APC SmartBunker SX 42U 5KVA UPS User Manual
Displayed below is the user manual for SmartBunker SX 42U 5KVA UPS by APC which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals
Installation and Customization
NetShelter™ SX Cabinet
990-2183H-001
Publication Date: November, 2015
Schneider Electric Legal Disclaimer
The information presented in this manu al is not warranted by Schneider Electric to be authoritative, error free,
or complete. This publication is not meant to be a substitute for a detailed operational and site specific
development plan. Therefore, Schneider Electric assumes no liability for damages, violations of codes,
improper installation, system failures, or any other problems that could arise based on the use of this
Publication.
The information contained in this Publication is provided as is and has been prepared solely for the purpose of
evaluating dat a ce nter design an d con struction. Th is Publication ha s b een comp iled in g ood faith by Schn eider
Electric. However, no representation is made or warranty given, either express or implied, as to the
completeness or accuracy of the information this Publication contains.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, OR ANY PARENT, AFFILIATE OR SUBSIDIAR Y COMPANY
OF SCHNEIDER ELECTRIC OR THEIR RESPECTIVE OFFICERS, DIRECTORS, OR EMPLOYEES BE
LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL
DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT,
REVENUE, DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING OUT,
OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT,
EVEN IF SCHNEIDER ELECTRIC HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH
DAMAGES. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH
RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME
WITHOUT NOTICE.
Copyright, intellectual, an d all other propriet ary rights in the content (includ ing but not limited to sof tware, audio,
video, text, and photogra phs) rests with Schneider Electric or it s licensors. All right s in the content not expressly
granted herein are re served. No rights of any kind are licensed or assigned or shall otherwise pass to persons
accessing this information.
This Publication shall not be for resale in whole or in part.
Table of Contents
NetShelter SX Cabinet - Installation and Customization Manual i
Introduction............................................................................................................1
Unpack the Cabinet ...............................................................................................2
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Please Recycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Component Identification.......................................................................................4
Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cabinet Installation ................................................................................................6
Move the Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Level the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Join the Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Secure the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Ground the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Install Side Panels, Roof and Doors ....................................................................10
Side Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Roof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Door Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Door Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Reverse the Front Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Equipment Installation..........................................................................................14
Adjust the Vertical Mounting Flanges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Position the Vertical Mounting Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Vertical Mounting Flange Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Install the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Cage nuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Cable Containment Bracket (24U Models Only) . . . . . . . . . . . . . . . . . . . . . . . . .17
Remove the Cable Cutout Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Cable Management..............................................................................................18
Accessory Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Specifications.......................................................................................................19
Limited Factory Warranty.....................................................................................20
Terms of Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Non-transfer ab le Wa rr an ty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Exclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Warranty Claims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
1 NetShelter SX Cabinet - Installa tion and Customization Manual
Introduction
The Schneider Electric NetShelter SX cabinets are high-quality cabinets for storage of industry-standard (EIA/
ECA-310), 19 in. (483 mm) rack-mount hardware, which includes servers and voice, data, networking,
internetworking, and power protection equipment.
This manual covers the general installation and the customization of the NetShelter SX Premium Datacenter
Cabinets. Refer to the NetShelter SX specification manu al for detailed measurements and ra tings of specific
models.
These cabinets are available on 600 mm (23.6 in.) an d 750 mm (29.5 in.) widths. Optional vertical mounting
flanges are available for the 750 mm (29.5 in.) cabinet to accommodate 23 in. EIA / ECA telecommunications
equipment.
NetShelter SX Cabinet - Installation and Customization Manual2
Unpack the Cabinet
Disclaimer
Schneider Electric is not responsible for damage sustained duri ng reshipment of this product.
Inspection
Inspect the packaging and contents for ship ping damage. Make sure that all part s are accounted for. Report
any damage immediately to the shipping agent. Report missing contents, damage, or other problems
immediately to Schneider Electric or your reseller.
Please Recycle
The shipping materials are recyclable. Save them for later use, or dispose of them appropriately.
Importa nt Safety Information
Read the instructions carefully to become familiar with the equipment before trying to install, operate, service or
maintain it. The following messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard
exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death
or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death
or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor
or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation
which, if not avoided, can result in equipment damage.
NOTICE
NOTICE addresses practices not related to physical injury including certain environmental
hazards, potential damage or loss of data.
3 NetShelter SX Cabinet - Installa tion and Customization Manual
Safety Instructions
This manual contains important instructions that must be followed during the installation and customization of
the cabinet.
Labels
Look for additional safety information af fixed to the cabinet. See “Labels” on page 6 for more information.
WARNING
TIP / HEAVY EQUIPMENT HAZARD
• This cabinet is easily tipped. Use extreme caution when unpacking or moving.
• At least two people are required to unpack and move the cabinet.
• Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom of the
cabinet for extra stability.
• Make sure the leveling feet are up and push the cabinet only from the front or rear when moving
the cabinet on its casters. Never push the cabinet from the sides.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NetShelter SX Cabinet - Installation and Customization Manual4
Component Identification
Cabinet
Adjustable vertical 0U accessory channel*Casters
Removable rear split doors Removable and reversible front door
Removable side panel with lock Key for doors and sid e panels
Cabinet frame Vertical mounting flanges
Adjustable leveling feet Roof
Hardware bag (see page 5)
* 1200 mm (47.24 in.) deep cabinets include four vertical 0U Accessory Channels.
ns0609d
5 NetShelter SX Cabinet - Installa tion and Customization Manual
Hardware
Tools provided
Plastic cup
washer (60) M6 x 16 Phillip s
slot screw (60) M5 x 12
screw (4) Cage nut (60) 7 mm (0.28 in.)
hole plug (4 )
Torx® T30 / #2 Phillips tool Cage nut tool (1)
NetShelter SX Cabinet - Installation and Customization Manual6
Cabinet Installation
Move the Cabinet
Eye bolts. The cabinet can be lifted using eye bolts with up to 567 kg (1,250 lb) of
equipment installed. Use M10 eye bolts with a shoulder rated for 181 kg (400 lb).
NOTE: Use appropriate lifting hardware to assure straight-line pull on lifting eye bolts.
WARNING
TIP HAZARD
• This cabinet is easily tipped. Use extreme caution when unpacking or moving.
• At least two people are required to unpack and move the cabinet.
• Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom of the
cabinet for extra stability.
• Make sure the leveling feet are up and push the cabinet only from the front or rear when moving
the cabinet on its casters. Never push the cabinet from the sides.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Labels. The following labels can be found on the cabinet, and serve to
communicate the following information:
Label : Generic Tip Hazard
Label : Extend Slide-Mounted Hardware One Piece at a Time
Casters. The cabinet can be mo ve d on its casters with up to
1021 kg (2,250 lb) of eq u ipm e nt ins talled. Once in pla ce , lowe r the
leveling feet. With the leveling feet lowered, the sta tic cabinet can be
loaded to 1364 kg (3,000 lb).
NOTE: Some labels on cabinet indicate caster related information.
See label to right.
Casters
2250 lbs Max
(1020 kg)
Leveling Feet:
3000 lbs Max
(1361 kg)
U.S. Patent No.
初⦌₢Ⓒ⚆
7,293,666
ns2378a
7 NetShelter SX Cabinet - Installa tion and Customization Manual
Level the Equipment
The leveling feet at the corners of the equipment provide a stable base if the floor is uneven , but they cannot
compensate fo r a badly sloped surface.
Ensure the cabinet is in its intended location. Remove the front and rear doors.
See “Door Removal” on page 11 for instruction.
NOTE: Before removing the front door, unplug the ground wires and any other wire connections that may interfere
with the removal of the doors.
Insert a Phillips head screwdriver into the screw above the
leveling foot. T urn the screw clockwise to extend the leveling
foot until it makes firm contact with the floor. NOTE: This
method works best with an empty, or near empty, cabinet.
Adjust each foot and, using a level, adjust the feet until the
cabinet is level and plum b.
Do not install the doors until after the cabinet is joined to
others in the row
Join the Cabinets
Join cabinets with the provided brackets to provide alignment and added stability. Cabinets may be joined with or
without the side panels installed.
If installed, remove the front and rear doors. See
“Door Removal” on page 11 for instructions.
Choose between 24 in. cente rs or 600 mm
centers (see the detail view below).
Align the cabinet s and locate the joining brackets .
There are two brackets on the front and two
brackets on the back of each cabinet.
Cabinets are joined using a M5 x 12 countersunk
screw, provided in the hardware bag. Using the
Phillips head end of the provided tool or a similar
tool, insert the screw into the designated hole and
tighten.
Install the doo rs. See “Door Removal” on p age 1 1
for instructions.
NOTICE
• A13 mm open ended wrench can also be used to lower the
leveling feet if the cabin et is loaded with equipment.
• Door removal is not required if using the 13 mm open-ended
wrench.
WARNING
TIP HAZARD
Joining cabinets provides limited stability to the cabinets. Secure the cabinet to the floor before
installing equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
ns1632b
ns1594b
24 in.
600 mm
X4
NetShelter SX Cabinet - Installation and Customization Manual8
Secure the Cabinet
To secure the cabinet to the floor, use fastener locations on the outside or inside of the cabinet, and choose from
the accessories shown below.
WARNING
TIP HAZARD
Secure the cabinet to the floor before installing equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Accessory Part Number Description
Pallet / Bolt-down
Brackets provided with the
cabinet Attaches to the cabinet,
internally or externally, to
secure the rack to the floor.
This provides additional
stability without blocking cable
access. With th e ap pr o pr iate
mounting hardware, meets IBC/
CBC seismic requirements.
Bolt-down kit AR7701
(Optional) Attaches to cabinet and floor
internally or externally to
provide additional stability
without blocking cable access.
NetShelter SX
Stabilizer Plate AR7700
(Optional) Attaches externally to the
cabinet and floor to provide
additional stability.
ns1780b
9 NetShelter SX Cabinet - Installa tion and Customization Manual
Ground the Cabinet
Each cabinet should be bonded directly to a common ground using one of the designated grounding locations (two
M6 threaded inser ts) at the top or bottom of the cabinet.
• Use a Common Bonding Network Jumper kit (for example, Listed [KDER] Panduit® RGCBNJ660PY or equivalent).
• Use paint-piercing washers between the ground terminal and the cabinet frame, or remove the paint on the fra me
under the grou nd ter m ina ls, pe r NEC NF PA 70 Article 250.12.
• Torque the screws to 6.9 N•m (60 lb-in).
Bonding Locations on the Cabinet
DANGER
HAZARD OF ELECTRIC SHOCK
Connection of the cabinet to building Common Bon ding Network (CBN) is required.
Failure to follow these instructions will result in death or serious injury.
ns1617a
NetShelter SX Cabinet - Installation and Customization Manual10
Install Side Panels, Roof and Doors
Side Panels
Roof
X2
ns1724b
na2591a
11 NetShelter SX Cabinet - Installa tion and Customization Manual
Door Removal
1. Unlock the cabinet front door handle and open the door.
2. Disconnect the grou nd wire and any other wire connections
that may interfere with the removal of the doors.
3. The hinges come apart by lifting upward and outward. Slowly
lift and pul l the door from the cabinet until the hinge pins on the
door are free of the hinges on the ca binet frame.
Door Installation
1. The doors self- align on hi nge pins when properly
installed. With the door at a 90 degree angle to
the front of the cabinet, position the door over
the hinge pins .
2. Slowly lower the door into the cabinet frame
ensuring that the door hinges correctly align to
the cabinet frame hinges.
3. Connect the ground wire and any othe r wire
connections.
ns2283a
ns1604b
ns2284a
ns2285a
NetShelter SX Cabinet - Installation and Customization Manual12
Reverse the Front Door
NOTE: The front door can be reversed so that the door opens in the other direction. This procedure assumes that
initially, when facing the cabinet, the hinges are on the left and the door is opening from right.
1. Remove the handle by removing the screw-plate.
Pull the handle from the door.
2. Disconnect the ground wire, and any other wire
connections . R em o ve th e do or fro m th e fra m e.
See “Door Removal” on page 11 for more
information.
3. Locate the upp er hinge on the cabinet frame.
Remove the two screws holding the hinge in
place. Install the hinge ont o th e ot he r side of th e
cabinet frame. Repeat this step for the lower
hinge.
4. Rotate the door . Remove the hinges from
the door, and install them to the alternate hole
location . The hinges on door should now align
with the hinges on the cabinet.
5. Install the door to the hinges now on the reverse side
of the cabinet frame. See “Door Removal” on
page 11 for instruction. Connect the ground wire and
any other wire con nections previously disc on n ect ed .
ns1752b
ns1758b
ns1824a
ns2289a
13 NetShelter SX Cabinet - Installa tion and Customization Manual
6. Locate the lock handle.
Remove the cam screw, cam washer,
and cam.
Rotate the cam washer 90 degrees,
and the latch 180 degrees.
Install the handle on the door.
ns1779b
ns1766b
NetShelter SX Cabinet - Installation and Customization Manual14
Equipment Installation
NOTE: NetShelter SX cabinets are intended for use with Listed equ ipment. If you insta ll un-Listed equipment, you
should evaluate the safety of your configuration.
Adjust the Vertical Mounting Flanges
Vertical mounting flanges come factory-installed at 737 mm (29 in.), the proper
location for use with rack-mountable equipment.
The mounting flanges are adjustable towards the fro nt or the r ear o f the cab ine t to
accommodate different r ails or equipment with other depths.
A common application for the 750 mm (29.5 in.) wide cabinet is to move the
flanges to a depth of 476 mm (18.75 in.) to accommodate networking and
telecommunications equipm en t.
Position the Vertical Mounting Flanges
WW
D
D
a
b
c
ns2293a
Accessory Channel
Top View
•Configuration 1: The Accessory Channel is installed. The Vertical
Mounting Flanges can be installed a minimum distance of (a) and
can extend as far as (b).
•Configuration 2: The Accessory Channel is removed. The Vertical
Mounting Flanges can extend as far as (c).
Cabinet
Width (W) Cabinet
Depth (D) a b c
600 mm 1070 mm 190 mm
(7.5 in.) 787 mm
(30.75 in.) 921 mm
(36.25 in.)
750 mm 1070 mm 285 mm
(11.25 in.) 787 mm
(30.75 in.) 921 mm
(36.25 in.)
600 mm 1200 mm 190 mm
(7.5 in.) 787 mm
(30.75 in.) 1047 mm
(41.25 in.)
750 mm 1200 mm 285 mm
(11.25 in.) 787 mm
(30.75 in.) 1047 mm
(41.25 in.)
ns1621b
15 NetShelter SX Cabinet - Installa tion and Customization Manual
Vertical Mounting Flange Adjustment
1. Use the provided Torx T30 tool to
loosen the top, mid dle, and bottom Torx
screws holding the vertical mounting
flange in place. The bracket s, all held in
place by the Torx screws, will now be
loose. Move all three brackets to the
designated unlocked position .
NOTE: The 600 mm and 750 mm wide cabinets have dif ferent brackets. See the illustrations below.
WARNING
FALLING EQUIPMENT
Remove all equipment installed on the vertical mo unting flanges before performing any adjustments.
Failure to follow these instructions can result in serious injury or equipment damage.
600 mm wide cabinet 750 mm wide cabinet
ns1622b
ns07
15b
na0715a
ns0977a
NetShelter SX Cabinet - Installation and Customization Manual16
2. Move the mounting flange to the desired location. Vertical
mounting flanges adjust in 6 mm (1/4 in.) increments.
3. To align the vertical mounting flange, note the symbol
(for example, a diamond) visible through one of the three
holes. Only one symbol will be visible. In the factory
standard position, a circle symbol is visible.
Make sure the same symbol is visible through the
corresponding hole at both the top and the bottom of the
flange.
4. When the vertical mounting flange is in the desired location
at the top, middle, and bottom, raise the flat bracket to the
lock position. The teeth in the bracket will engage fully with
the teeth in the side brace . Tighten the Torx screws .
NOTE: On the 750 mm cabinet there are circle symbols 476 mm (18.75 in.) behind the front mounting flange. These
circle symbols designate rear vertical mounting flange positions required for installation of particular networking and
telecommunications equipment.
ns1623a
ns0718a
ns2292a
17 NetShelter SX Cabinet - Installa tion and Customization Manual
Install the Equipment
To install rack-mount equipment in the cabinet:
Review the equipment manufacturer’s installation instructions.
Locate the top and bottom U space on the ver tical mounting rails. Every third hole on
the mounting rails is numbered to indicate the middle of a U space.
Install the cage nuts on the interior of the vertical mounting rail; then install the
equipment.
Cage nuts
Installation: Schneider Electric offer s a cage nut hardware kit (AR8100) for use with
square holes.
NOTE: Install cage nuts horizontally, with the ears engaging the sides of the
square hole. Do NOT install cage nuts vertically with the ears engaging the
top and bottom of the square hole.
Insert the cage nut into the square hole by hooking one ear of the cage nut
assembly through the far side of the hole.
NOTE: Install the cage nuts on the interior of the vertical mounting flange.
Place the cage nut tool on the other side of the cage nut and pull to snap it
into position.
Removal: Remove any attached screw.
Grasp the cage nut and squeeze the sides to release it from the square hole.
Cable Containment Bracket
(24U Models Only)
ns1725b
The rear door cable containment bracket is installed
within the cabinet under the left hand door. The
bracket has 4 lobes for attaching cables with hook-
and-loop fastener s (provided) and cable ties (not
provided).
WARNING
TIP HAZARD
• This cabinet is easily tipped. Make sure you have secured the cabinet to the floor before installing
equipment.
• Install the heaviest equipment first and toward the bottom of the cabinet to prevent the cabinet
from becoming top-heavy.
• Do not extend equipment on sliding rails until you have installed 158 kg (350 lb) of equipment into
the bottom of the cabinet for stability or until you have installed the stabilizer plate or bolt-down
brackets. Do not extend more than one piec e of equipment on sliding rails at a time.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1U
7
6
5
ns0014a
ns1768a
gen0188a
NetShelter SX Cabinet - Installation and Customization Manual18
Remove the Cable Cutout Covers
For NetShelter SX 750 mm (29.5 in.) wide
cabinets that include equipment requiring
side airflow, on the side of the cabinet
nearest the air intake for the equipment,
remove the cable cutout covers from the
front vertical mounting flange. Reinstall the
covers in the cable cutout holes on the rear
vertical mounting flange on the same side of
the cabinet.
Cable Management
The NetShelter SX cabinet has multiple cable access openings, including on the roof, sides, and bottom.
Route, secure, and organize cables using these openings.
In addition, two rear vertical 0U cab le organizer s, or accessory channe ls, are includ ed with the cabine t. Furth er cable
management accessories ar e available. Please go to www.schneider-electric.com, or contact a Schneider Electric
reseller for more information.
Accessory Channel
ns1923a
The accessory channels provide toolless mounting capabilities for Rack Power
Distribution Units and cable mana ge m en t ac ce sso rie s.
There are four Accessory Ch annels included with the 1200 mm (47.24 in.) deep
cabinet. There are two included with all other cabinets. The factory-default
position for the accessory channels is in the rear of the cabinet, as shown in the
graphic to the right.
The channels also provide tie-off locations for cables, as well as other specific
holes for managing cables with many NetShelter brackets, fastener s, and
toolless mounting equipment.
Similar to the mounting flanges, the accessory channel can be moved
anywhere along the side br aces. See “Adjust the Vertical Mounting Flang es” on
page 14 for more instruction.
NOTE: If needed, the accessory channels can be removed. Additional vertical
0U accessory channels are available for order.
ns1071b
19 NetShelter SX Cabinet - Installa tion and Customization Manual
Specifications
General specifications for SX cabinets:
(For detailed dimensions and weights refer to the NetShelter SX Specification manuals.)
* 54U models have not been evaluated by UL.
NOTE: Additional packaging is required if the cabinet is being shipped with equipment installed.
See the NetShelter SX product family page at www.schneider-electric.com for details on cabinets with shock
packaging.
Height Width Depth
Umm in. mm in. mm in.
24U 1199 47.2 600 23.6 1070 42.1
42U 1991 78.4 700* 27.6 1200 47.2
45U 2124 83.6 750 29.5
48U 2258 88.9 * 700 mm models in Japan only
50U 2347 92.4
52U 2436 95.9
54U* 2525 99.4
Door Perforation pattern 69% open area
Clearance for wiring between
front door and vertical rail 60.96 mm (2.4 0 in.)
Weight rating: static load11363.6 kg (3,000 lb)
Weight rating: rolling21022.7 kg (2,250 lb)
1 Lower the leveling feet if the static weight is over 1022.7 kg (2,250 lb).
2 Rolling rating valid only for rolling the cabinet into position.
NetShelter SX Cabinet - Installation and Customization Manual20
Limited Factory Warranty
The limited warranty provided by Schneider Electric in this Statement of Limited Factory Warranty applies only
to Products you purchase for your commercial or industrial use in the ordinary course of your business.
Terms of Warranty
Schneider Electric warrants its products to be free from de fects in materials and workmanship for a period of
five years (two years in Japan) from the date of purchase. Its obligation under this warranty is limited to
repairing or replacing, at its sole discretion, any such defective products. This warranty does not apply to
equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified
in any way. Repair or replacement of a defective product or part thereof does not extend the original warranty
period. Any parts furnished under this warranty may be new or factory-remanufactured.
Non-transferable Warranty
This warranty applies only to the original purchaser who must have properly registere d the product. Product
may be registered at www.schneider-electric.com.
Exclusions
Schneider Electric shall not be liable under the warranty if its testing and examination disclose that the alleged
defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence ,
improper installation or testing. Further Schneider Electric shall not be liable under th e warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection, inappropriate
on-site operation conditions, corrosive atmosphere, repair, installation, start-up by non-Schneider Electric
designated personnel, a chang e in location or op erating us e, e xposure to the elements, Acts of God, fire, theft,
or installation contrary to Schneider Ele ctric reco mmendations o r specifications or in any event if the Schneid er
Electric serial number has been altered, de faced, or removed, or any other cause beyond the range of the
intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF
PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION
HEREWITH. SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC EXPRESS
WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR
LIABILITY WILL ARISE OUT OF, SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER
ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND
REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE
WARRANTIES SET FORTH ABOVE CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND
PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SCHNEIDER
ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD
PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS, AFFILIATES OR
EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE
DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER
SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF F AULT, NEGLIGENCE OR STRICT
LIABILITY OR WHETHER SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBLY
OF SUCH DAMAGES. SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS, SUCH
AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF
SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR
OTHERWISE. NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS AUTHORIZED TO
ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT
ALL, ONLY IN WRITING SIGNED BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Warranty Claims
Customers with warranty claims issues may access the Schneider Electric worldwide customer support
network by visiting www.schneider-electric.com. Select your country from the country selection pull-down
menu. Open the Support tab at the top of the web page to obtain contact information for customer support in
your region.
Worldwide Customer Support
Customer support for this or any other product is available at www.schneider-electric.com. For information o n
how to obt ain local customer support, contact the r epresentative or other distributors fr om whom you purchased
your product.
11/2015
990-2183H-001
© 2015 Schneider Electric. All Rights Reserved. Schneider Electric and NetShelter are trademarks owned by
Schneider Electric Industries S.A.S. or its affiliated companies. All other trademarks are property of their
respective owners.