APC SMV1500AI-MS User Manual
Displayed below is the user manual for SMV1500AI-MS by APC which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals
DANGER
WARNING
CAUTION
NOTICE
Important Safety Messages
SAVE THESE INSTRUCTIONS - This section contains important instructions that should be followed
during installation and maintenance of the UPS and batteries.
Read these instructions carefully and look at the equipment to become familiar with the device before
trying to install, operate, service or maintain it. The following special messages may appear throughout this
bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies
or simplifies a procedure.
User Manual Easy UPS
SMV Series 750, 1000, 1500, 2000, 3000 VA
The addition of this symbol to either a “Danger” or “Warning” safety label indicates that an
electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE is used to address practices not related to physical injury.
2 Easy UPS SMV Series 750, 1000, 1500, 2000, 3000VA
CAUTION
Product Handling Guidelines
Adhere to all national and local electrical codes.
This UPS is intended for indoor use only. To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area, free of conductive contaminants.
Mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily
accessible.
UPS must be connected to an earthed mains socket outlet.
HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
Failure to follow these instructions can result in injury
Servicing of user replaceable batteries should be performed or supervised by personnel
knowledgeable about batteries and required precautions. In this case batteries are not user
replaceable.
When replacing battery the UPS must be OFF, and its AC inlet unplugged.
CAUTION Do not dispose of batteries in a fire. The batteries may explode.
CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
according to the instructions.
Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin
and eyes.
CAUTION A battery can present a risk of electrical shock and high short circuit current. The
following precautions should be observed when working on batteries.
a. Remove watches, rings or other metal objects.
b. Use tools with insulated handles.
c. Wear rubber gloves and boots.
d. Do not lay tools or metal parts on top of batteries.
e. Disconnect the charging source prior to connecting or disconnecting battery terminals.
f. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance.
CAUTION Risk of electric shock, do not remove the chassis cover. Servicing should be performed
by Qualified Engineer.
<18 kg
<40 lb
18-32 kg
40-70 lb
32-55 kg
70-120 lb
>55 kg
>120 lb
Easy UPS SMV Series 750, 1000, 1500, 2000, 3000VA 3
CAUTION The UPS contains internal batteries and may present a shock hazard even when
disconnected from AC power.
CAUTION Risk of electric shock, Battery Circuit is not isolated from AC input, hazardous voltage
may exist between battery terminals and ground. Test before touching.
CAUTION This UPS is designed to satisfy all of requirement of PCs only.
Radio Frequency Warning
This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
Inventory
Optional
USB cable
Software, User documentation
CD
a) IEC C14 plug
to C13 plug
b) SCHUKO plug
to IEC C13 plug
c) SCHUKO plug
to IEC C19 plug
d) NEMA 5-15P plug
to IEC C13 plug
e) NEMA 5-15P plug
to IEC C19 plug
Model
Cable
SMV750I
SMV1000I
SMV1500AI
SMV2000AI
a x1
b x1
SMV3000AI
a x1
c x1
SMV750I-GR
SMV1000I-GR
SMV1500AI-GR
SMV2000AI-GR
b x2
SMV3000AI-GR
b x1
c x1
SMV750I-MS
SMV1000I-MS
SMV1500AI-MS
SMV2000AI-MS
b x1
d x1
SMV3000AI-MS
b x1
e x1
4 Easy UPS SMV Series 750, 1000, 1500, 2000, 3000VA
Features
●
A
ON/OFF button
●
F
AC Inlet
●
B
RS-232
●
G
Fuse
●
C
USB port
●
H
Battery backup outlets with surge protection
●
D
Fan /ventilation hole
●
I
Output breaker (only for SMV3000AI)
●
E
Battery connector
Model
Output Type
and Quantity
SMV750I
SMV1000I
SMV1500AI
x6
SMV750I-GR
SMV1000I-GR
SMV1500AI-GR
x4
SMV750I-MS
SMV1000I-MS
SMV1500AI-MS
x4
Model
Output Type
and Quantity
SMV2000AI
x6
SMV2000AI-GR
x4
SMV2000AI-MS
x6
Model
Output Type
and Quantity
SMV3000AI
x6
SMV3000AI-GR
x4
SMV3000AI-MS
x6
A
A
Easy UPS SMV Series 750, 1000, 1500, 2000, 3000VA 5
NOTICE
Before installing the UPS, ensure the input breaker on the UPS upstream is Type C rated at 16A.
Front Panel Display
LCD
Status
1. On Line mode
2. Battery mode
3. Automatic Voltage Regulation
4. Battery capacity
5. Load capacity
6. UPS status
7. Power ON/OFF button
Place and Power On
1. Installation:
UPS MUST be installed indoor with controlled environment free of excessive dust, corrosive air
or conductive dust.
Do NOT install in outdoor.
Keep out of direct sun light, water and heat sources
Place the unit on the stable floor.
2. Connect the battery by pulling the battery handle up, and then pushing it into the unit.
The battery connector is located on the rear panel.
-Connect prior to operation.
- Disconnect prior to transportation. Turn OFF the UPS
and remove input power cable before disconnecting the
battery connector.
3. Connect equipment to the UPS. Avoid using extension cords.
Do NOT connect printers, heaters, or copiers to the UPS.
During a power outage or other AC problems, the Battery Backup outlets receive power for a
limited time from the Easy UPS.
4. Plug the Easy UPS power cord directly into a wall outlet, not into a surge protector or power strip.
5. Press the ON/OFF button to turn on the unit.
The Easy UPS should charge the battery for at least 8 hours to ensure sufficient runtime.
Press On / OFF button in 1~3 seconds. The buzzer sound confirms that the Easy UPS is on and
provide power to outlets.
6. Cold start the UPS
Use cold start feature to supply power to connected equipment from
the UPS batteries when the UPS is off and there is no power utility.
7. Connect and install management software
Easy UPS is provided with management software for unattended
operating system shutdown, UPS monitoring, and UPS settings.
Refer to www.apc.com for more information.
Battery connect step
6 Easy UPS SMV Series 750, 1000, 1500, 2000, 3000VA
Specifications
Model
SMV750I
SMV1000I
SMV1500AI
SMV2000AI
SMV3000AI
Input
Voltage
220/230/240VAC
Voltage range
165~290Vac±5Vac
165~295Vac±8Vac
Fuse
8A
8A
12A
20A
25A
Frequency Range
45-65 Hz (auto sensing) ±1Hz
Output
UPS Capacity (total)
750VA
525W
1000VA
700W
1500VA
1050W
2000VA
1400W
3000VA
2100W
Rated Voltage
230VAC
Transfer time
Typical 2-6 ms, 12ms max.
Waveform
Pure Sine Wave
Battery
Type
(maintenance-free)
12V/7Ah x2
lead acid
12V/7Ah x2
lead acid
12V/10Ah x2
lead acid
12V/7Ah x4
lead acid
12V/9Ah x4
lead acid
Charging time
4-6 hours recover to 90% capacity
Physical
Dimension
(D x W x H, mm)
410 x 160 x 220
455 x 180 x 240
Net Weight (kg)
13.6
17.8
23.5
25.2
Packaging
Dimension
(D x W x H, mm)
508 x 272 x 339
604 x 319 x 414
Gross Weight (kg)
16.6
20.75
26.9
28.9
Environment
Operating
temperature &
Humidity
0-90 % RH @ 0-40°C
(non-condensing)
0-95 % RH @ 0-40°C
(non-condensing)
Noise level
Less than 45dB
Enclosure
type
IP Rating
IP20
Audible Indicators and Status Icons
If the Easy UPS…
Possible cause...
Beeps every 2 seconds.
Easy UPS is running on battery. You
should consider saving any work in
progress.
Continuous Beeping.
Low battery condition and battery run-time
is very low. Promptly save any work in
progress, exit all open applications, and
shut down the operating system.
Continuous tone with illuminated.
Battery Backup outputs are overloaded.
Continuous tone with illuminated.
a. Press ON/OFF button for 1-3 seconds to mute the alarm.
b. Continuous tone will persist until battery LOW.
(<11Vdc each BATT)
: Fan fault detected
: Inverter short
: Inverter over voltage
Beeps every 4 seconds with illuminated.
The battery is near the end of useful life or
damaged.
Easy UPS SMV Series 750, 1000, 1500, 2000, 3000VA 7
Troubleshooting
Problem and Possible Cause
Solution
The Easy UPS will not turn on
The Easy UPS has not been turned on.
Press the ON/OFF button.
The Easy UPS is not connected to AC power, there is
no AC power available at the wall outlet, or the AC
power is experiencing a brownout or over voltage
condition.
Make sure the power cord is securely connected to
the wall outlet, and that there is AC power
available at the wall outlet. Where applicable,
check that the wall outlet is switched on or input
fuse works properly.
The battery is disconnected.
Refer to the Place and Power On page 5.
Connected equipment loses power
An Easy UPS overload condition has occurred.
Remove all nonessential equipment connected to
the outlets. One at a time reconnect equipment to
the Easy UPS.
The Easy UPS battery is completely discharged.
Connect the Easy UPS to AC power and recharge
for 10 hours.
The Easy UPS may require service.
Contact Schneider Electric Technical Support.
The Easy UPS is operating on battery power, while connected to AC power
The plug has partially pulled out of the wall outlet,
the wall outlet is no longer receiving AC power, or
the fuse has been blown.
Ensure that the plug is fully inserted into the wall
outlet. Ensure that the wall outlet is receiving AC
power by checking it with another device. Or
replace the fuse.
The message illuminates on the display interface
: Fan fault detected
Turn the Easy UPS off. Clean dust or foreign
materials clogging cooling fan and turn the Easy
UPS on. If the error message persists, contact
Schneider Electric Technical Support.
: Inverter short detected
Turn the Easy UPS off. Disconnect non-essential
equipment from the outlets and turn the Easy UPS
on. If the error message persists, contact Schneider
Electric Technical Support.
: Inverter over voltage detected
Contact Schneider Electric Technical Support.
The Easy UPS beeping every 4 seconds
The battery is disconnected.
Make sure the battery connector in rear panel is
connected.
The battery is near the end of useful life or damaged.
Contact Schneider Electric Technical Support if the
Easy UPS remain beeping with battery connector
securely connected.
The Easy UPS has an inadequate battery runtime
The battery is not fully charged.
The battery is near the end of useful life and should
be replaced.
Leave the Easy UPS connected to AC power for 10
hours while the battery charges to full capacity.
As a battery ages, the runtime capability decreases.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the APC by
Schneider Electric website, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers
are located on the rear panel of the unit.
b. Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If
this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric
website for country specific instructions.
3. Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam
beads for packaging. Damage sustained in transit is not covered under warranty.
4. Always DISCONNECT THE UPS BATTERIES before shipping. The United States Department
of Transportation (DOT), and the International Air Transport Association (IATA) regulations
require that UPS batteries be disconnected before shipping. The internal batteries may remain in
the UPS.
5. Write the RMA# provided by Customer Support on the outside of the package.
6. Return the unit by insured, pre-paid carrier to the address provided by Customer Support
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure is to replace
the original unit with a factory reconditioned unit. Customers who must have the original unit back due
to the assignment of asset tags and set depreciation schedules must declare such a need at first contact
with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective
unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card
number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs
to ship the replacement unit to the customer.
APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric website, www.apc.com.
© 2019 APC by Schneider Electric. APC, the APC logo are owned by Schneider
Electric Industries S.A.S., or their affiliated companies. All other trademarks are
property of their respective owners.
EN 990-91224A
04/2019