVA
non-linear load.
For a 2+0 parallel system for capacity, the parallel maintenance bypass panel can
support a load of up to 240 kW/kVA as long as the neutral current (500 A) is not
exceeded:
• at 380 V, the maximum neutral current capability is reached with a 190 kVA
non-linear load.
• at 400 V, the maximum neutral current capability is reached with a 200 kVA
non-linear load.
Recommended Upstream Protection
NOTE: For local directives which require 4-pole circuit breakers: If neutral
conductor is expected to carry a high current, due to line-neutral non-linear
load, the circuit breaker must be rated according to expected neutral current.
Upstream Input Breaker
Commercial
reference
GVSBPAR10K30H
Parallel system
type
Capacity (2+0) Redundancy (1+1)
Parallel system
rating
20 kW 40 kW 60 kW 10 kW 20 kW 30 kW
Breaker type LV429674 LV429671 LV430671 LV429676 LV429674 LV429672
In (A) 40 80 125 25 40 63
Ir (A) 40 80 125 20 40 63
Im (A) 500 (fixed) 640 (fixed) 1250 (fixed) 300 (fixed) 500 (fixed)
Upstream Input Breaker
Commercial
reference
GVSBPAR40K50H
Parallel system
type
Capacity (2+0) Redundancy (1+1)
Parallel system
rating
80 kW 100 kW 40 kW 50 kW
Breaker type LV430670 LV431671 LV429671 LV429670
In (A) 160 200 80 100
Ir (A) 160 200 80 100
Im (A) 1250 (fixed) 5-10 x In 640 (fixed) 800 (fixed)
990-91216A-001 9

Parallel Maintenance Bypass Panel for Two UPSs Specifications
Upstream Input Breaker
Commercial
reference
GVSBPAR60K120H
Parallel system
type
Capacity (2+0) Redundancy (1+1)
Parallel system
rating
120 kW 160 kW 200 kW 240 kW 60 kW 80 kW 100 kW 120 kW
Breaker type LV431670 LV432695 LV432695 LV432895 LV430671 LV430670 LV431671 LV431670
In (A) 250 320 400 500 125 160 200 250
Ir (A) 250 1 0.94 125 160 200 250
Im (A) / Isd (A) 5-10 x In 1.5-10 1250 (fixed) 5-10 x In
Recommended Cable Sizes
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
• The maximum allowable input cable and load cable size is 35 mm2and the
maximum allowable UPS input/output cable size is 16 mm2for
GVSBPAR10K30H.
• The maximum allowable input cable and load cable size is 70 mm2and the
maximum allowable UPS input/output cable size is 25 mm2for
GVSBPAR40K50H.
• The maximum allowable input cable and load cable size is 185 mm2and the
maximum allowable UPS input/output cable size is 50 mm2for
GVSBPAR60K120H.
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection is to be provided by others.
Cable sizes in this manual are based on table B.52.5 of IEC 60364-5-52 with the
following assertions:
• 90 °C conductors
• An ambient temperature of 30 °C
• Use of copper or aluminum conductors
• Installation method C
PE size is based on table 54.2 of IEC 60364-4-54.
If the ambient temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the IEC. Aluminum cables
are not recommended for ambient temperatures over 30 °C.
10 990-91216A-001

Specifications Parallel Maintenance Bypass Panel for Two UPSs
Copper
Commercial
reference
GVSBPAR10K30H GVSBPAR40K50H
Parallel system
type
Capacity (2+0) Redundancy (1+1) Capacity (2+0) Redundancy (1+1)
Parallel system
rating
20 kW 40 kW 60 kW 10 kW 20 kW 30 kW 80 kW 100 kW 40 kW 50 kW
Input (mm2) 6 16 35 6 6 10 50 70 16 25
Input PE (mm2) 6 16 16 6 6 10 25 35 16 16
Input N (mm2)110 35 2 x 16 6 10 16 2 x 50 2 x 70 35 50
UPS input (mm2) 6 6 10 6 6 10 16 25 16 25
UPS output (mm2) 6 6 10 6 6 10 16 16 16 16
UPS PE (mm2) 6 6 10 6 6 10 16 16 16 16
UPS N (mm2)16 10 16 6 10 16 2 x 16 2 x 16 2 x 16 2 x 16
Load (mm2) 6 16 25 6 6 10 50 70 16 16
Load PE (mm2) 6 16 16 6 6 10 25 35 16 16
Load N (mm2)110 35 2 x 16 6 10 16 2x50 2x70 35 50
Copper
Commercial
reference
GVSBPAR60K120H
Parallel system
type
Capacity (2+0) Redundancy (1+1)
Parallel system
rating
120 kW 160 kW 200 kW 240 kW 60 kW 80 kW 100 kW 120 kW
Input (mm2) 95 120 185 2 x 120 35 50 70 95
Input PE (mm2) 50 70 95 120 25 25 35 50
Input N (mm2)1120 2 x 120 2 x 150 3 x 150 50 95 120 120
UPS input (mm2) 35 50 2 x 25 2 x 50 35 50 2 x 25 2 x 50
UPS output (mm2) 25 50 2 x 25 2 x 35 25 50 2 x 25 2 x 35
UPS PE (mm2) 25 25 35 50 25 25 35 50
UPS N (mm2)150 95 3 x 35 3 x 35 50 2 x 50 3 x 35 3 x 35
Load (mm2) 95 120 185 2 x 95 25 50 70 95
Load PE (mm2) 50 70 95 95 16 25 35 50
Load N (mm2)1120 2 x 120 2 x 150 3 x 150 50 95 120 120
Aluminum
Commercial
reference
GVSBPAR10K30H GVSBPAR40K50H
Parallel system
type
Capacity (2+0) Redundancy (1+1) Capacity (2+0) Redundancy (1+1)
Parallel system
rating
20 kW 40 kW 60 kW 10 kW 20 kW 30 kW 80 kW 100 kW 40 kW 50 kW
Input (mm2) 6 25 NA 6 6 NA 70 NA 25 NA
Input PE (mm2) 6 16 NA 6 6 NA 35 NA 16 NA
Input N (mm2)12 x 16 2 x 16 NA 6 16 NA 2 x 70 NA 50 NA
990-91216A-001 11
1. Neutral conductor is sized to handle 1.73 times phase current in case of high harmonic content from non-linear loads. If no or low
harmonic currents are expected, the neutral conductor can be sized as the phase conductor.

Parallel Maintenance Bypass Panel for Two UPSs Specifications
Aluminum (Continued)
Commercial
reference
GVSBPAR10K30H GVSBPAR40K50H
Parallel system
type
Capacity (2+0) Redundancy (1+1) Capacity (2+0) Redundancy (1+1)
Parallel system
rating
20 kW 40 kW 60 kW 10 kW 20 kW 30 kW 80 kW 100 kW 40 kW 50 kW
UPS input (mm2) 6 6 NA 6 6 NA 25 NA 25 NA
UPS output (mm2) 6 6 NA 6 6 NA 16 NA 16 NA
UPS PE (mm2) 6 6 NA 6 6 NA 16 NA 16 NA
UPS N (mm2)26 16 NA 6 16 NA 2 x 16 NA 2 x 16 NA
Load (mm2) 6 16 NA 6 6 NA 70 NA 16 NA
Load PE (mm2) 6 16 NA 6 6 NA 35 NA 16 NA
Load N (mm2)216 2 x 16 NA 6 2 x 16 NA 2 x 70 NA 50 NA
Aluminum
Commercial
reference
GVSBPAR60K120H
Parallel system
type
Capacity (2+0) Redundancy (1+1)
Parallel system
rating
120 kW 160 kW 200 kW 240 kW 60 kW 80 kW 100 kW 120 kW
Input (mm2) 150 185 2 x 120 NA 50 70 95 NA
Input PE (mm2) 95 95 150 NA 25 70 50 NA
Input N (mm2)2185 2 x 120 3 x 150 NA 70 150 185 NA
UPS input (mm2) 50 2 x 35 2 x 50 NA 50 2 x 35 2 x 50 NA
UPS output (mm2) 50 2 x 35 2 x 35 NA 50 2 x 35 2 x 35 NA
UPS PE (mm2) 25 35 50 NA 25 35 50 NA
UPS N (mm2)22 x 35 3 x 35 3 x 50 NA 2 x 35 3 x 35 3 x 50 NA
Load (mm2) 120 185 2 x 120 NA 50 70 95 NA
Load PE (mm2) 70 95 120 NA 25 35 50 NA
Load N (mm2)2185 2 x 120 4 x 95 NA 70 150 185 NA
Torque Specifications
Bolt size Torque
M4 1.7 Nm
M5 2.2 Nm
M6 5 Nm
M8 17.5 Nm
M10 30 Nm
12 990-91216A-001
2. Neutral conductor is sized to handle 1.73 times phase current in case of high harmonic content from non-linear loads. If no or low
harmonic currents are expected, the neutral conductor can be sized as the phase conductor.

Specifications Parallel Maintenance Bypass Panel for Two UPSs
Parallel Maintenance Bypass Panel Weights and Dimensions
Commercial reference Weight kg Height mm Width mm Depth mm
GVSBPAR10K30H 35 700 650 210
GVSBPAR40K50H 50 850 750 250
GVSBPAR60K120H 83 1000 900 280
Clearance
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
Environment
Operating Storage
Temperature 0 °C to 40 °C -25 °C to 55 °C
Relative humidity 0-95% non-condensing 0-95% non-condensing
Elevation 0-3000 m
Protection class IP20
Color RAL 9003, gloss level 85%
990-91216A-001 13

Parallel Maintenance Bypass Panel for Two UPSs Specifications
One Line Diagram
UIB1 Unit input breaker for UPS 1
UIB2 Unit input breaker for UPS 2
MBB Maintenance bypass breaker
IMB Internal maintenance breaker
UOB1 Unit output breaker for UPS 1
UOB2 Unit output breaker for UPS 2
BB Battery breaker
The parallel maintenance bypass panel is used in single mains systems to parallel
two UPSs for either capacity or redundancy.
NOTE: The internal maintenance breaker IMB* in the UPS cannot be used in
a system with a parallel maintenance bypass panel and the internal
maintenance breaker IMB* must be padlocked in the open position.
14 990-91216A-001

Installation Procedure Parallel Maintenance Bypass Panel for Two UPSs
Installation Procedure
1. Mount the Parallel Maintenance Bypass Panel to the Wall, page 16.
2. Prepare for Cables, page 19.
3. Only in countries where required: Remove the Neutral Jumper (Option), page
20.
4. Perform one of the following:
–Connect the Power Cables on GVSBPAR10K30H, page 22, or
–Connect the Power Cables on GVSBPAR40K50H, page 23, or
–Connect the Power Cables on GVSBPAR60K120H, page 24.
5. Connect the Signal Cables, page 25.
6. Add Translated Safety Labels to Your Product, page 27.
990-91216A-001 15

Parallel Maintenance Bypass Panel for Two UPSs Mount the Parallel Maintenance Bypass Panel to the Wall
Mount the Parallel Maintenance Bypass Panel to the
Wall
CAUTION
RISK OF INJURY OR EQUIPMENT DAMAGE
• Mount the parallel maintenance bypass panel to a wall or a rack that is
structurally sound and able to support the weight of the unit.
• Use appropriate hardware for the wall/rack type.
Failure to follow these instructions can result in injury or equipment
damage.
16 990-91216A-001

Mount the Parallel Maintenance Bypass Panel to the Wall Parallel Maintenance Bypass Panel for Two UPSs
1. Measure and mark the four mounting hole locations on the wall.
GVSBPAR10K30H GVSBPAR40K50H
GVSBPAR60K120H
2. Drill holes in each of the four marked locations and mount the anchor bolts.
990-91216A-001 17

Prepare for Cables Parallel Maintenance Bypass Panel for Two UPSs
Prepare for Cables
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or punch holes with the gland plates installed and do not drill or
punch holes in close proximity to the cabinet.
Failure to follow these instructions will result in death or serious injury.
1. Remove the bottom gland plates.
2. Drill or punch holes for power cables and signal cables or grommets in the
gland plates. UPS input (A), input (B), load (C), UPS output (D).
3. Install grommets (if applicable) and reinstall the gland plates.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Ensure that there are no sharp edges that can damage the cables.
Failure to follow these instructions will result in death or serious
injury.
990-91216A-001 19

Parallel Maintenance Bypass Panel for Two UPSs Remove the Neutral Jumper (Option)
Remove the Neutral Jumper (Option)
NOTE: The neutral jumper makes a bolted connection of the neutral so that
the neutral is not disconnected when the 4-pole breakers are opened. Only
remove the neutral jumpers if this is a local requirement.
1. Remove the neutral jumpers (cable and/or busbar) between UOB1 and
UOB2. Reinstall the screws in the same position.
2. Remove the neutral jumpers on the MBB (cable or busbar).
GVSBPAR10K30H
20 990-91216A-001

Parallel Maintenance Bypass Panel for Two UPSs Connect the Power Cables on GVSBPAR10K30H
Connect the Power Cables on GVSBPAR10K30H
1. Connect the PE cables to the PE busbar.
2. Connect the input cables from utility/mains.
3. Connect the UPS input cables from UPS 1.
4. Connect the UPS input cables from UPS 2.
5. Connect the UPS output cables from UPS 1.
6. Connect the UPS output cables from UPS 2.
7. Connect the load cables.
8. Fasten the cables with cable ties (provided) to the cable reliefs as shown.
22 990-91216A-001

Connect the Power Cables on GVSBPAR40K50H Parallel Maintenance Bypass Panel for Two UPSs
Connect the Power Cables on GVSBPAR40K50H
1. Connect the PE cables to the PE busbar.
2. Connect the input cables from utility/mains.
3. Connect the UPS input cables from UPS 1.
4. Connect the UPS input cables from UPS 2.
5. Connect the UPS output cables from UPS 1.
6. Connect the UPS output cables from UPS 2.
7. Connect the load cables.
8. Fasten the cables with cable ties (provided) to the cable reliefs as shown.
990-91216A-001 23

Parallel Maintenance Bypass Panel for Two UPSs Connect the Power Cables on GVSBPAR60K120H
Connect the Power Cables on GVSBPAR60K120H
1. Connect the PE cables to the PE busbar.
2. Connect the input cables from utility/mains.
3. Connect the UPS input cables from UPS 1.
4. Connect the UPS input cables from UPS 2.
5. Connect the UPS output cables from UPS 1.
6. Connect the UPS output cables from UPS 2.
7. Connect the load cables.
8. Fasten the cables with cable ties (provided) to the cable reliefs as shown.
24 990-91216A-001

Connect the Signal Cables Parallel Maintenance Bypass Panel for Two UPSs
Connect the Signal Cables
NOTE: Route the signal cables separately from the power cables and route
the Class 2/SELV cables separately from the non-Class 2/non-SELV cables.
1. Connect the Class 2/SELV signal cables for the breaker indicator lights from
the control terminal block in the parallel maintenance bypass panel to UPS 1
and UPS 2.
NOTE: The breaker indicator light circuit is considered Class 2/SELV.
Class 2/SELV circuits must be isolated from the primary circuitry. Do not
connect any circuit to the breaker indicator light terminals unless it can be
confirmed that the circuit is Class 2/SELV.
2. Connect the non-Class 2/non-SELV signal cables from the control terminal
block in the parallel maintenance bypass panel to UPS 1 and UPS 2.
3. Pull up the slack in the signal cables and fasten the signal cables to the cable
reliefs.
990-91216A-001 25

Add Translated Safety Labels to Your Product Parallel Maintenance Bypass Panel for Two UPSs
Add Translated Safety Labels to Your Product
The safety labels on your product are in English and French. Sheets with
translated safety labels are provided with your product.
1. Find the sheets with translated safety labels provided with your product.
2. Check which 885-XXX numbers are on the sheet with translated safety
labels.
3. Locate the safety labels on your product that match the translated safety
labels on the sheet – look for the 885-XXX numbers.
4. Add the replacement safety label in your preferred language to your product
on top of the existing French safety label.
990-91216A-001 27

Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
*990-91216A-001*
As standards, specifications, and design change from time to time,
please ask for confirmation of the information given in this publication.
© 2019 – 2019 Schneider Electric. All rights reserved.
990-91216A-001