APC GVSMODBC6 User Manual
Displayed below is the user manual for GVSMODBC6 by APC which is a product in the UPS Battery Cabinets category. This manual has pages.
Related Manuals

Galaxy VS
Modular Battery Cabinet
Installation
Up to 6 Battery Strings
GVSMODBC6
6/2019
www.schneider-electric.com

Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Go to
IEC: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_iec/ or
UL: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_ul/
or scan the QR code above for digital experience and translated manuals.

Modular Battery Cabinet
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS.........................................................................................5
FCC Statement ..........................................................................................6
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Additional Safety Precautions After Installation........................................8
Electrical Safety .........................................................................................8
Battery Safety ............................................................................................9
Modular Battery Cabinet Specifications ................................................10
Torque Specifications................................................................................12
Modular Battery Cabinet Weights and Dimensions ......................................12
Clearance ................................................................................................12
Environment.............................................................................................13
Overview of Installation Kits ....................................................................14
Installation Procedure ..............................................................................17
Prepare for Installation.............................................................................19
Install the Conduit Box on the Modular Battery Cabinet .....................20
Prepare Modular Battery Cabinet 1 for Signal Cables ........................21
Install the Seismic Anchoring (Option) ..................................................22
Interconnect Modular Battery Cabinet 1 and the Adjacent UPS
with Internal Batteries...............................................................................23
Interconnect Modular Battery Cabinet 1 and the Adjacent UPS
for External Batteries................................................................................24
Interconnect the Modular Battery Cabinets ..........................................27
Connect the Power Cables for a UPS Rated for Maximum 50
kW ...............................................................................................................28
Connect the Power Cables for a UPS Rated over 50 kW ...................31
Connect the Signal Cables......................................................................34
Add Translated Safety Labels to Your Product.....................................38
Final Installation ........................................................................................39
990-91263-001 3


Important Safety Instructions — SAVE THESE
INSTRUCTIONS Modular Battery Cabinet
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a “Danger” or “Warning” safety
message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990-91263-001 5

Modular Battery Cabinet
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
FCC Statement
NOTE: This equipment has been tested and found to comply with the limits for
a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.
Electromagnetic Compatibility
NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product category C2 UPS product. In a residential environment, this
product may cause radio inference, in which case the user may be required to
take additional measures.
Failure to follow these instructions can result in equipment damage.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the installation manual before installing or working on
this product.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the product until all construction work has been completed and the
installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be installed according to the specifications and requirements
as defined by Schneider Electric. It concerns in particular the external and
internal protections (upstream breakers, battery breakers, cabling, etc.) and
environmental requirements. No responsibility is assumed by Schneider Electric
if these requirements are not respected.
Failure to follow these instructions will result in death or serious injury.
6 990-91263-001

Important Safety Instructions — SAVE THESE
INSTRUCTIONS Modular Battery Cabinet
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the product in a temperature controlled indoor environment free of
conductive contaminants and humidity.
• Install the product on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product is not designed for and must therefore not be installed in the
following unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the installation manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
990-91263-001 7

Modular Battery Cabinet
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE
RISK OF OVERHEATING
Respect the space requirements around the product and do not cover the
ventilation openings when the product is in operation.
Failure to follow these instructions can result in equipment damage.
Additional Safety Precautions After Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned. If additional construction work is
needed in the installation room after this product has been installed, turn off the
product and cover the product with the protective packaging bag the product
was delivered in.
Failure to follow these instructions will result in death or serious injury.
Electrical Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
• Turn off all power supplying the UPS system before working on or inside the
equipment.
• Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
• The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the utility/mains supply. Before
installing or servicing the UPS system, ensure that the units are OFF and
that utility/mains and batteries are disconnected. Wait five minutes before
opening the UPS to allow the capacitors to discharge.
• A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. This disconnection device must be easily
accessible and visible.
• The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
8 990-91263-001

Important Safety Instructions — SAVE THESE
INSTRUCTIONS Modular Battery Cabinet
Battery Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
• Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
• Disconnect charging source prior to connecting or disconnecting battery
terminals.
• Do not dispose of batteries in a fire as they can explode.
• Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting battery
terminals.
• Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply
circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.
NOTICE
RISK OF EQUIPMENT DAMAGE
• Wait until the system is ready to be powered up before installing batteries in
the system. The time duration from battery installation until the UPS system
is powered up must not exceed 72 hours or 3 days.
• Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period,
Schneider Electric recommends that you energize the UPS system for a
period of 24 hours at least once every month. This charges the batteries,
thus avoiding irreversible damage.
Failure to follow these instructions can result in equipment damage.
990-91263-001 9

Modular Battery Cabinet Modular Battery Cabinet Specifications
Modular Battery Cabinet Specifications
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Refer to the UPS installation manual for detailed specifications for the UPS
system.
Failure to follow these instructions can result in equipment damage.
Maximum four modular battery cabinets can be connected to a UPS.
Number of battery blocks 40
Number of battery strings Up to 6
Nominal battery voltage (VDC) 480
Nominal float voltage (VDC) 545
Maximum boost voltage (VDC) 571
Temperature compensation Enabled
End of discharge voltage (full load) (VDC) 384
Maximum battery current (A) 150
Maximum short circuit rating 3.8 kA
Trip Settings for Battery Breaker
Breaker type JDF36150
Ir (A) 150 (fixed)
Im 5-10 Ir
10 990-91263-001

Modular Battery Cabinet Specifications Modular Battery Cabinet
Recommended Cable Sizes for 380/400/415 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection is to be provided by others.
Cable sizes in this manual are based on table B.52.3 and table B.52.5 of IEC
60364-5-52 with the following assertions:
• 90 °C conductors
• An ambient temperature of 30 °C
• Use of copper conductors
• Installation method C
PE cable size is based on table 54.2 of IEC 60364-4-54.
If the ambient temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the IEC.
DC+/DC- 35 mm2
DC PE 16 mm2
Recommended Cable Sizes for 200/208/220/480 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
Cable sizes in this manual are based on Table 310.15 (B)(16) of the National
Electrical Code (NEC) with the following assertions:
• 90 °C (194 °F) conductors (75 °C (167 °F) termination)
• An ambient temperature of 30 °C (86 °F)
• Use of copper conductors
Equipment grounding conductors (PE in this manual) are sized in accordance with
NEC Article 250.122 and Table 250.122.
If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to
be selected in accordance with the correction factors of the NEC.
DC+/DC- 1 AWG
DC PE 6 AWG
990-91263-001 11

Modular Battery Cabinet Modular Battery Cabinet Specifications
Torque Specifications
Bolt size Torque
M4 1.7 Nm (1.25 lb-ft / 15 lb-in)
M5 2.2 Nm (1.62 lb-ft / 19.5 lb-in)
M6 5 Nm (3.69 lb-ft / 44.3 lb-in)
M8 17.5 Nm (12.91 lb-ft / 154.9 lb-in)
M10 30 Nm (22 lb-ft / 194.7 lb-in)
Modular Battery Cabinet Weights and Dimensions
Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
GVSMODBC6
– Empty
– With six battery strings
145 (319.67)
913 (2012.82)
1485 (58.46) 521 (20.51) 847 (33.35)
NOTE: One battery module weighs approximately 32 kg (70.5 lbs).
Clearance
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
NOTE: The required minimum rear clearance is 150 mm (5.91 in).
12 990-91263-001

Modular Battery Cabinet Overview of Installation Kits
Overview of Installation Kits
Installation Kit 0H-9330
Part Used in Number of units
Baying cover Interconnect Modular Battery Cabinet 1 and the Adjacent
UPS with Internal Batteries, page 23, or Interconnect
Modular Battery Cabinet 1 and the Adjacent UPS for
External Batteries, page 24, and Interconnect the
Modular Battery Cabinets, page 27.
1
PE cable 0W49449 Connect the Power Cables for a UPS Rated for Maximum
50 kW, page 28 or Connect the Power Cables for a UPS
Rated over 50 kW, page 31.
1
DC cable 0W49426 Connect the Power Cables for a UPS Rated for Maximum
50 kW, page 28.
2
Installation Kit 0H-9332
Part Used in Number of units
M6 x 16 mm screw with washer Interconnect Modular Battery Cabinet 1 and the Adjacent
UPS with Internal Batteries, page 23 and Interconnect the
Modular Battery Cabinets, page 27.
9
Interconnection bracket 3
M6 nut with washer Connect the Power Cables for a UPS Rated for Maximum
50 kW, page 28 or Connect the Power Cables for a UPS
Rated over 50 kW, page 31.
5
M6 x 20 mm bolt with washer 6
Signal cable 0W12680 Connect the Signal Cables, page 34. 1
Signal cable 0W76629 1
Cable ties Connect the Power Cables for a UPS Rated for Maximum
50 kW, page 28 or Connect the Power Cables for a UPS
Rated over 50 kW, page 31.
18
14 990-91263-001

Overview of Installation Kits Modular Battery Cabinet
Optional Seismic Kit GVSOPT002
Part Used in Number of units
M8 x 20 mm bolt with washer Install the Seismic Anchoring (Option), page 22 and Final
Installation, page 39.
12
Rear anchor 1
Rear anchoring bracket 1
Front anchoring bracket 1
Rear connection plate 1
990-91263-001 15

Modular Battery Cabinet Overview of Installation Kits
Optional Kit GVSOPT030
Only for installation with an adjacent UPS for external batteries.
Part Used in Number of units
Interconnection clamp Interconnect Modular Battery Cabinet 1 and the Adjacent
UPS for External Batteries, page 24.
3
M6 x 16 mm screw with washer 3
M6 nut with washer 3
M8 x 25 mm bolt with washer Connect the Power Cables for a UPS Rated for Maximum
50 kW, page 28 or Connect the Power Cables for a UPS
Rated over 50 kW, page 31.
9
M8 nut with washer 9
PE cable 0W13065 (for modular battery cabinet 1) 1
DC cable 0W13071 (for modular battery cabinet 1) 1
DC cable 0W13066 (for modular battery cabinet 2) Connect the Power Cables for a UPS Rated over 50 kW,
page 31.
1
DC cable 0W13068 (for modular battery cabinet 3) 1
DC cable 0W13067 (for modular battery cabinet 4) 1
Signal cable 0W13070 Connect the Signal Cables, page 34. 1
Signal cable 0W13069 1
Cable tie Connect the Power Cables for a UPS Rated for Maximum
50 kW, page 28 or Connect the Power Cables for a UPS
Rated over 50 kW, page 31.
18
Cable tie Interconnect Modular Battery Cabinet 1 and the Adjacent
UPS for External Batteries, page 24.
30
16 990-91263-001

Installation Procedure Modular Battery Cabinet
Installation Procedure
Modular Battery Cabinets and Adjacent UPS Rated
for Maximum 50 kW
Modular Battery Cabinets and Remote UPS Rated
for Maximum 50 kW
Modular Battery Cabinets and Adjacent UPS Rated
over 50 kW
Modular Battery Cabinets and Remote UPS Rated
over 50 kW
NOTE: The distance between the modular battery cabinet(s) and the UPS
must not exceed 100 m. Contact Schneider Electric for installations with a
longer distance.
1. Follow the UPS manual to prepare the UPS for installation.
2. Prepare for Installation, page 19.
3. For remote installation:
a. Install the Conduit Box on the Modular Battery Cabinet, page 20, and
b. Prepare Modular Battery Cabinet 1 for Signal Cables, page 21.
4. Option: Install the Seismic Anchoring (Option), page 22.
5. For adjacent installation: Perform one of the following:
–Interconnect Modular Battery Cabinet 1 and the Adjacent UPS with
Internal Batteries, page 23, or
–Interconnect Modular Battery Cabinet 1 and the Adjacent UPS for External
Batteries, page 24.
6. Interconnect the Modular Battery Cabinets, page 27.
990-91263-001 17

Modular Battery Cabinet Installation Procedure
7. Perform one of the following:
–Connect the Power Cables for a UPS Rated for Maximum 50 kW, page 28,
or
–Connect the Power Cables for a UPS Rated over 50 kW, page 31.
8. Connect the Signal Cables, page 34.
9. Add Translated Safety Labels to Your Product, page 38.
10. Final Installation, page 39.
18 990-91263-001

Prepare for Installation Modular Battery Cabinet
Prepare for Installation
1. Remove the front panel.
2. Remove the upper plate.
3. Remove the transparent plate.
4. Remove the top cover.
5. Remove side panels that will be adjacent to another modular battery cabinet
or an adjacent UPS.
6. Remove the cover from board 640-7552.
7. Remove the battery cover.
990-91263-001 19

Modular Battery Cabinet Install the Conduit Box on the Modular Battery Cabinet
Install the Conduit Box on the Modular Battery
Cabinet
1. Remove the conduit box from the rear of the modular battery cabinet(s).
Rear View of the Modular Battery Cabinet
2. Remove the top or bottom gland plate from the conduit box.
3. Drill/punch holes for power cables/conduits in the top or bottom gland plate.
Install conduits (not provided), if applicable.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or punch holes with the gland plates installed and do not drill or
punch holes in close proximity to the cabinet.
Failure to follow these instructions will result in death or serious
injury.
4. Reinstall the top or bottom gland plate on the conduit box.
5. Install the conduit box on the modular battery cabinet(s). Note that the conduit
box is installed in the reverse position.
Rear View of the Modular Battery Cabinet
20 990-91263-001

Prepare Modular Battery Cabinet 1 for Signal Cables Modular Battery Cabinet
Prepare Modular Battery Cabinet 1 for Signal Cables
1. Remove the gland plates and the brush plates from the rear of modular
battery cabinet 1.
Rear View of Modular Battery Cabinet 1
2. Perform one of the following:
–For installation without conduits: Reinstall the brush plates.
–For installation with conduits: Drill a hole in the gland plates for
conduits, install conduits, and reinstall the gland plates.
Rear View of Modular Battery Cabinet 1 without
Conduits
Rear View of Modular Battery Cabinet 1 with
Conduits
3. Route the Class 2/SELV signal cable through the left gland plate and into
modular battery cabinet 1.
4. Route the non-Class 2/non-SELV signal cable through the right gland plate
and into modular battery cabinet 1.
990-91263-001 21

Modular Battery Cabinet Install the Seismic Anchoring (Option)
Install the Seismic Anchoring (Option)
1. Mount the rear anchor(s) to the floor. Use appropriate hardware for the floor
type – the hole diameter in the rear anchor is ø14 mm. Use the rear
interconnection plate with multiple modular battery cabinets and/or an
adjacent UPS.
2. Install the rear anchoring bracket on the modular battery cabinet(s) with the
provided M8 bolts.
Rear View of the Modular Battery Cabinet
22 990-91263-001

Interconnect Modular Battery Cabinet 1 and the Adjacent UPS
with Internal Batteries Modular Battery Cabinet
Interconnect Modular Battery Cabinet 1 and the
Adjacent UPS with Internal Batteries
1. Push modular battery cabinet 1 and the UPS into place.
2. Install the three interconnection brackets between modular battery cabinet 1
and the UPS.
3. Install the three interconnection screws between modular battery cabinet 1
and the UPS.
4. Push the baying cover down between modular battery cabinet 1 and the UPS.
Modular Battery Cabinet 1 and the UPS
990-91263-001 23

Modular Battery Cabinet
Interconnect Modular Battery Cabinet 1 and the Adjacent
UPS for External Batteries
Interconnect Modular Battery Cabinet 1 and the
Adjacent UPS for External Batteries
1. Push the UPS into place.
2. Install the three interconnection clamps on modular battery cabinet 1.
Rear View of Modular Battery Cabinet 1
24 990-91263-001

Interconnect Modular Battery Cabinet 1 and the Adjacent UPS
for External Batteries Modular Battery Cabinet
3. Fasten the DC cables and the PE cable from optional kit GVSOPT030 on the
right side of modular battery cabinet 1 with the provided cable ties. Place the
cable ends temporarily in the top and in the bottom shelf of modular battery
cabinet 1, so the cables do not get damaged during the interconnection with
the UPS. Cable connections are described in Connect the Power Cables for a
UPS Rated for Maximum 50 kW, page 28 or Connect the Power Cables for a
UPS Rated over 50 kW, page 31.
Adjacent UPS for External Batteries Rated for
Maximum 50 kW
Adjacent UPS for External Batteries Rated over 50
kW
4. Align modular battery cabinet 1 with the UPS. Push in modular battery cabinet
1 until the holes for the front interconnection screws are aligned with the holes
in the UPS. The interconnection clamps will connect to the UPS when in the
correct position.
5. Install the three interconnection screws between modular battery cabinet 1
and the UPS.
990-91263-001 25

Interconnect the Modular Battery Cabinets Modular Battery Cabinet
Interconnect the Modular Battery Cabinets
1. Push the modular battery cabinets into place. For seismic anchoring, ensure
that the rear anchoring brackets connects to the rear anchors.
2. Install the three interconnection brackets between the modular battery
cabinets.
3. Install the three interconnection screws between the modular battery
cabinets.
4. Push the baying cover down between the modular battery cabinets.
990-91263-001 27

Modular Battery Cabinet
Connect the Power Cables for a UPS Rated for Maximum 50
kW
Connect the Power Cables for a UPS Rated for
Maximum 50 kW
NOTICE
RISK OF EQUIPMENT DAMAGE
Only connect the DC cables from battery breaker to battery breaker in
installations with a UPS rated for maximum 50 kW. For installations with a UPS
rated over 50 kW, the DC cables from each modular battery cabinet must be
connected directly in the UPS. See Connect the Power Cables for a UPS Rated
over 50 kW, page 31.
Failure to follow these instructions can result in equipment damage.
1. Connect the provided PE cable (0W49449) between the modular battery
cabinets as shown.
Front View of Two Modular Battery Cabinets
2. Connect the provided DC cables (0W49426) between the modular battery
cabinets as shown.
Top View of the Modular Battery Cabinets
28 990-91263-001

Connect the Power Cables for a UPS Rated for Maximum 50
kW Modular Battery Cabinet
3. For remote UPS:
a. Connect the PE cable and the DC cables (not provided) in modular
battery cabinet 1.
b. Route the PE and DC cables out through the conduit box and into the
UPS power cabling area.
c. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front View of Modular Battery Cabinet 1 for Remote UPS
4. For adjacent UPS with internal batteries:
a. Connect the provided PE cable (0W49449) and DC cables (0W49426) in
the UPS. Follow the UPS installation manual to connect and route the PE
cable and DC cables in the UPS.
b. Connect the PE and DC cables in modular battery cabinet 1.
Front View of Modular Battery Cabinet 1 for Adjacent UPS
990-91263-001 29

Modular Battery Cabinet
Connect the Power Cables for a UPS Rated for Maximum 50
kW
5. For adjacent UPS for external batteries:
a. Connect the PE cable (0W13065) and the DC cables (0W13071) from
optional kit GVSOPT030 in modular battery cabinet 1.
b. Route the PE and DC cables through the right side and into the UPS
power cabling area.
c. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front View of Modular Battery Cabinet 1 for Adjacent UPS
30 990-91263-001

Connect the Power Cables for a UPS Rated over 50 kW Modular Battery Cabinet
Connect the Power Cables for a UPS Rated over 50
kW
NOTICE
RISK OF EQUIPMENT DAMAGE
For installations with a UPS rated over 50 kW, the DC cables from each modular
battery cabinet must be connected directly in the UPS.
Failure to follow these instructions can result in equipment damage.
1. For remote UPS:
a. Connect the PE cable and the DC cables (not provided) in each modular
battery cabinet
b. Route the PE and DC cables out through the conduit box and into the
UPS power cabling area.
c. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front View of the Modular Battery Cabinet for Remote UPS
990-91263-001 31

Modular Battery Cabinet Connect the Power Cables for a UPS Rated over 50 kW
2. For adjacent UPS for external batteries:
a. Connect the provided PE cable (0W49449) between the modular battery
cabinets as shown.
Front View of Two Modular Battery Cabinets
b. Connect the PE cable from optional kit GVSOPT030 in modular battery
cabinet 1 and route the PE cable through the right side and into the UPS
power cabling area.
c. Connect the DC cables from optional kit GVSOPT030 in each modular
battery cabinet and route the DC cables through the right side and into
the UPS power cabling area. The DC cables are routed through the
modular battery cabinets.
d. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front View of Modular Battery Cabinet 1
32 990-91263-001

Modular Battery Cabinet Connect the Signal Cables
Connect the Signal Cables
1. Assign an ID to each modular battery cabinet with the switch below the
battery breaker. Set the IDs according to the installation overview images in
Installation Procedure, page 17.
Front View of the Modular Battery Cabinet
34 990-91263-001

Connect the Signal Cables Modular Battery Cabinet
2. Connect the provided signal cables between all the modular battery cabinets:
a. Connect the provided signal cable 0W12680 from J8007 to J8008 on
board 640-7552 between the modular battery cabinets.
b. Connect the provided signal cable 0W76629 from J8011 to J8014 on
board 640-7552 between the modular battery cabinets.
c. Mount a termination plug (T) in the unused J8008 connector in the last
modular battery cabinet.
Modular Battery Cabinet 3 Modular Battery Cabinet 2 Modular Battery Cabinet 1
Front View of Two Modular Battery Cabinets
3. For installation with adjacent UPS with internal batteries:
a. Connect the signal cable 0W12680 to J8007 on board 640-7552 in
modular battery cabinet 1, route through the right side, and follow the
UPS installation manual to connect the signal cables in the UPS.
b. Connect the provided signal cable 0W76629 to J8011 on board 640-7552
in modular battery cabinet 1, route through the right side, and follow the
UPS installation manual to connect the signal cables in the UPS.
990-91263-001 35

Modular Battery Cabinet Connect the Signal Cables
4. For installation with adjacent UPS for external batteries:
a. Connect the signal cable 0W13070 from optional kit GVSOPT030 to
J8007 on board 640-7552 in modular battery cabinet 1, route through the
right side, and follow the UPS installation manual to connect the signal
cables in the UPS.
b. Connect the signal cable 0W13069 from optional kit GVSOPT030 to
J8011 on board 640-7552 in modular battery cabinet 1, route through the
right side, and follow the UPS installation manual to connect the signal
cables in the UPS.
Front View of Modular Battery Cabinet 1 for Adjacent UPS
36 990-91263-001

Connect the Signal Cables Modular Battery Cabinet
5. For remote installation:
a. Connect signal cables to J8007 on board 640-7552 in modular battery
cabinet 1, route through the rear, and follow the UPS installation manual
to connect the signal cables in the UPS.
NOTE: The provided signal cable 0W12680 is not long enough for a
remote UPS installation. A 5 meter signal cable (0J-0W4527) or 50
meter signal cable (0J-0W3758) can be ordered from Schneider
Electric. For other signal cable lengths, please contact Schneider
Electric. This signal cable is classified as Class 2/SELV.
b. Connect signal cables to J8011 on board 640-7552 in modular battery
cabinet 1, route through the rear, and follow the UPS installation manual
to connect the signal cables in the UPS.
NOTE: The provided signal cable 0W76629 is not long enough for a
remote UPS installation. Reuse the connectors from the provided
signal cable 0W76629 to make new signal cables in the correct
length. This signal cable is classified as non-Class 2/non-SELV.
Signal Cable for UPS with Internal Batteries
Signal Cable for UPS for External Batteries
Rear View of Modular Battery Cabinet 1 for Remote UPS
990-91263-001 37

Modular Battery Cabinet Add Translated Safety Labels to Your Product
Add Translated Safety Labels to Your Product
The safety labels on your product are in English and French. Sheets with
translated safety labels are provided with your product.
1. Find the sheets with translated safety labels provided with your product.
2. Check which 885-XXX numbers are on the sheet with translated safety
labels.
3. Locate the safety labels on your product that match the translated safety
labels on the sheet – look for the 885-XXX numbers.
4. Add the replacement safety label in your preferred language to your product
on top of the existing French safety label.
38 990-91263-001

Final Installation Modular Battery Cabinet
Final Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting battery
terminals.
• Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply
circuit).
Failure to follow these instructions will result in death or serious injury.
WARNING
RISK OF EQUIPMENT DAMAGE
Wait until the system is ready to be powered up before installing batteries in the
system. The time duration from battery installation until the UPS system is
powered up must not exceed 72 hours or 3 days.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
1. Lower the front and rear leveling feet on the modular battery cabinet with a
wrench until they connect with the floor. Use a bubble-leveler to check that
the modular battery cabinet is level.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not move the cabinet after the leveling feet have been lowered.
Failure to follow these instructions can result in equipment damage.
990-91263-001 39

Modular Battery Cabinet Final Installation
2. Only for seismic anchoring:
a. Install the seismic front anchoring bracket on the modular battery cabinet
with the provided M8 bolts.
b. Mount the seismic front anchoring bracket on the modular battery cabinet
to the floor. Use appropriate hardware for the floor type – the hole
diameter in the front anchoring bracket is ø18 mm.
3. Set the battery breaker BB to the open (OFF) position.
4. Push the battery modules into the slots. Fill the shelves from the bottom and
upwards.
5. Turn down the battery module handle and fasten the handle to the shelf with
the provided screw.
6. Reinstall the indicated plates and covers.
40 990-91263-001

Final Installation Modular Battery Cabinet
7. Connect the battery terminals to the front of the battery modules.
Front View of Battery Module
8. Reinstall the battery cover.
9. Reinstall the front panel.
a. Insert the two tabs in the bottom of the front panel in the modular battery
cabinet at a tilted angle.
b. Reconnect the front panel strap to the modular battery cabinet.
c. Close the front panel and lock with the two locking knobs.
990-91263-001 41



Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
*990-91263-001*
As standards, specifications, and design change from time to time,
please ask for confirmation of the information given in this publication.