Table of Contents
- Important Safety Messages
- Product Handling Guidelines
- Safety and General Information
- Deenergizing safety
- Electrical safety
- Battery safety
- Hardwire safety
- General information
- FCC Class A Radio Frequency Warning
- Specifications
- Environmental
- Physical
- Battery
- *Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery modules.
- Electrical
- Front panel features
- Rear panel features
- Key to identify rear panel features
- Wiring Specifications
- Connect Equipment
- Turn the UPS On/Off
- UPS Display Interface
- UPS Display Interface operation
- LCD display interface angle adjustment
- Menu overview
- UPS Settings
- Startup configuration
- General settings
- Controllable Outlet Groups provide battery backup power to connected equipment.
- Overview
- Connect controllable outlet groups
- Overview
- Normally open contacts
- Normally closed contacts
- Install a Ferrite Bead
- Introduction
- Features
- Related Documents
- IP Address Configuration
- Definitions
- Features
- Maintenance
- End of useful life
- Replace the RBCs in a UPS
- Recommended actions after installing new RBCs
- XLBP installation and replacement
- SUO UM 990-4506 MenuTree EN.pdf
APC SRT10KXLTUS User Manual
Displayed below is the user manual for SRT10KXLTUS by APC which is a product in the Uninterruptible Power Supplies (UPSs) category. This manual has pages.
Related Manuals
Operation Manual
Smart-UPS™ On-Line SRT
Uninterruptible Power Supply
SRT8KXLI
SRT8KRMXLI
SRT8KXLT
SRT8KRMXLT
SRT8KXLT-IEC
SRT8KRMXLT-IEC
SRT10KXLI
SRT10KRMXLI
SRT10KXLT
SRT10KRMXLT
SRT10KXLT-IEC
SRT10KRMXLT-IEC
208/220/230/240 Vac
Tower/Rack-Mount 6U
suo0797a
1Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
General Information
Important Safety Messages
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during
installation and maintenance of the Smart-UPS and batteries.
Read these instructions carefully and look at the equipment to become familiar with the device before trying to
install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol either to a “Danger” or “Warning” safety label indicates that an electrical
hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
Product Handling Guidelines
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
<18 kg
<40 lb
18-32 kg
40-70 lb
32-55 kg
70-120 lb
>55 kg
>120 lb
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U2
Safety and General Information
• Adhere to all national and local electrical codes.
• All wiring must be performed by a qualified electrician.
• Changes and modifications to this unit not expressly approved by APC could void the warranty.
• This unit is intended for indoor use only.
• Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or
humidity.
• Be sure the air vents on this unit are not blocked. Allow adequate space for proper ventilation.
• For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not
use surge protectors or extension cords.
• The UPS will recognize as many as 10 external battery packs connected to the UPS.
Note: For each XLBP that is added, increased recharge time will be required.
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• The batteries are heavy. Remove the batteries before installing the UPS and external battery packs (XLBPs),
in a rack.
• Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the
XLBPs.
• Always install peripheral equipment above the UPS in rack-mount configurations.
• Additional safety information can be found in the Safety Guide supplied with this unit.
Deenergizing safety
• The UPS contains internal batteries and may present a shock hazard even when disconnected from AC and
DC power.
• The AC and DC output connectors may be energized by remote or automatic control at any time.
• Before installing or servicing the equipment check that the:
– Mains circuit breaker is in the OFF position
– Internal UPS batteries are removed
– XLBP battery modules are disconnected
Electrical safety
• For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a
qualified electrician.
• 230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe,
output cords attached to the UPS must not exceed 10 meters in length.
• The protective earth conductor for the UPS carries the leakage current from the load devices (computer
equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the
UPS. The conductor must have the same size and insulation material as the grounded and ungrounded
branch circuit supply conductors. The conductor will typically be green and with or without a yellow stripe.
• The UPS input ground conductor must be properly bonded to protective earth at the service panel.
• If the UPS input power is supplied by a separately derived system, the ground conductor must be properly
bonded at the supply transformer or motor generator set.
3Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Battery safety
• It is not necessary to ground the battery system. The user has the option of referencing the battery system to
chassis ground at either a positive or negative battery terminal.
• Replace batteries with the same number and type of batteries as originally installed in the equipment.
• The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient
temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life.
• Replace batteries immediately when the unit indicates battery replacement is necessary.
• Schneider Electric uses Maintenance-Free sealed Lead Acid batteries. Under normal use and handling, there
is no contact with the internal components of the battery. Over charging, over heating or other misuse of
batteries can result in a discharge of battery electrolyte. Released electrolyte is toxic and may be harmful to
the skin and eyes.
• CAUTION: Before installing or replacing the batteries, remove jewelry such as wristwatches and rings.
High short circuit current through conductive materials could cause severe burns.
• CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
• CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes and may be
toxic.
Hardwire safety
• Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out
before installing cables or making connections, whether in the junction box or to the UPS.
• Wiring by a qualified electrician is required.
• Check national and local codes before wiring.
• Strain relief is required for all hardwiring (supplied with select products).
Snap in type strain reliefs are recommended.
• All openings that allow access to UPS hardwire terminals must be covered. Failure to do so may result in
personal injury or equipment damage.
• Select wire size and connectors according to national and local codes.
General information
• The UPS will recognize as many as 10 external battery packs connected to the UPS.
Note: For each XLBP added, increased recharge time will be required.
• The model and serial numbers are located on a small, rear panel label. For some models, an additional label
is located on the chassis under the front bezel.
• Always recycle used batteries.
• Recycle the package materials or save them for reuse.
FCC Class A Radio Frequency Warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U4
Product Description
The APC by Schneider Electric Smart-UPS™ On-Line SRT is a high performance uninterruptible power supply
(UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts,
sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power
for connected equipment until utility power returns to acceptable levels or the batteries are completely discharged.
This user manual is available on the enclosed Documentation CD and on the APC by Schneider Electric web site,
www.apc.com.
Product Overview
Specifications
For additional specifications refer to the APC by Schneider Electric Web site, www.apc.com.
Environmental
Physical
Temperature Operating 0° to 40° C (32° to 104° F)
Storage -15° to 45° C (5° to 113° F)
Maximum Elevation Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (0 - 50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing
Protection Class IP 20 rating
Note: Charge the battery modules every six months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor quality mains power, and
frequent short duration discharges will shorten battery life.
The UPS is heavy. Follow all lifting guidelines.
Unit weight without packaging 111.82 kg (246 lb)
Unit weight with packaging Rack-Mount models: 130 kg (286 lb)
Tower models: 126.82 kg (279 lb)
Unit dimensions without packaging
Height x Width x Depth
263 mm x 432 mm x 715 mm
10.35 in x 17 in x 28.15 in
Unit dimensions with packaging
Height x Width x Depth
461 mm x 600 mm x 1000 mm
18.2 in x 23.62 in x 39.4 in
The model and serial numbers are on a small label located on the rear panel.
5Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Battery
*Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery modules.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
• Replace the battery at least every 5 years.
• Replace the battery immediately when the UPS indicates battery replacement is necessary.
• Replace battery at the end of its service life.
• Replace batteries with the same number and type of batteries as originally installed in the equipment.
• Replace the battery immediately when the UPS indicates a battery overtemperature condition, or when
there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the
batteries. Do not operate the UPS until the batteries have been replaced.
• *Replace all battery modules (including the modules in External Battery Packs) which are older than one
year, when installing additional battery packs or replacing the battery module(s).
Failure to follow these instructions could result in equipment damage and minor or moderate injury.
Battery type Sealed, maintenance-free, Valve Regulated
Lead-Acid battery
Replacement battery module
This UPS has replaceable battery modules.
Refer to the appropriate replacement battery user manual for
installation instructions.
Contact your dealer or go the APC by Schneider Electric Web site,
www.apc.com for information on replacement batteries.
APCRBC140
Number of battery modules 4 battery modules
Voltage for each battery module
Total voltage for the UPS
Ah rating
96 VDC
± 192 VDC
5 Ah per battery module
XLBP cable length 500 mm (19.7 in)
Battery module UPS XLBP
APCRBC140 SRT8KXLx/SRT8KRMXLx/SRT10KXLx/SRT10KRMXLx SRT192BP2/SRT192RMBP2
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U6
Electrical
CAUTION: To reduce the risk of fire, connect the UPS only to a circuit provided with recommended maximum branch
circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical
Code, Part I, C22.1.
Models Rating
Online Green Mode
SRT8KXLT
8 kVA / 8 kW 8 kVA
SRT8KRMXLT
SRT8KX LT-IEC
SRT8KR MXLT-IE C
SRT8KXLI
SRT8KRMXLI
SRT10KXLT
10 kVA / 10 kW 10 kVA
SRT10KRMXLT
SRT10K XLT- IEC
SRT10KRMXLT-IEC
SRT10KXLI
SRT10KRMXLI
Output
Output Frequency 50 Hz/60 Hz ± 3 Hz
Nominal Output
Vo l t ag e
SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI: 220 Vac / 230 Vac / 240 Vac
SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT: 208 Vac / 240 Vac
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC: 208 Vac / 240 Vac
Input
Input Frequency 40 Hz-70 Hz
Nominal Input
Vo l t ag e
SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI: 220 Vac / 230 Vac / 240 Vac
SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT: 208 Vac / 240 Vac
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC: 208 Vac / 240 Vac
7Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Front panel features
Rear panel features
Note: Refer to the table “Key to identify rear panel features” on page 9, that provides a key to the callout numbers for the
rear panel graphics depicted in this manual.
UPS Display Interface
panel
UPS battery compartment
doors x2
UPS battery connectors x4
Bezels x2
SRT8KXLT/SRT8KRMXLT/SRT10KXLT/SRT10KRMXLT
suo0796a
OUTPUT: 50/60Hz
208/240VAC
GROUP 1
20 AMP MAX
GROUP 2
20 AMP MAX
10 100
/
Reset
Con
so le Ne tw or k
USBSerial
EPO
1234
1234
NO
NC
HARDWIRED OUTPUT
GROUP 3
30 AMP MAX
suo0772a
192V DC
+
-
BATT COMM
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U8
SRT8KXLT-IEC/SRT8KRMXLT-IEC/SRT10KXLT-IEC/SRT10KRMXLT-IEC
SRT8KXLI/SRT8KRMXLI/SRT10KXLI/SRT10KRMXLI
GROUP 3
15 AMP MAX
HARD WIRED OUTPUT
10 100/
Reset
Co
nsole Ne twork
USBSerial
OUTPUT: 50/60Hz
208/240VAC
EPO
1234
1234
NO
NC
GROUP 2
20 AMP MAX
GROUP 1
20 AMP MAX
suo0770a
192V DC
+
-
BATT COMM
HARDWIRED OUTPUT
10 100/
Reset
Co
nsol e Networ k
USBSerial
OUTPUT: 50/60Hz
220/230/240VAC
EPO
1234
1 234
NO
NC
GROUP 2
16 AMP MAX
GROUP 1
16 AMP MAX
suo0771a
GROUP 3
10 AMP MAX
192V DC
+
-
BATT COMM
9Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Key to identify rear panel features
Network port Use the Network port to connect the UPS to the network.
Console port Use the Console port to configure the network management features.
Universal I/O port Use to connect:
• Temperature sensor AP9335T (supplied)
• Temperature/humidity sensor AP9335TH (not supplied)
• Relay input/output connector AP9810 (not supplied), supports two input contacts and one output relay
USB port The USB port is used to connect either a server for native operating system communications, or for
software to communicate with the UPS.
Note: Serial and USB communication should not be used simultaneously. Use either the Serial Com or
the USB port.
Serial Com The Serial Com port is used to communicate with the UPS.
Use only interface kits supplied or approved by APC by Schneider Electric. Any other serial
interface cable will be incompatible with the UPS connector.
EPO terminal The Emergency Power Off (EPO) terminal allows the user to connect the UPS to a central EPO system.
Controllable outlet
group 1, with
circuit breaker
Connect electronic devices to these outlets.
In the event an overload condition occurs, disconnect nonessential equipment.
Then reset the circuit breaker.
Controllable outlet
group 2, with
circuit breaker
Connect electronic devices to these outlets.
In the event an overload condition occurs, disconnect nonessential equipment.
Then reset the circuit breaker.
Controllable outlet
group 3, with
circuit breaker
Connect electronic devices to these outlets.
In the event an overload condition occurs, disconnect nonessential equipment.
Then reset the circuit breaker.
AC output
inspection panel
Remove the panel to inspect the output terminal block wiring configuration.
The terminal block is located behind the inspection cover.
Refer to “Wiring Specifications” on page 10 for hardwire specifications.
AC input
inspection panel
Remove the panel to inspect the input terminal block wiring configuration.
The terminal block is located behind the inspection cover.
Refer to “Wiring Specifications” on page 10 for hardwire specifications.
AC hardwire
knockouts
Remove the 38.1 mm (1.5 in) knockout panels for AC input and output hardwiring.
Install appropriate strain reliefs (not supplied).
Hardwire box
input/output
Remove the box to connect input and output wires to the hardwire terminal blocks.
Chassis ground
screws
The UPS and XLBPs have ground screws for connecting the ground leads.
Prior to connecting a ground lead, disconnect the UPS from mains power.
External battery
power and
communication
connectors
Use the external battery power and communication cables to connect the UPS and XLBP.
XLBPs provide extended runtime during power outages.
The UPS will automatically recognize up to 10 external battery packs.
SmartSlot The SmartSlot can be used to connect optional management accessories.
PRL COMM port This port is not used with these products.
Reset button Use the Reset button to restart the Network Management Interface.
Note: A restart of the Network Management Interface does not affect UPS operation.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U10
Operation
Wiring Specifications
CAUTION
RISK OF ELECTRIC SHOCK
• Adhere to all national and local electrical codes.
• Wiring should be performed by a qualified electrician.
• Install 1 1/2 in (38.1mm) Snap-In strain reliefs.
• The UPS must be wired into a branch circuit, equipped with a circuit breaker rated as specified in the tables
below.
• Actual wire size must comply with required ampacity and national and local electrical codes.
Select wire size based on wire insulation, installation method, and environmental conditions.
• Recommended terminal screw torque:
16 mm2 or 6 AWG = 5.09 Nm (45 lbf-in)
25 mm2 or 4 AWG = 5.09 Nm (45 lbf-in)
4 mm2 or 12 AWG = 3.969 Nm (35 lbf-in)
Failure to follow these instructions can result in minor or moderate injury.
Single Feed
System Wiring
Number
of
Phases
Voltage
Current Full
Load
(nominal)
External Input
Circuit Breaker Mains
(typical)
Wire Size
Mains
(typical)
SRT8KXLT
Input 1 208/240 Vac 47 A 60 A / 2-pole 16 mm2
or 6 AWG
Output 1 208/240 Vac 40 A 16 mm2
or 6 AWG
SRT10KXLT
Input 1 208/240 Vac 56 A 70 A / 2-pole 25 mm2
or 4 AWG
Output 1 208/240 Vac 49 A 16 mm2
or 6 AWG
SRT8KXLI
Input 1 220/230/240 Vac 44 A 63 A / 2-pole 16 mm2
or 6 AWG
Output 1 220/230/240 Vac 38 A 16 mm2
or 6 AWG
Input 3 380/400/415 Vac 15 A
44 A*
63 A / 4-pole 16 mm2
or 6 AWG
Output 1 220/230/240 Vac 38 A 16 mm2
or 6 AWG
11Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
* Phase 1 (L1) current while in bypass mode
SRT10KXLI
Input 1 220/230/240 Vac 54 A 80 A / 2-pole 25 mm2
or 4 AWG
Output 1 220/230/240 Vac 47 A 16 mm2
or 6 AWG
Input 3 380/400/415 Vac 18 A
54 A*
80 A / 4-pole 25 mm2
or 4 AWG
Output 1 220/230/240 Vac 47 A 16 mm2
or 6 AWG
Dual Feed
System Wiring
Number
of
Phases
Volt age
Current
Full Load
(nominal)
External
Input
Circuit
Breaker
Mains
(typical)
External
Input
Circuit
Bypass
Mains
(typical)
Wire Size
Mains
(typical)
Wire Size
Bypass
(typical)
SRT8KXLI
Input 1 220/230/240 Vac 44 A 63 A / 2-pole 63 A / 2-pole 16 mm2
or 6 AWG
16 mm2
or 6 AWG
Input 3 380/400/415 Vac 15 A 20 A / 4-pole 63 A / 2-pole 4 mm2
or 12 AWG
16 mm2
or 6 AWG
Output 1 220/230/240 Vac 38 A 16 mm2
or 6 AWG
16 mm2
or 6 AWG
SRT10KXLI
Input 1 220/230/240 Vac 54 A 80 A / 2-pole 80 A / 2-pole 25 mm2
or 4 AWG
25 mm2
or 4 AWG
Input 3 380/400/415 Vac 18 A 25 A / 4-pole 80 A / 2-pole 4 mm2
or 12 AWG
25 mm2
or 4 AWG
Output 1 220/230/240 Vac 47 A 16 mm2
or 6 AWG
16 mm2
or 6 AWG
Single Feed
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U12
Connect Equipment
Note: The UPS batteries will charge to 90% capacity in the first three hours of normal operation. Do not expect
full battery runtime capability during this initial charge period.
1. Connect the internal battery module. See Installation manual for details.
2. Connect the UPS to the building utility power. Refer to the UPS Installation Guide.
3. Connect equipment to the outlets on the rear panel of the UPS.
Refer to “Controllable Outlet Groups” on page 21.
Turn the UPS On/Off
The first time the UPS is turned on the Setup Wizard screen will run. Follow the prompts to configure UPS
settings. Refer to “Configuration” on page 16.
To turn on the UPS and all connected equipment, press the Power ON/OFF button on the display panel. Follow the
prompts to either turn the UPS on immediately or after a delay, then press OK.
NOTE: When there is no input power and the UPS is off, the cold start feature can be used to turn on the UPS and
connected equipment using battery power.
To perform a cold start press the Power ON/OFF button.
The display panel will illuminate and the Power ON/OFF button will illuminate red.
To turn on the output power press the Power ON/OFF button again. Select the prompt Turn ON with NO AC and
press OK.
To turn output power off, press the Power ON/OFF button. Follow the prompts to either turn the UPS off
immediately or after a delay, then press OK.
NOTE: Once the AC power has been turned off the UPS will continue operating on battery power for a short
period of time. To remove power completely press the Power ON/OFF button. Follow the prompt to select Internal
Power Off, then press OK.
CAUTION
RISK OF ELECTRIC SHOCK
• Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment.
• Disconnect internal and external batteries before installing or servicing the UPS or connected equipment.
• The UPS contains internal and external batteries that may present a shock hazard even when disconnected
from the mains.
• UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
• Disconnect equipment from the UPS before servicing any equipment.
• Do not use the UPS as a safety disconnect.
Do not use the UPS as a safety disconnect.
Failure to follow these instructions can result in minor or moderate injury.
13Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
UPS Display Interface
UPS Display Interface operation
Use the UP/DOWN buttons to scroll through the options. Press the OK button to accept the selected option. Press the
ESC button to return to the previous menu.
POWER ON/OFF button
Button illumination indications:
-No illumination, the UPS and the output
power are off
-White illumination, the UPS and the
output power are on
-Red illumination, the UPS is on and the
output power is off
Load icon
Disable/mute audible alarm icon
UPS status information
Operation mode icons
ESCAPE button
OK button
UP/DOWN buttons
Controllable outlet group status icons
Battery status icons
The icons on the LCD display interface screen may vary depending on the installed firmware version.
Load icon: The approximate load capacity percentage is indicated by the number of load bar
sections illuminated. Each bar represents 16% of the load capacity.
Mute icon: Indicates the audible alarm is disabled/mute.
UPS Status Information
The status information field provides key information on the status of the UPS.
The Standard menu will allow the user to select one of the five screens listed below. Use the UP/DOWN buttons to scroll
through the screens.
The Advanced menu will scroll through the five screens automatically.
• Input Voltage
• Output Voltage
• Output Frequency
•Load
• Runtime
In the case of a UPS event, status updates will be displayed defining the event or condition that has occurred.
The display screen illuminates amber to indicate a Message and red to indicate an Alert depending on the severity of the
event or condition.
su0870a
Output
230.0
v
On-Line
12 3
LOAD
LOAD
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U14
Operation Mode Icons
On-Line mode: The UPS is supplying conditioned mains power to connected equipment.
Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains
power as long as the input voltage and frequency are within the configured limits.
Green mode: When in Green mode mains power is sent directly to the load.
In the event of a mains power outage, there will be an interruption in power to the load of up to
10 ms while the UPS switches to On-Line or Battery mode.
When enabling Green mode consideration should be given to devices that may be sensitive to
power fluctuations.
UPS Status Icon
Battery mode: The UPS is supplying battery power to connected equipment.
The UPS has detected an internal fault with the battery. Follow the instructions on the screen.
The UPS has detected a critical fault with the battery. The battery is at the end of its life and has
to be replaced.
Indicates a UPS alert that requires attention.
Controllable Outlet Group Icons
Controllable Outlet Group Power Available: The number next to the icon identifies the
specific outlet groups that have available power.
Flashing icon indicates the outlet group is turning from OFF to ON with delay.
Controllable Outlet Group Power Not Available: The number next to the icon identifies
specific outlet groups that do not have available power.
Flashing icon indicates the outlet group is turning from ON to OFF with delay.
Battery Status Icons
Battery Charge Status: Indicates the battery charge status.
Battery Charge In Progress: Indicates the battery is charging.
X
15Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
LCD display interface angle adjustment
The angle of the LCD display interface can be adjusted for ease in viewing the displayed messages.
1. Remove the front bezel.
2. Locate the button on the bottom of the display interface panel.
3. Press the button and slide the bottom of the LCD display interface screen out. An audible click will be
heard when the screen reaches the maximum angle.
Menu overview
The UPS Display Interface has Standard and Advanced menu screens. The preference for Standard or Advanced
menu selections is made during initial installation and can be changed at any time through the Configuration
menu.
The Standard menus include the most commonly used options.
The Advanced menus provide additional options.
Note: Actual menu screens may differ by model and firmware version.
su0926a
Configuration Menus Overview
Main Menu
Status
Control
Configuration
Test And Diagnostics
Log
About
Config Menu
UPS
Battery
Outlets
Communication
Display
Status Menu***
UPS
Battery
Accessory
Control Menu**
UPS
Bypass Control
Outlet Group 1*
Outlet Group 2*
Clear Alarms
Test and Diagnostics Menu
UPS Self Test
Runtime Test
Alarm Test - Short
Alarm Test - Continuous
Log
Event Log
Battery
RBC Health
RBC Summary – Installed MMYY, Replace MMYY
Internal RBC’s, Battery Packs, External RBC’s
Charge %, Runtime
Temperature, Voltage
Internal Pack – Temperature
Internal Pack – Health
External Pack – Temperature
External Pack - Health
UPS**
Efficiency
Output Power - Watts, VA,Load %
Output - Voltage, Frequency, Current
Energy Usage
Battery - Charge %, Runtime
- Input Voltage, Frequency
Self TestUPS
Runtime Test
Outlet Group 1**
Turn On Immediately
Turn On With Delay
Turn Off Immediately
Turn Off With Delay
Reboot Immediately
Reboot With Delay
Shutdown Immediately
Shutdown With Delay
Outlet Group 2**
Turn On Immediately
Turn On With Delay
Turn Off Immediately
Turn Off With Delay
Reboot Immediately
Reboot With Delay
Shutdown Immediately
Shutdown With Delay
Bypass Control**
Go into Bypass
Go out of Bypass
Clear Alarms**
No Alarms Exist
UPS**
Turn On Immediately
Turn On With Delay
Turn Off Immediately
Turn Off With Delay
Reboot Immediately
Reboot With Delay
Shutdown Immediately
Shutdown With Delay
Outlets
Main Outlet
Outlet Group 1
Outlet Group 2
Outlet Group 3
Display
Language
Audible Alarm – Disable, Enable
LCD Backlight – Always On, Auto Dim, Auto Off
LCD Settings- Color, Brightness, Contrast
Menu type - Standard / Advanced
Time***
UPS**
Green Mode - Enable / Disable
Output Setting - Lower Volt, Upper Volt
Output Setting – Acceptable Frequency
Output Setting – Frequency Slew Rate
Bypass Settings - Lower Volt, Upper Volt
Bypass Settings – Frequency
Battery Settings – Low Runtime Alert
Self Test Schedule
Alert Setting - Site Wiring Fault
PDU model -
Standard, SRT008
Default Setting
Energy Meter*
Battery
Install Date
Replace Notification
Replace Battery Alarm
Communication
Network - IP Address mode, IPV4 Address
Modbus*- Enable / Disable, Address
SmartSlot- IP Address Mode, IPv4 Address***
UPS***
UPS Hardware
PDU Hardware
UPS Hardware - Serial No.
UPS Hardware - Manufacture Date
UPS Firmware – Revision
UPS – DSP Firmware
UPS – Comm Firmware
UPS Time
About Menu***
UPS
Battery
Accessory
Battery
RBC Summary - Installed MMYY, Replace MMYY
Battery – Firmware
Battery – Part No.
Menus are subject to change depending on the installed firmware version
* Available on the Advanced Menu Screens
** Options displayed will vary based on UPS state.
*** Options displayed will vary based on connected accessories.
**** Disabled when AP9629 card is installed in the UPS.
suo1432c
Accessory***
Smart Slot – Probe 1 Temperature
Smart Slot – Probe 1 Humidity
Smart Slot – Probe 1 Relay I/O Status
Smart Slot – Probe 2 Temperature
Smart Slot – Probe 2 Humidity
Smart Slot – Probe 2 Relay I/O Status
Accessory***
Network - MAC Address
Network - IP Address
Smart Slot - Serial No.
Smart Slot - Part No.
Smart Slot - Firmware
Smart Slot - MAC Address
Smart Slot – IPv4 Address
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U16
Configuration
UPS Settings
There are three ways to select UPS configuration options.
1. The first time the UPS is turned on the Setup Wizard screen will open. On each menu screen select the desired
settings. Press OK after each UPS setting is selected.
Note: The UPS will not turn on until all of the settings have been configured.
2. Main Menu/Configuration/UPS/Default Setting. This screen allows the user to reset the UPS to factory
default settings. Press OK after the UPS setting is selected.
Refer to “Configuration” on page 16 and “UPS Menu Overview” .
3. Configure settings using an external interface, such as the Network Management Web interface.
Startup configuration
Note: The configuration menu options vary according to the UPS models.
Function Description
Select the language required for the display interface.
Language options will vary by model and firmware version.
Options:
• English
•Francais
• Italiano
•Deutsch
•Espanol
• Portugues
• Japanese
•Russian
Select the output voltage.
Options will vary by model.
Options:
• 208 Vac
• 220 Vac
• 230 Vac
• 240 Vac
The Standard menu options are the most commonly used options.
The Advanced menu options will be used by IT professionals who need
detailed configuration and reporting information.
Language
Francais
Italiano
Setup Wizard
Voltage AC Setting
230 VAC
240 VAC
Setup Wizard
Menu Type
Advanced
Setup Wizard
17Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
General settings
Configure these settings at any time, using the UPS Display Interface, or the Network Management web Interface.
Parameters Default Value Options Description
Config
Menu
UPS
Green Mode Disabled Disable
Enable
Disable or enable Green mode operation
AC Setting NA
(see description)
XLI models: 220 V,
230 V, 240 V
XLT models: 208 V,
240 V
Set the output voltage for the UPS. This setting can only
be changed when the UPS output is off.
These settings may vary depending on the UPS model.
Default Value:
The value selected by the user during initial
startup. Reset to factory default does not change
the selected value.
Output
Lower
Acceptable
Voltage
184 V for 208 V output
198 V for 220 V output
207 V for 230 V output
216 V for 240 V output
208 V - 169 to 184 V
220 V - 186 to 198 V
230 V - 195 to 207 V
240 V - 204 to 216 V
If the UPS input voltage is between the lower acceptable
voltage and the higher acceptable voltage, the UPS will
operate in Green mode when enabled.
If the output voltage goes outside the acceptable range
the UPS will switch from Green mode to On-Line
mode or to Battery mode.
Output Upper
Acceptable
Voltage
220 V for 208 V output
242 V for 220 V output
253 V for 230 V output
264 V for 240 V output
208 V - 220 to 235 V
220 V - 242 to 253 V
230 V - 253 to 265 V
240 V - 264 to 270 V
Output
Frequency
Auto 50/60 ± 3 Hz Auto 50/60 ± 3 Hz
50 ± 0.1 Hz
50 ± 3.0 Hz
60 ± 0.1 Hz
60 ± 3.0 Hz
Set the output frequency for the UPS.
Output
Frequency
Slew Rate
1 Hz/Sec 0.5 Hz/Sec
1 Hz/Sec
2 Hz/Sec
4 Hz/Sec
Select the rate of change for output frequency in
Hertz per second.
Bypass Lower
Acceptable
Voltage
160 V 208 V - 160 to 184 V
220 V - 160 to 198 V
230 V - 160 to 207 V
240 V - 160 to 216 V If the UPS input voltage is between the lower acceptable
voltage and the higher acceptable voltage, the UPS can
enter Bypass mode when enabled.
Bypass Upper
Acceptable
Voltage
250 V for 208 V output
255 V for 220 V output
265 V for 230 V output
270 V for 240 V output
208 V - 220 to 250 V
220 V - 242 to 264 V
230 V - 253 to 270 V
240 V - 264 to 270 V
Bypass
Setting
Acceptable
Frequency
Wider Frequency
47 - 63 Hz
• Wider Frequency
47 - 63 Hz
• Use Output
Frequency Setting
The setting Wider Frequency, enables Bypass mode
operation for an input frequency range of
47-63 Hz.
Battery
Conserve
Mode
Enable Enable/Disable When enabled this setting conserves battery by
switching to Bypass source.
Disable
Bypass
No Yes/No The UPS will not go to Bypass mode.
When UPS detects a fault the load will be dropped.
Low Runtime
Alert
150 seconds 0 to 1800 seconds The UPS will emit an audible alarm when the remaining
runtime has reached this threshold.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U18
Config
Menu
UPS
Self Test
Schedule
Startup + every 14 days
since last test
Never
Startup
Startup + 14 days
Startup + 7 days
This is the interval at which the UPS will execute a Self
Te s t .
PDU Model Standard XLT model -
SRT008
Select the PDU model installed in the UPS for
proper operation of the PDU.
See the user documentation for the PDU model
SRT008 for details.
Default
Setting
No Yes/No Allows the user to restore the UPS factory default
settings.
Reset Energy
Meter
No Yes/No The Energy Meter stores information on UPS output
energy usage.
The Reset feature allows the user to reset the Energy
Meter to 0 kWh.
Config
Menu
Battery
Install Date Battery Installation Date Month-Year Enter the installation date of the RBCs.
Replacement
Notification
Time
183 days • 0-360 days
•-1
To set the Near End of Life alarm, select the number of
days before the estimated battery end of life.
When this date is reached the UPS will emit an alarm
and a message will appear on the UPS Display Interface
screen.
Example: Using the default value, the Near End of Life
alarm will occur 180 days before the estimated end of
life date.
To disable the notifications select -1.
Replacement
Battery
Alarm Time
14 days • 0-180 days
•-1
The Near End of Life alarm can be muted.
Enter the number of days between the time a Near End
of Life alarm is acknowledged and the next Near End
of Life alarm occurs.
To disable the notifications select -1.
Parameters Default Value Options Description
19Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Config
Menu
Display
Language English English
Francais
Italiano
Deutch
Espanol
Portugues
Japanese
Russian
Select the language required for the UPS Display
Interface.
Language options will vary by model and firmware
version.
Audible
Alarm
Enabled Disable
Enable
When audible alarms are disabled, the UPS will
never emit an audible alarm.
LCD
Back Light
Auto Dim Always On
Auto Dim
Auto Off
To conserve energy, the LCD back light illumination
dims or turns off when no events are active.
Full UPS Display Interface illumination returns when
the UPS changes status as a result of an event or when
any button on the UPS Display Interface is pressed.
LCD Setting Optimal Values Color
Brightness
Contrast
Adjust the brightness and contrast individually for each
LCD back light color.
Menu Type User Choice Standard
Advanced
The Standard menus include the most commonly used
options.
The Advanced menu options include all parameters.
Time UTC time
Universal Time
Coordinated (UTC) is a
coordinated time scale,
maintained by the
Bureau International des
Poids et Mesures
(BIPM)]
DD-MMM-YYYY
HH:MM:SS am/pm
For non-NC models only: Scroll through the fields to set
the time.
Note: Not applicable when AP9630/31/35 Network
Management Card (NMC) is connected to the UPS.
Parameters Default Value Options Description
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U20
Config
Menu
Outlets
Power On
Delay
0 seconds 0-1800 seconds Select the amount of time the controllable outlet groups
will wait between receiving the command to turn on and
actual startup.
Power Off
Delay
90 seconds 0-32767 seconds Select the amount of time the controllable outlet groups
will wait between receiving the command to shutdown
and actual shutdown.
Reboot
Duration
8 seconds 4-300 seconds Select the amount of time the controllable outlet groups
will remain off before the UPS will restart.
Minimum
Return
Runtime
0 seconds 0-32767 seconds Select the amount of battery runtime that must be
available before the controllable outlet groups will turn
on using battery power, after a shutdown.
Loadshed On
Battery
Disable Disable
Enable
To conserve battery power the UPS can disconnect
power from controllable outlet groups not in use.
To configure the disconnect delay time for this feature
use the Loadshed Time On Battery setting.
Loadshed
Time On
Battery
5 seconds 5-32767 seconds Select the amount of time the controllable outlet groups
will be allowed to function on battery power before
shutdown.
Loadshed On
Runtime
Disable Disable
Enable
To conserve battery power the UPS can disconnect
power from controllable outlet groups when the
Loadshed Runtime threshold is reached.
Loadshed
Runtime
0 seconds 0-3600 seconds When the selected runtime threshold is reached the UPS
will shutdown the controllable outlet groups.
Loadshed
Overload
Disable Disable
Enable
To conserve energy in the event of an overload condition
greater than 105% output, the controllable outlet groups
will immediately turn off. The controllable outlet groups
will only turn on again with a manual restart command
once the overload condition has been corrected.
Config
Menu
Network
Manage
IP Address
Mode
Manual, DHCP,
BOOTP
Refer to the Network Management Utility CD.
IP Address Program IP, Subnet,
Gateway
Config
Menu
Commun
ication
Modbus
Modbus Disable Disable
Enable
Allows the user to enable or disable the UPS Modbus
functionality
Modbus
Address
1 1 - 223 Allows the user to select the Modbus address
Parameters Default Value Options Description
21Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Controllable Outlet Groups
Controllable Outlet Groups provide battery backup power to connected equipment.
Overview
The controllable outlet groups can be configured using the Advanced menu options.
Refer to “General settings” on page 17.
The controllable outlet groups can be configured to independently turn off, turn on, shutdown, switch to Sleep mode, and
reboot connected equipment.
• Turn Off: Disconnect output power to connected equipment either immediately using the Turn Off Immediately
feature or after a configured delay using the Turn Off With Delay feature.
NOTE: Controllable outlet groups can be turned on only using the Turn O n feature.
• Tu rn On: Connect output power to connected equipment either immediately using the Turn On Immediately
feature or after a configured delay using the Turn On With Delay feature.
• Shutdown: Disconnects the power to connected equipment either immediately or after a configured delay.
Equipment reconnects after a configured delay when mains power becomes available and other configured
conditions are met.
Each controllable outlet group can be configured separately to allow power sequencing for equipment connected
to any controllable outlet group.
• Reboot: Disconnect the power to connected equipment either immediately or after a configured delay. Reconnect
equipment after a configured delay when either mains or battery power becomes available and other configured
conditions are met.
Each controllable outlet group can be configured separately to allow power sequencing for loads connected to any
controllable outlet group.
• Sleep: This mode is a reboot with an extended duration where a outlet(s) remain turned off.
Disconnect the power to connected equipment either immediately or after a configured delay. Reconnect
equipment after a configured delay when either mains or battery power becomes available and other configured
conditions are met.
Each controllable outlet group can be configured separately to allow power sequencing for equipment connected
to any controllable outlet group.
To configure Sleep mode use an external interface, such as the Network Management web interface.
• Automatically turn off or shutdown when certain conditions occur, based on user configurations set using the
Config Menu Outlets menus. Refer to “Configuration” on page 16
Connect controllable outlet groups
• Connect critical equipment to one controllable outlet group.
• Connect peripheral equipment to the other controllable outlet groups.
– To conserve battery runtime during a power outage, nonessential equipment can be configured to shut down.
Use Loadshed Time on Battery Enable/Disable and Loadshed Time on Battery Setting defined in the
General Settings section. Refer to “General settings” on page 17.
– If equipment has dependent peripherals that must restart or shut down in a specific sequence, such as an
ethernet switch that must restart before a connected server can be restarted, connect the devices to different
outlet groups. Each controllable outlet group can be configured independently of the other groups.
• Use the Configuration menus to configure how the controllable outlet groups will react in the event of a power
outage.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U22
Emergency Power Off
Overview
The Emergency Power Off (EPO) option is a feature that will immediately disconnect all connected equipment from mains
power. The UPS will immediately shut down and will not switch to battery power.
Connect each UPS to the EPO switch. In configurations where multiple units are connected in parallel, each UPS must be
connected to the EPO switch.
The UPS must be restarted for power to return to connected equipment. Press the ON/OFF button on the front panel of the
UPS.
Normally open contacts
1. If the EPO switch or relay contacts are normally open, insert the wires from the switch
or contacts at pins 1 and 2 of the EPO terminal block. Use 16-28 AWG wire.
2. Secure the wires by tightening the screws.
If the contacts are closed, the UPS will turn OFF and power will be removed from the load.
Normally closed contacts
1. If the EPO switch or relay contacts are normally closed, insert the wires from the switch
or contacts at pins 2 and 3 of the EPO terminal block. Use 16-28 AWG wire.
2. Insert a wire jumper between pins 1 and 2. Secure the wires by tightening the three
screws at positions 1, 2, and 3.
If the contacts are opened, the UPS will turn OFF and power will be removed from the load.
Note: Pin 1 is the power source for the EPO circuit, it provides a few milliampere of 24 V power.
If the normally closed (NC) EPO configuration is used, the EPO switch or relay should be rated for “dry” circuit
applications, the rating should be for low voltage and low current applications. This normally implies the contacts are gold
plated.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect the EPO interface only to other SELV circuits.
The EPO interface monitors circuits that have no determined voltage potential. SELV circuits are controlled by a switch or
relay properly isolated from mains power. To avoid damage to the UPS, do not connect the EPO interface to any circuit other
than a SELV circuit.
Use one of the following cable types to connect the UPS to the EPO switch.
• CL2: Class 2 cable for general use.
• CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
• CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
• CLEX: Limited use cable for use in dwellings and for use in raceways.
• Installation in Canada: Use only CSA certified, type ELC, (extra low voltage control cable).
• Installation in countries other than Canada and the USA: Use standard low voltage cable in accordance with national
and local regulations.
CAUTION
RISK OF ELECTRIC SHOCK
• Adhere to all national and local electrical codes.
• Wiring must be performed by a qualified electrician.
• Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
23Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Install a Ferrite Bead
The supplied ferrite bead must be installed between the supplied EPO terminal block and the EPO switch.
Connect to
EPO Switch
Ferrite Bead
EPO
Terminal
Block
25-35 mm
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U24
Network Management Interface
Introduction
The UPS has a network port and console port that can be used to access the Network Management Interface. The Network
Management Interface is very similar to an AP9630 Network Management Card (NMC) that is integrated into a UPS with
one universal input/output port.
The Network Management Interface and the AP9630 NMC have the same firmware, operation modes and interaction with
other APC products such as PowerChute Network Shutdown.
Refer to the Network Management Card utility CD supplied with this product.
Features
The Network Management Interface allows the UPS to function as a web based, IPv6 ready product.
The Network Management Interface can manage the UPS using multiple open standards such as:
The Network Management Interface:
• Provides UPS control and Self Test scheduling features.
• Provides data and event logs.
• Enables you to set up notifications through event logging, e-mail, and SNMP traps.
• Provides support for PowerChute Network Shutdown.
• Supports using a Dynamic Host Configuration Protocol (DHCP) or BOOTstrap Protocol (BOOTP) server to provide
the network (TCP/IP) values.
• Supports use of Remote Monitoring Service (RMS).
• Provides the ability to export a user configuration (.ini) file from a configured UPS, to one or more unconfigured
UPS without conversion to a binary file.
• Provides a selection of security protocols for authentication and encryption.
• Communicates with StruxureWare Central and InfraStruxure Manager.
• Supports one universal input/output port for connection to a:
– Temperature probe, AP9335T (supplied)
– Temperature/humidity sensor, AP335TH (optional)
– Relay input/output connector that supports two input contacts and one output relay, AP9810 Dry Contact I/O
Accessory (optional)
Hypertext Transfer Protocol (HTTP) Secure SHell (SSH)
Simple Network Management Protocol versions 1
and 3 (SNMPv1, SNMPv3)
Hypertext Transfer Protocol over Secure Sockets
layer (HTTPS)
File Transfer Protocol (FTP) Secure Copy (SCP)
Telnet Syslog
RADIUS
25Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Related Documents
The Network Management Card Utility CD contains the following documentation:
• UPS Network Management Card 2 User’s Guide
• Network Management Card Upgrade Utilities
• Security Handbook
• PowerNet Management Information Base (MIB) Reference Guide
IP Address Configuration
The default TCP/IP configuration setting DHCP, assumes that a properly configured DHCP server is available to provide
TCP/IP settings to the Network Management Interface.
If the Network Management Interface obtains an IPv4 address from a DHCP server, use the UPS Display Interface menus
About/Interface, to see the address.
To setup a static IPv4 address use the UPS Display Interface Config menu. Set the IP address Subnet Mask and Gateway
from the Config menu.
See the User’s Guide on the Network Management Card Utility CD for user information about the Network Management
Interface and for setup instructions.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U26
Smart Battery Management
Definitions
• Battery Module: A string of battery cells arranged to produce a battery assembly with a connector.
• Replaceable Battery Cartridge (RBC): An APC battery cartridge consisting of two battery modules. Replacement
RBCs can be ordered from the APC by Schneider Electric Web site, www.apc.com.
• Smart External Battery Pack (XLBP): An enclosure that contains RBC(s) and battery management electronics.
• User Interface (UI): Any interface by which a user can interact with the system. This may include a UPS display
interface, a network management interface or PowerChute™ Network Shutdown software.
NOTE: Do not use a battery that is not APC approved.
The system will not detect the presence of a non APC approved battery and may adversely affect the operation of
the system.
Use of a non APC approved battery will void the manufacturer warranty.
Features
Smart Battery Management provides the following features:
• Monitors and informs the user of the health of each RBC.
• Monitors and shows on the UPS Display Interface screen, the date for the end of useful life for each RBC.
• The UPS emits an alarm and shows a message on the UPS Display Interface screen to indicate the estimated
battery end of life. On the UPS Display Interface screen the user can set the number of days before the alarm is
heard and the message appears on the UPS Display Interface screen.
• Automatically detects the addition or removal of XLBPs and RBCs.
• Monitors the internal temperature of each XLBP and automatically adjusts the battery charging.
Maintenance
• RBC maintenance: The APC RBC uses sealed lead acid battery cells and does not require maintenance.
• Runtime Test (Calibration): This should be performed anytime the steady state load is changed significantly, for
example a new server is added to or removed from the UPS load.
• Battery health monitoring: The battery energy output and voltage are monitored to assess the health of the
installed batteries when the UPS is operating on battery.
Battery health monitoring is done during a UPS Self Test, a Runtime Calibration Test, and when the UPS is
operating on battery power.
The UPS can be configured to perform periodic, automatic Self Tests.
End of useful life
• Near end of life notification: A warning message will appear on the UPS display interface screen when each
RBC is approaching the end of its useful life. For configuration details refer to Replacement Notification Time
and Replacement Battery Alarm Time.
The estimated replacement date for each RBC is available through the UI.
• Needs replacement notification: The UPS display interface screen shows when RBC replacement is required.
The RBC must be replaced as soon as possible.
When an RBC requires replacement, the UPS display interface may recommend that additional RBCs be replaced
if they will soon reach the end of their useful life.
Note: Continued operation after end of useful life notification may cause damage to the batteries.
• Recycling: Remove the RBC from the XLBP. Recycle the RBC. Do not disassemble an RBC.
27Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Replace the RBCs in a UPS
An RBC should only be disconnected or removed from the UPS temporarily as part of the battery replacement
procedure.
• Disconnect all connected battery modules in the UPS. Slide the RBCs out of the UPS.
• Slide the new RBCs into the UPS and connect the battery modules to the UPS.
• Securely connect each battery module. Press the battery connector into the UPS until it is firmly connected.
A battery that is not fully connected will cause erratic UPS operation, abnormal error messages and connected
equipment may not receive battery power during power outages.
• After installing the RBC, the UPS display interface may prompt the user to verify the status of the replaced
battery modules. If the battery module is new, respond YES. If the battery module is not new, respond NO.
Recommended actions after installing new RBCs
• Verify that the UPS is connected to input power and the output power is turned on. See “Operation” on page 10
for instructions.
• Perform a UPS Self Test.
• Verify on the UPS display interface that the installation dates for the replaced RBCs are set to the current date.
The installation dates can be changed manually on the UPS display interface.
If all RBCs have been replaced at the same time, all installation dates can be changed simultaneously.
For configuration details refer to Battery Install Date on page 19 of this manual.
• Allow the system to charge for 24 hours to ensure full runtime capability.
XLBP installation and replacement
Refer to the External Battery Pack Installation Guide for installation and replacement instructions.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U28
Troubleshooting
Use the table below to solve minor installation and operation problems.
Refer to the APC by Schneider Electric Web site, www.apc.com for assistance with complex UPS problems.
The UPS features firmware that can be upgraded.
Go to the APC by Schneider Electric Web site, www.apc.com/Support, or contact your local Customer Care
Center for more information.
Problem and Possible Cause Solution
UPS is not turning on or there is no output
The UPS is not connected to mains
power.
Be sure the power cable is securely connected to the UPS and to the mains
power supply.
The UPS display interface screen shows
very low or no mains power.
Check the mains power supply to verify acceptable power quality.
There is an internal UPS alert or warning. The UPS Display Interface screen will show a message to identify the alert or
warning and corrective action.
UPS emits an audible alarm
Normal UPS operation when running on
battery power.
The UPS is operating on battery power.
Refer to the status of the UPS as shown on the UPS Display Interface screen.
Press any key to mute all alarms.
The UPS emits an audible alarm and has
a red or amber back light on the UPS
Display Interface screen.
An Alarm or Warning condition exists.
Refer to the display interface screen for information.
UPS does not provide expected backup time
The UPS batteries are weak due to a
recent power outage or they are near the
end of service life.
Charge the batteries. Batteries require recharging after extended outages and
wear out faster when put into service often or when operated at elevated
temperatures. If the batteries are near the end of service life, consider
replacing the batteries even if the Replace Battery message is not displayed.
The UPS is experiencing an overload
condition.
The connected equipment exceeds the specified maximum load. Refer to the
APC by Schneider Electric Web site, www.apc.com for product
specifications.
The UPS will emit a sustained audible alarm until the overload condition is
corrected.
Disconnect nonessential equipment from the UPS to correct the overload
condition.
29Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
UPS operates on battery power while connected to mains power
The input circuit breaker has tripped. Reduce the load on the UPS. Disconnect nonessential equipment and reset the
circuit breaker. Check the circuit breaker rating for the connected equipment.
There is very high, very low, or distorted
input line voltage.
Navigate to the UPS Display Interface screen that shows input voltage. Verify
that the input voltage is within specified operating limits.
If no input voltage is indicated on the UPS Display Interface screen, contact
Customer Support through the APC by Schneider Electric Web site,
www.apc.com.
The UPS Display Interface screen shows
the message Waiting for Minimum
Runtime.
The UPS has been configured to operate for a specified period of runtime.
The setting can be changed through the Config/UPS menus.
UPS Display Interface Status screen shows Overload and the UPS emits a sustained audible alarm
The UPS is experiencing an overload
condition.
The connected equipment exceeds the maximum load rating for the UPS.
The UPS will emit a sustained audible alarm until the overload condition is
corrected.
Disconnect nonessential equipment from the UPS to correct the overload
condition.
UPS Display Interface Status screen shows UPS is operating in Bypass mode
The UPS received a command to operate
in Bypass mode
No action is required.
The UPS has automatically switched to
Bypass mode due to an internal UPS
alert or warning.
The UPS Display Interface screen will show a message to identify the alert or
warning and corrective action.
UPS Display Interface is red or amber and shows an alert or warning message
The UPS emits a sustained audible alarm
The UPS has detected a problem during
normal operation.
Follow the instructions on the UPS Display Interface screen.
Press any key to mute all alarms.
The UPS Display Interface screen shows
the message Disconnected Battery.
Be sure the battery cables are securely connected.
Perform a UPS Self Test to be sure the UPS detects all connected batteries.
To perform a UPS Self Test use the UPS Display Interface menu option Test
and Diagnostics.
The UPS Display Interface screen shows
the message Replace Battery.
Replace all of the batteries. Contact APC by Schneider Electric customer
support.
Problem and Possible Cause Solution
The UPS display turns red or amber, displays an alert message, and emits a sustained audible alarm
Red illumination indicates a UPS alarm that requires immediate attention
Amber illumination indicates a UPS alarm that requires attention
There is an internal UPS alert or warning. Do not attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
The UPS has detected a Site Wiring
Fault.
Check the AC mains neutral connection. Correct the building site wiring
fault.
The UPS is experiencing an overload
condition.
Reduce the load on the UPS. Disconnect nonessential equipment.
The Replace Battery alert is displayed
The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a
UPS Self Test. If the problem persists after recharging, replace the battery.
The replacement battery is not properly
connected.
Be sure the battery cable is securely connected.
Problem and Possible Cause Solution
1/1
Error P.05
Contact Customer Support
Output Off
123
2/2
Output Off
123
Site Wiring Fault
1/1
Output Overload
Backup Not Available
Bypass
123
31Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U
Transport
1. Shut down and disconnect all connected equipment.
2. Disconnect the unit from mains power.
3. Disconnect all internal and external batteries (if applicable).
4. Follow the shipping instructions outlined in the Service section of this manual.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact APC by Schneider Electric Customer Support through the APC by
Schneider Electric Web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers
are located on the rear panel of the unit and are available through the LCD display on select models.
b. Call Customer Support. A technician will attempt to solve the problem over the phone. If this is not
possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric
Web site for country specific instructions.
3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained
in transit is not covered under warranty.
Note: Before shipping, always disconnect battery modules in a UPS or external battery pack.
The disconnected internal batteries may remain inside the UPS or external battery pack.
4. Before shipping, always disconnect all battery modules in a UPS or external battery pack.
5. Write the RMA# provided by Customer Support on the outside of the package.
6. Return the unit by insured, prepaid carrier to the address provided by Customer Support.
Smart-UPS On-Line SRT8K/10K Tower/Rack-Mount 6U32
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and
workmanship for a period of three (3) years excluding the batteries, which are warranted for two (2) years from the
date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole
option, any such defective products. Repair or replacement of a defective product or part thereof does not extend
the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days
of purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the
product does not exist or was caused by end user or any third person misuse, negligence, improper installation,
testing, operation or use of the product contrary to SEIT recommendations of specifications. Further, SEIT shall not
be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or
inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5)
exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product
where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY
OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR
FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND
FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND
NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR
OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL
OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE
SEIT’S SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT
EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE
LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES,
ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR
STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY
OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST
PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE
OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY
THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT OR DEATH OR
PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT
MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY
APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from
customer support. Customers with warranty claims issues may access the SEIT worldwide customer support
network through the APC by Schneider Electric Web site: www.apc.com. Select your country from the country
selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer
support in your region. Products must be returned with transportation charges prepaid and must be accompanied by
a brief description of the problem encountered and proof of date and place of purchase.
3/2019EN 990-4506D
APC™ by Schneider Electric
Worldwide Customer Support
Customer support for this or any other APC™ by Schneider Electric product is available at no charge in any of
the following ways:
• Visit the APC web site to access documents in the APC by Schneider Electric Knowledge Base and to
submit customer support requests.
–www.apc.com (Corporate Headquarters)
Connect to localized APC web site for specific countries, each of which provides customer support
information.
–www.apc.com/support/
Global support searching APC by Schneider Electric Knowledge Base and using e-support.
• Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
– Local, country specific centers: go to www.apc.com/support/contact for contact information.
– For information on how to obtain local customer support, contact the APC by Schneider Electric
representative or other distributor from whom you purchased your APC by Schneider Electric
product.