Table of Contents
- Installation Guide Smart-UPS™ On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI
- Important Safety Messages
- Product Handling Guidelines
- Safety and General Information
- Overview
- Package Contents
- Specifications
- Rack-Mount Installation
- Tower Installation (limited to one battery pack)
- Connect Battery and Ground Cables
- Smart Battery Management
- Troubleshooting
- Limited Factory Warranty
- APC by Schneider Electric Worldwide Customer Support
APC XBP48RM1U-LI User Manual
Displayed below is the user manual for XBP48RM1U-LI by APC which is a product in the UPS Batteries category. This manual has pages.
Related Manuals

Installation Guide Smart-UPS™ On-Line
External Battery Pack
XBP48RM1U-LI/XBP48RM1U2-LI
Important Safety Messages
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during
installation and maintenance of the External Battery Pack (XLBP).
Read the instructions carefully to become familiar with the equipment before trying to install, operate, service or
maintain it. The following special messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol either to a “Danger” or “Warning” safety label indicates that an electrical
hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible injury or death.
Product Handling Guidelines
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
<18 kg
<40 lb
18-32 kg
40-70 lb
32-55 kg
70-120 lb
>55 kg
>120 lb

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI2
Safety and General Information
• Adhere to all national and local electrical codes.
• Changes and modifications to this unit not expressly approved by APC by Schneider Electric could void the
warranty.
• This unit is intended only for indoor use in a controlled environment.
• Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
• Allow adequate space for proper ventilation.
• The battery typically lasts for five to eight years. Environmental factors impact battery life. Elevated ambient
temperatures, poor quality mains power, and frequent short duration discharges will shorten battery life.
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the XLBPs.
• UPS models will recognize external battery packs connected to the UPS. See product manual for details.
Note: For each XLBP added, increased recharge time will be required.
• Always recycle used batteries.
• Recycle the package materials or save them for reuse.
Battery safety
• Schneider Electric uses Lithium Ion (NMC) batteries. Under normal use and handling, there is no contact with
the internal components of the battery.
• CAUTION: Before installing or replacing the batteries, remove conductive jewelry such as chains,
wrist watches and rings. High energy through conductive materials could cause severe burns.
• CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
• CAUTION: Do not open the battery pack enclosure. Doing so will expose the cell terminals which pose an
energy hazard.
Overview
• To verify that installation of an external battery pack (XLBP) has been successful, go to the UPS display
interface.
Perform a Visible Alarm Test to determine if the XLBP is recognized by the UPS.
The green LED on the XLBP will illuminate if successful communication has been established.
• When viewing the status of an XLBP on the UPS display interface screen, the LED on the corresponding XLBP
will flash.

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI 3
Package Contents
Inspect the contents upon receipt. Notify the carrier and dealer if there is damage.
Specifications
For additional specifications, refer to the APC by Schneider Electric web site at www.apc.com.
Environmental
Physical
Ground cable
2 pan head screws to secure the
ground cable
Communication cable Rail Kit with instructions and hardware
for installing rails in a rack
1 pan head screw to secure the XLBP battery
cable connector to an XLBP or to the UPS.
• 1 pair rack-mount bracket
• 4 flat head screws to secure rack-mount brackets to the XLBP
• 4 ornamental screws to secure the rack-mount bracket to the rack
4 flat head screws to secure rack-mount
brackets to XLBP
Te m pe r a tu r e Operating 0° to 40° C (32° to 104° F)
Storage -15° to 45° C (5° to 113° F)
Elevation Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (49,212 ft)
Humidity 0% to 95% relative humidity, non-condensing
Protection Class IP 20 rating
Note: Charge the battery packs every six months during storage.
The battery pack is heavy. Follow all lifting guidelines.
Unit weight, without packaging 13 kg (28.7 lb)
Unit weight, with packaging 16.4 kg (36.2 lb)
Rack-mount unit dimensions without packaging
Height x Width x Depth
43 mm x 432 mm x 521 mm
1.7 in x 17 in x 20.5 in
Unit dimensions with packaging
Height x Width x Depth
200 mm x 600 mm x 850 mm
7.9 in x 23.6 in x 33.5 in
The model and serial numbers are on a small label located on the rear panel.
suo
1273a
x4
x4

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI4
Battery
WARNING
RISK OF CHEMICAL HAZARD AND EXCESSIVE HEAT
• Replace the battery pack at least every 8 years.
• Replace the battery pack immediately when the UPS indicates battery replacement is necessary.
• Replace battery pack at the end of its service life.
• Replace battery packs with the same type of batteries as originally installed in the equipment.
• Replace the battery packs immediately when the UPS indicates a battery over-temperature condition.
Power off the UPS, unplug it from the AC input, and disconnect the battery packs. Do not operate the
UPS until the battery packs have been replaced.
Failure to follow these instructions can result in minor or moderate injury
Replacement battery pack
Refer to the appropriate replacement battery user manual for installation
instructions.
Contact your dealer or go the APC by Schneider Electric web site,
www.apc.com for information on replacement battery pack.
XBP48RM1U-LI XBP48RM1U2-LI
Note: The UPS does not support any other make/
type of battery packs.
Battery type Lithium Ion NMC chemistry
Typical energy capacity 600 watt-hours
Maximum continuous discharge rate 2 kW 3 kW
Maximum charge rate
Note: Battery pack will automatically disconnect to protect cells if
charge current exceeds 12 A.
Note: Around 0º C, battery pack will automatically limit charge current
to approximately 400 mA to protect the cells.
12 A
Battery capacity 12 Ah
Charge voltage for full capacity 58.1 VDC
Applicable UPS models
SRT1000UXI-NCLI
SRT1500UXI-NCLI
SRT1000UXI-LI
SRT1500UXI-LI
SRT3000UXI-NCLI
SRT2200UXI-NCLI
SRT3000UXI-LI
SRT2200UXI-LI
Battery power cable length 600 mm (23.6 in)
Battery communication cable length 300 mm (11.8 in)

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI 5
Rack-Mount Installation
UPS model may differ in appearance from those depicted in these graphics.
The XLBP installation process is identical for all models.
Refer to the rail kit Installation Guide for instructions on rail installation.
CAUTION
RISK OF FALLING EQUIPMENT
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• Always use the recommended number of screws to secure brackets to the XLBP.
• Always use the recommended number of screws to secure the XLBP to the rack.
• Always install the XLBP at the bottom of the rack.
• Always install the XLBP below the UPS in the rack.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
Secure four brackets to the XLBP.
Use two screws in each bracket. Install the 1U Rail Kit included with the UPS. Refer to
the installation instructions provided with the rail kit.
Slide the XLBP into the rack.
Secure the XLBP to the rack.
Use one screw in each bracket. Install UPS bezel
x2
x2
x2
x2
suo1260b
su
o1261a
suo1262
a
suo1263a

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI6
Tower Installation (limited to one battery pack)
CAUTION
RISK OF FALLING EQUIPMENT
• In the tower configuration, always mate one XLBP to the UPS.
• The equipment is heavy.
• Always practice safe lifting techniques adequate for the weight of the equipment.
Failure to follow these instructions can result in minor or moderate injury
suo1264a
suo1
265a
suo1266a
suo1267a
x2
x2
suo1268a

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI 7
Connect Battery and Ground Cables
Connect ground cables
Connect one external battery pack cable and communication cable
Note: Secure the communication cable with the UPS. The UPS will display inaccurate runtime if this connection is not
secure.
CAUTION
RISK OF ELECTRIC SHOCK
Ground both the UPS and the battery pack.
Failure to follow these instructions can result in minor or moderate injury
suo1269a
GRO UP 2
10 AMP MAX
GR OUP 1
10 AMP MAX
GRO UP 2
10 AMP MAX
GROUP 1
10 AMP M AX
suo1270a

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI8
External battery pack cable and communication cable connections for one UPS and two
XLBPs
Smart Battery Management
Definitions
• Smart External Battery Pack (XLBP): An enclosure that contains cells and battery management electronics.
Replacement XLBP can be ordered from the APC by Schneider Electric web site, www.apc.com.
• User Interface (UI): Any interface by which a user can interact with the system. This includes a UPS display
interface.
NOTE: Do not use a battery that is not APC by Schneider Electric approved.
The system will not detect the presence of a non APC by Schneider Electric approved battery and may adversely
affect the operation of the system.
Use of a non APC by Schneider Electric approved battery will void the manufacturer warranty.
Maintenance
• Battery health monitoring: The battery energy output and voltage are monitored to assess the health of the
installed batteries when the UPS is operating on battery.
Battery health monitoring is done during a UPS Self Test, a Runtime Calibration Test, and when the UPS is
operating on battery power.
The UPS can be configured to perform periodic, automatic Self Tests.
suo1271a

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI 9
End of useful life
• Near end of life notification: A message will appear on the UPS display interface screen when each XLBP is
approaching the end of its useful life. For configuration details refer to Replacement Notification Time and
Replacement Battery Alarm Time in the UPS Operation Manual.
• Needs replacement notification: The UPS display interface screen shows when XLBP replacement
is required. The XLBP must be replaced as soon as possible.
• Recycle the XLBP. Do not disassemble.
Recommended actions after installing new XLBPs
Refer to the UPS Operation Manual for details on Test and Diagnostics Menu options for the following tests:
• Self Test
• Runtime Test
• Visible Alarm Test
The following actions should be performed after installing a new XLBP:
• Verify that the UPS is connected to input power and output power is turned on.
• When a new XLBP is installed, verify that the XLBP is detected by the system.
– Perform a UPS Visible Alarm Tes t.
– Check that the LED on all installed XLBPs is lit.
– Allow the XLBP to charge for at least 24 hours.
• Verify that the UPS load is greater than 400 watts. This can be verified through the UPS display interface.
• Perform a UPS Self Test.
• If at the time of XLBP installation UPS input power is not available, turn on the UPS output from battery power
for 30 seconds. This will allow the UPS to detect all installed XLBPs.
Refer to the UPS Operation Manual for instructions on how to turn the UPS on and off.
• Verify on the UPS display interface that the installation dates for the replaced XLBPs are set to the current date.
The installation dates can be changed manually on the UPS display interface.
For configuration details refer to Battery Install Date in the UPS Operation Manual.
• Allow the system to charge for 24 hours to ensure full runtime capability.
• Initiate a Runtime Calibration Test through the UI.
User interface
View notifications: The status of connected XLBPs can be viewed using the UPS display interface menu options.
• XLBP Status LED: The XLBP LED illuminate pattern indicates three possible states.
–Off: XLBP IS not powering / communicating with UPS. Power / Communication cable is not connected.
–Solid red: The XLBP is not functional.
–Flashing green and solid red: user accessing the non functional XLBP from UI
•Flashing green: user accessing the functional XLBP from UI
•Solid green: Healthy functional XLBP
•Green LED flashing at a faster rate: XLBP firmware upgrade in progress
•For identification purposes each XLBP is automatically assigned a number.
To verify the number of a specific XLBP, use the UPS display interface menu options.
Select an XLBP number. The LED will flash on the XLBP assigned to that number.

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI10
• XLBP LED test: From the UPS display interface, LED functionality can be tested by executing a Visible
Alarm Test. This command causes the LED on each connected XLBP to flash.
• System interfaces: Battery status, alerts, and measurements are shown on the UPS display interface
screen. Refer to the UPS Operation Manual.
Troubleshooting
Issues Possible Cause Solution
XLBP green LED
flashes.
• The UPS display interface is
requesting XLBP status
•Visible Alarm Test has been
requested by the UPS
• XLBP firmware upgrade is in
progress
No action is necessary.
XLBP red LED
remains illuminated.
XLBP has detected a potential
hardware error
• Contact APC by Schneider Electric Customer Support.
XLBP is not
recognized by UPS.*
• XLBP has detected a
communication issue
• XLBP has detected a potential
hardware error
• Be sure the battery power connections to the XLBPs are
secure.
• Be sure the communication cable connection between the
XLBPs and the UPS are secure.
• Perform a Visible Alarm Test to verify that the LED
flashes.
• If the detected issue persists, contact APC by Schneider
Electric Customer Support.
suo1272a
XLBP Status LED

Smart-UPS On-Line External Battery Pack XBP48RM1U-LI/XBP48RM1U2-LI 11
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship
for a period of five (5) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing
or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts
thereof does not extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of
purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product
does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation, testing,
operation or use of the product contrary to SEIT recommendations or specifications. Further, SEIT shall not be liable
for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical
voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6)
theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been
altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY
OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR
FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND
FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO
OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT’S RENDERING OF TECHNICAL OR OTHER
ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE
LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY
THIRD PARTIES.
UPS display interface
shows XLBP
disconnected
message.*
• Power cable / communication cable
is not securely connected to an
XLBP or to the UPS
• XLBP has detected a hardware error
• Be sure the battery connections to the XLBPs are secure.
• Perform a Visible Alarm Test to verify that the LED
flashes.
• If the detected issue persists, contact APC by Schneider
Electric Customer Support.
XLBP red LED
illuminates and green
LED flashes
• XLBP is not functional and the UPS
display is requesting XLBP Status
• Contact APC by Schneider Electric Customer Support.
* Refer to the troubleshooting section in the UPS operation manual for details.
Issues Possible Cause Solution

© 2018 APC by Schneider Electric. APC, the APC logo, and Smart-UPS are owned by Schneider
Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their
respective owners.
EN 990-91021A
10/2018
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE
FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING
OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES
ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY
OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES.
SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE,
WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF
SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR
OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT’S LIABILITY
FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT
MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY
APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer
support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the
APC by Schneider Electric web site: www.apc.com. Select your country from the country selection drop down menu.
Open the Support tab at the top of the web page to obtain information for customer support in your region. Products
must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem
encountered and proof of date and place of purchase.
APC by Schneider Electric
Worldwide Customer Support
Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the
following ways:
• Visit the APC by Schneider Electric web site to access documents in the APC by Schneider Electric
Knowledge Base and to submit customer support requests.
–www.apc.com (Corporate Headquarters)
Connect to localized APC by Schneider Electric web sites for specific countries, each of which
provides customer support information.
–www.apc.com/support/
Global support searching APC by Schneider Electric Knowledge Base and using e-support.
• Contact APC by Schneider Electric Customer Support Center by telephone or e-mail.
– Local, country specific centers: go to www.apc.com/support/contact for contact information.
– For information on how to obtain local customer support, contact the APC by Schneider Electric
representative or other distributor from whom you purchased your APC by Schneider Electric
product.